Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual ▷ View online
5 - 41
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
The intake temperature (ambient temperature) of the indoor unit is
above 36°C.
above 36°C.
3-6
Prevent air short
circuit
circuit
3-7
Yes
No
The filter of the indoor unit is clogged.
3-7
Clean the filter
3-8
Yes
No
The fan of the indoor unit is broken or the fan motor is faulty.
3-8
Replace the indoor
fan (motor)
fan (motor)
4-1
Yes
No
Is the outdoor unit’s electronic control valve operating correctly?
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
4-1
4-3
Repair the electronic
control valve of the
outdoor unit
control valve of the
outdoor unit
Yes
No
If an alarm is occurred with the high pressure below 3.80 MPa,
with the pressure measured as displayed by the manifold gauge,
check the check valve in the compressor discharge line.
Are these checking finished without fail?
with the pressure measured as displayed by the manifold gauge,
check the check valve in the compressor discharge line.
Are these checking finished without fail?
4-3
4-4
Replace the check
valve in the
compressor
discharge line
valve in the
compressor
discharge line
Yes
No
The electronic control valve is faulty.
In systems where the solenoid valve kits and the ice thermal
storage tank are connected, check these solenoid valves.
In systems where the solenoid valve kits and the ice thermal
storage tank are connected, check these solenoid valves.
4-4
Replace the
electronic control
valve and/or
solenoid valve.
electronic control
valve and/or
solenoid valve.
5-1
Yes
No
The indoor unit's expansion valve is operating correctly.
(check for debris clogging the valve, a problem with the electronical
coil and/or the control PC board)
(check for debris clogging the valve, a problem with the electronical
coil and/or the control PC board)
4-2
4-3
Repair the expansion
valve of the indoor
unit
valve of the indoor
unit
Yes
No
3 Problem
around the
heat
exchanger
heat
exchanger
4 Blockage
in the
refrigerant
circuit
refrigerant
circuit
Error occurs when the system is operating in cooling mode.
5-1
5-3
5-2
Yes
No
An alarm is occurred with the high pressure at 3.80 MPa, with the
pressure measured either as displayed by the monitoring software
or with a manifold gauge, at which time the temperature of liquid in
the outdoor unit’s heat exchanger is detected to be at the
temperature of the outside air.
pressure measured either as displayed by the monitoring software
or with a manifold gauge, at which time the temperature of liquid in
the outdoor unit’s heat exchanger is detected to be at the
temperature of the outside air.
5-3
5-5
Contact the service
representative
representative
Yes
No
An alarm is occurred with the high pressure at 3.80 MPa, with the
pressure measured either as displayed by the monitoring software
or with a manifold gauge, at which time the temperature of liquid in
the indoor heat exchanger is detected to be at room temperature
(intake temperature).
pressure measured either as displayed by the monitoring software
or with a manifold gauge, at which time the temperature of liquid in
the indoor heat exchanger is detected to be at room temperature
(intake temperature).
5-4
5-5
Contact the service
representative
representative
Yes
No
The system may be overcharged. Check how much refrigerant was added during installation.
When a system is inspected for airtightness, it is seldom that enough nitrogen has been
expelled, so some remains in the circuit.
In this case, it is necessary to collect the refrigerant and then recharge the system.
When a system is inspected for airtightness, it is seldom that enough nitrogen has been
expelled, so some remains in the circuit.
In this case, it is necessary to collect the refrigerant and then recharge the system.
5-5
Error occurs when the system is operating in heating mode.
5-2
5-4
5-5
Yes
No
5 Overcharg-
ing
SM830195-03_Mini VRF SYS.indb 41
SM830195-03_Mini VRF SYS.indb 41
2014/09/04 13:36:30
2014/09/04 13:36:30
5 - 42
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
1-1
1-4 : Single-phase model
1-2 : 3-phase model
1-2 : 3-phase model
3-1 : Single-phase model
2-1 : 3-phase model
2-1 : 3-phase model
Check for open circuit and the voltage at the breaker.
if a problem is found, fix it and check again.
if a problem is found, fix it and check again.
Yes
No
Turn the power back on and check again.
Is the alarm triggered again?
Is the alarm triggered again?
1-4
2-1
Power wiring N-phase is connected.
Power wiring L2 and N are reverse connected.
The connector CN-PRY2 on the outdoor CR PC board is
connected properly (locked).
connected properly (locked).
1-2
1-3
4-1
Yes
No
Correct wiring
1-3
Yes
No
Correct wiring
1-4
Yes
No
1 Check
the power
supply &
the wiring
supply &
the wiring
Are the wires (RE1, RE2) from the reactor firmly installed?
