DOWNLOAD Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual ↓ Size: 7.63 MB | Pages: 127 in PDF or view online for FREE

Model
U-4LE1E5 U-4LE1E8 U-5LE1E5 U-5LE1E8 U-6LE1E5 U-6LE1E8 S-15M S-22M S-28M S-36M S-45M S-60M S-73M S-90M S-106M S-140M S-160M
Pages
127
Size
7.63 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / MINI VRF SYSTEM
File
u-4le1e5-u-4le1e8-u-5le1e5-u-5le1e8-u-6le1e5-u-6le.pdf
Date

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual ▷ View online

5 - 41
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
The intake temperature (ambient temperature) of the indoor unit is 
above 36°C.
3-6
Prevent air short 
circuit
3-7
Yes
No
The filter of the indoor unit is clogged.
3-7
Clean the filter
3-8
Yes
No
The fan of the indoor unit is broken or the fan motor is faulty.
3-8
Replace the indoor 
fan (motor)
4-1
Yes
No
Is the outdoor unit’s electronic control valve operating correctly? 
(Check for debris clogging the electronic control valve, a problem 
with the electronical coil and/or the control PC board.)
4-1
4-3
Repair the electronic 
control valve of the 
outdoor unit
Yes
No
If an alarm is occurred with the high pressure below 3.80 MPa, 
with the pressure measured as displayed by the manifold gauge, 
check the check valve in the compressor discharge line. 
Are these checking finished without fail?
4-3
4-4
Replace the check
valve in the
compressor
discharge line
Yes
No
The electronic control valve is faulty. 
In systems where the solenoid valve kits and the ice thermal 
storage tank are connected, check these solenoid valves.
4-4
Replace the 
electronic control 
valve and/or 
solenoid valve.
5-1
Yes
No
The indoor unit's expansion valve is operating correctly.
(check for debris clogging the valve, a problem with the electronical 
coil and/or the control PC board)
4-2
4-3
Repair the expansion
valve of the indoor
unit
Yes
No
3 Problem
around the
heat
exchanger
4 Blockage
in the
refrigerant
circuit
Error occurs when the system is operating in cooling mode.
5-1
5-3
5-2
Yes
No
An alarm is occurred with the high pressure at 3.80 MPa, with the 
pressure measured either as displayed by the monitoring software 
or with a manifold gauge, at which time the temperature of liquid in 
the outdoor unit’s heat exchanger is detected to be at the 
temperature of the outside air.
5-3
5-5
Contact the service
representative
Yes
No
An alarm is occurred with the high pressure at 3.80 MPa, with the 
pressure measured either as displayed by the monitoring software 
or with a manifold gauge, at which time the temperature of liquid in 
the indoor heat exchanger is detected to be at room temperature 
(intake temperature).
5-4
5-5
Contact the service
representative
Yes
No
The system may be overcharged. Check how much refrigerant was added during installation.
When a system is inspected for airtightness, it is seldom that enough nitrogen has been 
expelled, so some remains in the circuit. 
In this case, it is necessary to collect the refrigerant and then recharge the system.
5-5
Error occurs when the system is operating in heating mode.
5-2
5-4
5-5
Yes
No
5 Overcharg-
ing
SM830195-03_Mini VRF SYS.indb   41
SM830195-03_Mini VRF SYS.indb   41
2014/09/04   13:36:30
2014/09/04   13:36:30
5 - 42
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
1-1
1-4 : Single-phase model 
1-2 : 3-phase model
3-1 : Single-phase model 
2-1 : 3-phase model
Check for open circuit and the voltage at the breaker. 
if a problem is found, fix it and check again.
Yes
No
Turn the power back on and check again. 
Is the alarm triggered again?
1-4
2-1
Power wiring N-phase is connected.
Power wiring L2 and N are reverse connected.
The connector CN-PRY2 on the outdoor CR PC board is 
connected properly (locked).
1-2
1-3
4-1
Yes
No
Correct wiring
1-3
Yes
No
