89 
17.1.2  CU-Z50UBEA  CU-Z60UBEA 
 
CN-HOT
CN-STM1
CN-TH1
CN-MTR1
CN-MTR2
CN-S
CN-TANK
AC-BLK
DATA
AC-WHT
POWER
TRANSISTOR
(IPM)
CURRENT
TRANSFORMER
(CT)
 
 
 
 
 
 
 
 
 
90 
18. Troubleshooting 
Guide 
18.1  Refrigeration Cycle System 
In order to diagnose malfunctions, make sure that there are no 
electrical problems before inspecting the refrigeration cycle. 
Such problems include insufficient insulation, problem with the 
power source, malfunction of a compressor and a fan. 
The normal outlet air temperature and pressure of the refrigeration 
cycle depends on various conditions, the standard values for them 
are shown in the table on the right. 
 
 
 
 
Difference in the intake
and outlet
air temperatures 
More than 8°C
(15 minutes after an
operation is started.)
at cooling mode.
Above 14°C
(15 minutes after an
operation is started.)
at heating mode. 
Value of electric
current during operation
Normal
Inefficient compressor
Insufficient refrigerant
Excessive amount
of refrigerant
Dusty condenser
preventing heat radiation
Measuring the air temperature
difference
Measuring electric current
during operation
Less than 8°C at the cooling mode
Less than 14°C at the heating mode.
Higher than specified
Gas side
pressure
Clogged strainer or
capillary tube
Measuring gas side pressure
Cooling Mode
High
Lower than specified
Low
Low
Inefficient compressor
Insufficient refrigerant
Clogged strainer, capillary
tube or expansion valve
Heating Mode
Low
Low
High
 
 
 
 
Normal Pressure and Outlet Air Temperature (Standard)
 
Gas Pressure 
MPa 
(kg/cm
2
G) 
Outlet air 
Temperature 
(°C) 
Cooling Mode
0.9 ~ 1.2 (9 ~ 12) 
13 ~ 17 
Heating Mode 2.0 ~ 2.7 (20 ~ 27) 
32 ~ 42 
*Condition:  • Indoor fan speed = High 
• Outdoor temperature 35°C at the cooling 
                      mode and 7°C at the heating mode 
                    • Compressor operates at rated frequency       
91 
18.1.1  Relationship Between the Condition of the Air Conditioner and Pressure and 
Electric Current 
 
Condition of the  
air conditioner 
Cooling Mode 
Heating Mode 
Low Pressure 
High Pressure 
Electric current 
during operation
Low Pressure 
High Pressure 
Electric current 
during operation
Insufficient refrigerant 
(gas leakage) 
 
 
 
 
 
 
Clogged capillary tube or 
Strainer 
 
 
 
 
 
 
Short circuit in the indoor unit 
 
 
 
 
 
 
Heat radiation deficiency 
of the outdoor unit 
 
 
 
 
 
 
Inefficient compression 
 
 
 
 
 
 
•  Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
92 
18.2  Breakdown Self Diagnosis Function 
18.2.1  Self Diagnosis Function (Three Digits Alphanumeric Code) 
  Once abnormality has occurred during operation, the unit will stop its operation, and OFF/ON operation LED OFF. 
  OFF indicator does not shown on remote control display. 
  In operation after breakdown repair, the last error code abnormality will be stored in EEPROM. 
  To make a diagnosis 
1.  OFF/ON operation LED OFF and the unit automatically stops the operation, but the OFF indicator does not 
shown. 
2.  Press CHECK button continuously for 5 seconds. 
3.  “- -” will be displayed on the remote controller display. 
4. Press 
timer 
▲ or ▼ button on the remote control. The error code “H00” (no abnormality) will be displayed. 
5.  Every press of the button (▲ or ▼) will increase the error code number. 
6.  When the displayed error code matches the unit's error code, OFF/ON operation LED will be ON 
continuously. 
7.  The breakdown diagnosis mode will be cancelled by pressing CHECK button continuously for 5 seconds or 
wait for 30 seconds 
 
 
 
 
 
 
 
  AC Reset button 
When AC Reset button is pressed, the error code 
will be reset so that the unit will be able to operate 
and recheck if any error occurred. 
 
 
 
  To display memorized error status: 
1  Turn ON the power supply. 
2  Press CHECK button continuously for 5 seconds. 
3  “- -” will be displayed on the remote controller display. 
4 Press 
timer 
▲ or ▼ button on the remote control. The error code "H00" (no abnormality) will be displayed. 
5  Every press of the button (▲ or ▼) will increase the error code number. 
6  When the displayed error code matches the unit's error code, OFF/ON operation LED will be ON 
continuously. 
7  The breakdown diagnosis mode will be cancelled by pressing CHECK button continuously for 5 seconds or 
wait for 30 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 