3-1
3-2
Correct wiring
Yes
No
Turn the power back on and check again.
Is the alarm triggered again?
Is the alarm triggered again?
4hp, 5hp:
Common in RE1 and RE2
Plug-in type
6hp: Fastening screw type
*
3-2
Replace the outdoor
unit HIC PC board.
unit HIC PC board.
4-1
Yes
No
3 Check the
outdoor
unit HIC
PC board
unit HIC
PC board
2 Check the
outdoor
unit CR
PC board
unit CR
PC board
There may be a instantaneous blackout failure.
If there is nothing abnormal, see what happens.
If there is nothing abnormal, see what happens.
RE1*
RE2*
4-1
4 Final check
P05 Power Supply Error
Error Detection Method
Error Diagnosis
Instantaneous blackout
•
Note : The work involved in diagnosing each of the items is extremely dangerous, so turn the power off at the breaker before
performing the tests.
Zero-cross (waveform input of power supply) error
•
DC voltage charge failure
•
1.
2.
Is the voltage on each of the
terminal boards within +10%
of the rated voltage?
terminal boards within +10%
of the rated voltage?
RE1
RE2
Single-phase outdoor unit HIC PC board
3-phase outdoor unit HIC PC board
Correct wiring
(connector)
(connector)
3-1
Yes
No
(for 3-phase outdoor unit CR PC board)
CN-PRY2
SM830195-03_Mini VRF SYS.indb 42
SM830195-03_Mini VRF SYS.indb 42
2014/09/04 13:36:30
2014/09/04 13:36:30
5 - 43
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
P13 Forgot-to-open Valve Alarm
Error Detection Method
Error Diagnosis
1.
2.
Detection is performed only in the test run. When once detected or the test run finished without any error,
the second detection will not be done.
In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the
following conditions.
the second detection will not be done.
In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the
following conditions.
The status of small temperature change of the oprating indoor unit continues for 3 minutes even after 5-minute to
15-minute since the cooling test run has started.
15-minute since the cooling test run has started.
•
The status of small temperature change of the oprating indoor unit continues for 3minutes even after 7-minute to
15-minute since the heating test run has started.
15-minute since the heating test run has started.
•
1-1
2-1
Yes
No
1 Service
valve
Open the service
valve
valve
2-1
2 Adjustment
to
refrigerant
change
refrigerant
change
3 Blockage
in
refrigerant
circuit
refrigerant
circuit
3-1
Avoid clogging
3-2
Yes
No
Are the tubes clogged?
Not additional refrigerant charged
3-1
Yes
No
Additional
refrigerant charge
refrigerant charge
3-2
3-3
Replace the
electronic control
valve
electronic control
valve
Yes
No
Is the outdoor unit’s electronic control valve operating correctly?
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
(Check for debris clogging the electronic control valve, a problem
with the electronical coil and/or the control PC board.)
3-3
As the second detection is not done, restart and see what happens if there is no error.
Service valve inside the outdoor unit closed
SM830195-03_Mini VRF SYS.indb 43
SM830195-03_Mini VRF SYS.indb 43
2014/09/04 13:36:31
2014/09/04 13:36:31
5 - 44
5
Mini VRF SYSTEM
Trouble Diagnosis
3. Mini VRF System Alarm Codes
1-1
3-1
2-1
Yes
No
1 System
configuration
Is the indoor EEPROM setting, item code 0B, on the indoor unit’s
control PC board set to 0001?
control PC board set to 0001?
2-1
After correcting the
setting, 3-1
setting, 3-1
4-1
Yes
No
2 Indoor unit’s
EEPROM
setting
setting
P14 O
2
Sensor
Error Detection Method
Error Diagnosis
It is judged an error whenever the outdoor unit receives the signal “O
2
Alarm Occurred” from the indoor unit.
•
With the indoor unit's EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
•
1.
2.
Is an O
2
sensor being used?
Correct wiring
4-1
Yes
No
Is the indoor EXCT socket (wire) shorted?
3-1
3
4
Indoor EXCT
wiring
wiring
4-3
4-2
Yes
No
Is the alarm triggered if the indoor EXCT socket (wire) is
disconnected, and the power is reset?
disconnected, and the power is reset?
Since there is no error, see what happens.
4-1
4-2
4-3 Indoor unit control PC board error
replace PC board.
Indoor unit’s
control
PC board
control
PC board
SM830195-03_Mini VRF SYS.indb 44
SM830195-03_Mini VRF SYS.indb 44
2014/09/04 13:36:31
2014/09/04 13:36:31