Correct wiring
1-4
Yes
No
1 Check 
the power 
supply &
the wiring
Are the wires (RE1, RE2) from the reactor firmly installed?
3-1
3-2
Correct wiring
Yes
No
Turn the power back on and check again. 
Is the alarm triggered again?
4hp, 5hp: 
Common in RE1 and RE2
Plug-in type
6hp: Fastening screw type
*
3-2
Replace the outdoor 
unit HIC PC board. 
4-1
Yes
No
3 Check the
outdoor
unit HIC 
PC board
2 Check the
outdoor
unit CR
PC board
There may be a instantaneous blackout failure. 
If there is nothing abnormal, see what happens.
RE1*
RE2*
4-1
4 Final check
P05 Power Supply Error
Error Detection Method
Error Diagnosis
Instantaneous blackout
Note : The work involved in diagnosing each of the items is extremely dangerous, so turn the power off at the breaker before
performing the tests.
Zero-cross (waveform input of power supply) error
DC voltage charge failure
1.
2.
Is the voltage on each of the 
terminal boards within +10% 
of the rated voltage?
RE1
RE2
Single-phase outdoor unit HIC PC board
3-phase outdoor unit HIC PC board
Correct wiring 
(connector)
3-1
Yes
No
(for 3-phase outdoor unit CR PC board)
CN-PRY2
SM830195-03_Mini VRF SYS.indb   42
SM830195-03_Mini VRF SYS.indb   42
2014/09/04   13:36:30
2014/09/04   13:36:30
5 - 43
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
P13 Forgot-to-open Valve Alarm
Error Detection Method
Error Diagnosis
1.
2.
Detection is performed only in the test run. When once detected or the test run finished without any error, 
the second detection will not be done. 
In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the 
following conditions.
The status of small temperature change of the oprating indoor unit continues for 3 minutes even after 5-minute to 
15-minute since the cooling test run has started.
The status of small temperature change of the oprating indoor unit continues for 3minutes even after 7-minute to 
15-minute since the heating test run has started.
1-1
2-1
Yes
No
1 Service 
valve
Open the service 
valve
2-1
2 Adjustment 
to 
refrigerant 
change
3 Blockage 
in 
refrigerant 
circuit
3-1
Avoid clogging
3-2
Yes
No
Are the tubes clogged?
Not additional refrigerant charged
3-1
Yes
No
Additional 
refrigerant charge
3-2
3-3
Replace the 
electronic control 
valve
Yes
No
Is the outdoor unit’s electronic control valve operating correctly? 
(Check for debris clogging the electronic control valve, a problem 
with the electronical coil and/or the control PC board.)
3-3
As the second detection is not done, restart and see what happens if there is no error.
Service valve inside the outdoor unit closed
SM830195-03_Mini VRF SYS.indb   43
SM830195-03_Mini VRF SYS.indb   43
2014/09/04   13:36:31
2014/09/04   13:36:31
5 - 44
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
1-1
3-1
2-1
Yes
No
1 System 
configuration
Is the indoor EEPROM setting, item code 0B, on the indoor unit’s 
control PC board set to 0001?
2-1
After correcting the
setting, 3-1
4-1
Yes
No
2 Indoor unit’s
EEPROM
setting
P14 O
2
 Sensor
Error Detection Method
Error Diagnosis
It is judged an error whenever the outdoor unit receives the signal “O
2
 Alarm Occurred” from the indoor unit.
With the indoor unit's EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
1.
2.
Is an O
2
 sensor being used?
Correct wiring
4-1
Yes
No
Is the indoor EXCT socket (wire) shorted?
3-1
3
4
Indoor EXCT
wiring
4-3
4-2
Yes
No
Is the alarm triggered if the indoor EXCT socket (wire) is 
disconnected, and the power is reset?
Since there is no error, see what happens.
4-1
4-2
4-3 Indoor unit control PC board error
replace PC board.
Indoor unit’s
control 
PC board
SM830195-03_Mini VRF SYS.indb   44
SM830195-03_Mini VRF SYS.indb   44
2014/09/04   13:36:31
2014/09/04   13:36:31
Page of 127
Display

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual ▷ Download