Mini VRF SYSTEM
Control Functions
• 
• 
• 
11-2. Inverter Compressor
11-3. CT Circuit Detection Failure
12. Pressure Sensor Failure
This system includes a high-pressure sensor.
12-1. High-Pressure Sensor Failure
Connector disconnection or displacement failure is judged according to the relationship between the high-pressure
sensor temperature, which is detected by the high-pressure sensor, and the various temperature thermistors.
However, if the pressure rises suddenly, a high-pressure sensor failure warning may be judged before the high-
pressure sensor activates. Therefore check the following before determining that a pressure sensor failure has
occurred:
Has the service valve been left open?
Is there a blocked circuit?
Is there leakage of refrigerant into stopped outdoor units?
Also check the difference between the high-pressure pressure as measured by a manifold gauge and the pressure
as detected by the pressure sensor.
13. 4-Way Valve Failure [L18]
When a 4-way valve coil failure, coil disconnection or similar failure occurs, a judgment is made automatically from
the operating conditions, and an alarm is output.
Alarm
Description
P16
Occurs when overcurrent (32.5 A) is detected during normal 
operation.
P29
Occurs when a missing phase or overcurrent (48 A) is detected 
when the inverter compressor starts.
H31
Occurs when the HIC detects overcurrent (75 A), and when an 
abnormal temperature (150°C) is reached.
The inverter current values include primary current and secondary current. 
Alarm judgment uses both of these current values. However, in general the secondary 
current is higher than the primary current.
Alarm
Description
H03
Occurs when an open circuit is detected in the inverter
compressor CT circuit.
Alarm
Description
F16
High-pressure sensor failure
Compressor 1
(inverter compressor)
If the operating frequency of the inverter compressor is low, the current value is also low. 
As a result, this alarm is detected only when the compressor is stopped.
11. Current Protection
12. Pressure Sensor Failure
13. 4-Way Valve Failure [L18]
SM830195-03_Mini VRF SYS.indb   19
SM830195-03_Mini VRF SYS.indb   19
2014/09/04   18:14:07
2014/09/04   18:14:07
1 - 20
1
Mini VRF SYSTEM
Control Functions
14. Servicing and Maintenance Functions
(1)
(2)
The below functions are available, and are selected by the outdoor unit EEPROM settings.
14-1. Outdoor Unit Noise Countermeasures (outdoor Quiet mode function)
This function reduces the operating noise to lessen the noise produced by the outdoor unit. When this mode is
selected, noise reduction is given priority during operation, and the outdoor fan mode and compressor operating
frequency are restricted (to approximately 80% of capacity).
The following two operations are required in order to engage this mode. (This mode cannot be engaged when nei-
ther (1) nor (2) below has been completed.)
Outdoor unit EEPROM settings
Outdoor unit EEPROM 05 can be set from 0 to 1.
Short-circuit the “SILENT”2P pin on the outdoor unit PCB.
14-2. Slime Countermeasure:EEPROM 0C (set only on the main unit)
14-3. Delayed Start for Each System:Outdoor EEPROM 3E
The operation start time can be delayed according to the set system addresses.
This setting reduces voltage drops by preventing multiple systems from starting at the same time when operation is
restarted after recovery when multiple operating systems were stopped due to a power outage or other cause.
Noise reduction mode is engaged constantly when this pin is short-circuited. To operate in noise reduction 
mode only at night, or for similar control at other times, use an external timer (field supply).
This setting controls the operation of the drain pump.
EEPROM
setting
Max. fan
mode
Capacity ratio
Effect
Normal operation (setting at time of factory shipment)
100%
14
12
5 and 6 hp units. Noise reduced by approx. 3 dB from the catalog value.
Only 4 hp unit. Noise reduced by approx. 3 dB from the catalog value.
1
11
0
Approx. 80%
EEPROM
setting
Details of operation
Normal operation (setting at time of factory shipment)
1
0
2
Drain pump operates for 20 minutes at 2-hour intervals
Drain pump operates for 20 minutes, at intervals of 20 minutes
3
Drain pump operates continuously
EEPROM
setting
Effect
Delayed start is not performed (setting at time of factory shipment)
System address: Delay in seconds before start
2
1
0
3
Start after System address × 2 seconds
Start after System address × 3 seconds
Operating mode
Discharge temperature control value
Change method
Cooling
12
Enter shift value 
for indoor EEPROM 
setting “1C.”
Heating
50
Enter shift value 
for indoor EEPROM 
setting “1D.”
The method is the same as ordinary indoor unit discharge temperature shift.
<Reference> Indoor unit discharge temperature control
SM830195-03_Mini VRF SYS.indb   20
SM830195-03_Mini VRF SYS.indb   20
2014/09/04   18:14:07
2014/09/04   18:14:07
1 - 21
1
Mini VRF SYSTEM
Control Functions
15. Demand Control
15-1. Demand Control
15-2. Demand Display Selection Function EEPROM : 1E
Demand terminal block (optional CZ-CAPDC3) or Seri-Para I/O unit (optional CZ-CAPDC2) must be connected 
in order to perform demand control. 
The current limitation values can be set by changing either contact.
* The rated current indicates the current value that is listed in the catalog or service manual.
During setting in LV1-LV3,
(demand-activated) displays on the remote controller of the indoor unit.
*
*
*
In respect of connection method for demand terminal block and Seri-Para I/O unit, refer to the installation 
instructions supplied with the units.
XX% is possible to change among 40 to 100% (5% interval scale) by the indoor unit EPROM.
Outdoor Unit EEPROM Setting :  The display mark for demand function is selectable by changing 1E as shown 
below.
[1A]:100% at shipment /  [1B]:70% at shipment
It is also possible to make setting that the display (symbol of demand-activated) is concealed as shown 
in the following table.
: Input present
: Input not present
EEPROM Setting
0
1
2
No mark is displayed even in demand-activated mode.
When demand input is ON, demand-activated mark is displayed. (At factory shipment)
When demand is set to LV3 (forced thermostat OFF), demand-activated mark is display.
Description
Seri-Para I/O unit
Demand terminal block
COM short circuit
Non
LV1
LV2
LV3
Contact 1
Contact 2
No control
Operates to the maximum capacity.
Operates to XX% [EEPROM:1A] 
of the upper limit for the rated 
current
Current is limited to the set values.
Operates to XX% [EEPROM:1B] 
of the upper limit for the rated 
current
Current is limited to the set values.
-
Control
Demand meaning
Forced thermostat OFF setting
SM830195-03_Mini VRF SYS.indb   21
SM830195-03_Mini VRF SYS.indb   21