Panasonic CS-Z25UD3EAW / CS-Z35UD3EAW / CS-Z50UD3EAW / CS-Z60UD3EAW / CU-Z25UBEA / CU-Z35UBEA / CU-Z50UBEA / CU-Z60UBEA Service Manual ▷ View online

113 
18.4.19  F11 (4-way Valve Switching Failure) 
Malfunction Decision Conditions 
  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during 
cooling and compressor operating, the 4-way valve is detected as malfunction. 
 
Malfunction Caused 
  Indoor heat exchanger (pipe) thermistor 
  4-way valve malfunction 
 
Troubleshooting 
 
 
 
* Check gas side pipe – for hot gas flow in cooling mode 
 
 
 
 
 
 
 
114 
18.4.20  F17 (Indoor Standby Units Freezing Abnormality) 
Malfunction Decision Conditions 
  When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor 
pipe temperature is below -1.0°C. 
 
Remark: 
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor 
unit and H39 to other indoor unit(s). 
 
Malfunction Caused 
  Wrong wiring connection 
 Faulty 
sensor 
  Faulty expansion valve 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
115 
18.4.21  F90 (Power Factor Correction Protection) 
Malfunction Decision Conditions 
  To maintain DC voltage level supply to power transistor. 
  To detect high DC voltage level after rectification. 
 
Malfunction Caused 
  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at 
the outdoor unit main PCB senses abnormal DC voltage level for power transistors. 
  When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level. 
  When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFF 
relay RY-C. 
 
Troubleshooting 
 
 
 
 
 
 
116 
18.4.22  F91 (Refrigeration Cycle Abnormality) 
Malfunction Decision Conditions 
  The input current is low while the compressor is running at higher than the setting frequency. 
 
Malfunction Caused 
  Lack of gas. 
  3-way valve close. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 