3 - 7
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
n XX-YY R.C. (Fig. 3-3)
Displays the outdoor unit sub-bus address which is
currently selected.
XX = Outdoor system address on main bus line (1 – 30)
YY = Outdoor unit sub-bus address.
“1” appears when there is only 1 outdoor unit.
currently selected.
XX = Outdoor system address on main bus line (1 – 30)
YY = Outdoor unit sub-bus address.
“1” appears when there is only 1 outdoor unit.
01: <No. of connected indoor units>
4 units connected
<Sample displays>
02: <Unit Nos. 1, 2, 3, and 4 are
connected>
Fig. 3-3
Fig. 3-4
Fig. 3-5
3. Ordinary Display Controls and Functions
SM830195-03_Mini VRF SYS.indb 7
SM830195-03_Mini VRF SYS.indb 7
2014/09/09 13:52:24
2014/09/09 13:52:24
3 - 8
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
n
Concerning the 7-segment, 4-digit display remote controller timer display
The unit Nos. of connected units are indicated by four 7-segment digits (
) and a colon.
1
2
7
12
17
3
13
18
8
4
14
19
9
5
10
15
20
6
11
16
21
22
27
32
37
23
33
38
28
24
34
39
29
25
30
35
40
26
31
36
1 ~ 20
21 ~ 40
41 ~ 60
61 ~ 80
1 ~ 20
21 ~ 40
41 ~ 60
61 ~ 80
l
The meaning of the colon changes in the same way to indicate unit Nos. up to 80.
l
Sample displays of the connected indoor unit Nos.:
NOTE
The change of the colon display (between unit Nos. 1-20 to unit Nos. 21-40) occurs automatically
every 10 seconds. (However the display does not change if there are no higher-number units connected.)
To change the display to the higher-number units before 10 seconds have passed, press the
every 10 seconds. (However the display does not change if there are no higher-number units connected.)
To change the display to the higher-number units before 10 seconds have passed, press the
(FLAP)
button.
n The total compressor operating time is displayed
(in 1-hour units) using 8 digits.
•
When the fi rst 4 digits are displayed, the bottom
dot of the colon is illuminated. (Figure (A))
•
When the last 4 digits are displayed, the colon
dot is OFF. (Figure (B))
•
The display of the fi rst 4 digits and last 4 digits
changes automatically after 10 seconds. The display
can also be changed by pressing the
(FLAP)
button.
NOTE
With the outdoor unit maintenance remote controller (when connected to the outdoor unit), the unit remote
controller check functions will not operate.
controller check functions will not operate.
•
Display of unit No. 1
•
Display of unit Nos. 1 and 2
•
Display of unit Nos. 1, 2, and 3
•
Display of unit Nos. 1, 2, 3, and 4
l
Display of unit Nos. 1 − 20
l
Display of unit Nos. 21 − 40
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
Meaning of display colon
is not displayed.
Meaning of display colon
(B)
(A)
10: <Compressor’s total operating time>
(A) and (B) are displayed alternately.
(The example here (0000, 0062) indicates 62 hours.)
(The example here (0000, 0062) indicates 62 hours.)
3. Ordinary Display Controls and Functions
SM830195-03_Mini VRF SYS.indb 8
SM830195-03_Mini VRF SYS.indb 8
2014/09/09 13:52:24
2014/09/09 13:52:24
3 - 9
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
Display the indoor unit and outdoor unit sensor
temperatures.
temperatures.
<Operating procedure>
À
Press and hold the
(CHECK) button and
buttons simultaneously for 4 seconds or longer to
engage temperature monitor mode.
engage temperature monitor mode.
During temperature monitoring,
is illuminates.
(The display and operations are the same as
for monitor mode using the indoor unit remote
controller.)
for monitor mode using the indoor unit remote
controller.)
Á
Press the
button and select the indoor unit
to monitor.
Â
Press the temperature setting
and
buttons and select the item code of the temperature
to monitor.
to monitor.
The unit No. of the selected indoor unit, and the
temperature data, are displayed.
temperature data, are displayed.
Ã
To end monitoring, press the
(CHECK) button.
The display returns to the normal display.
NOTE
The display does not blink.
1
4
2
3
4. Monitoring Operations
SM830195-03_Mini VRF SYS.indb 9
SM830195-03_Mini VRF SYS.indb 9
2014/09/09 13:52:25
2014/09/09 13:52:25
3 - 10
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
4. Monitoring Operations
Display of unit No. 1 (main unit)
s
k
r
a
m
e
R
n
o
i
t
p
i
r
c
s
e
D
N
D
°C
Indoor unit intake temp.
°C
Indoor unit heat exchanger temp. (E1)
°C
Not used
°C
Indoor unit heat exchanger temp. (E3)
Indoor unit
°C
°C
Discharge air temp.
Discharge air temp. setting
Indoor unit MOV position
STEP
°C
°C
°C
°C
Discharge temp. (TD)
High-pressure sensor temp.
Suction temp. (TS)
Heat exchanger liquid temp. (C1)
°C
Outdoor air temp. (TO)
Outdoor unit
Not used
Inverter primary current
A
MOV position
Actual operating frequency
Hz
SM830195-03_Mini VRF SYS.indb 10
SM830195-03_Mini VRF SYS.indb 10
2014/09/09 13:52:27
2014/09/09 13:52:27