 2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern
1
2
3
4
5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
90
55
70
110
125
8.1.10. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Quiet button is pressed again.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. When change mode to fan only mode.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
C. Control contents
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -100 rpm from setting fan speed.
8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
Automatic Fan Speed (Dry operation)
25
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
Manual Fan Speed (Dry operation)
8.1.10.2. Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Quiet button is pressed again.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. When change mode to fan only mode.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
C. Control contents
a. Fan Speed manual
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -100 rpm from setting fan speed.
 3. Fan Speed Auto
  • If FM Lo
-100 rpm reduce from normal Heating Auto Fan Speed
  • If FM Lo
maintain RPM
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
26
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
8.1.11. Delay ON Timer Control
Delay ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to
provide a comfortable environment when reaching the set ON time.
Seventy minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine
the indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
8.1.12. Delay OFF Timer Control
Delay OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
8.1.13.  Auto Restart Control
 1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power
supply resumes.
 2. This type of control is not applicable during ON/OFF Timer setting.
8.1.14.  Auto Operation Switch
 1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
 2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
 3. When the switch is pressed between 8 to 11 seconds, the unit is forced to operate in Heating Mode.
27
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
8.1.16. Ionizer Operation
 4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control, the unit can be
changed to different controlling setting (A-B mode) or to testify oxygen operation.
 5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote control signal
receiving sound can be cancelled or turned on.
8.1.15. Indoor Power Relay Control
Power relay will turn on during operation or in progress of stopping operation. Although operation stops, the power relay continues
on for three minutes.
However, during an instantaneous power failure (< 0.5s), power relay will turn off. Then, it will turn on 2 minutes after power recover
and the unit will operate as previous operation condition.
Purpose
To provide fresh air effect to users by discharging minus ion to air.
Control Condition
a. Ionizer Only Operation.
 1. When an air-conditioner unit is at “OFF” condition (standby) and an ION operation button at remote control is pressed.
Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1
→ 2)
However, fan speed can be adjusted later by customer during this operation.
Airflow direction (Horizontal Vane) control:
Follow vane direction control at cooling mode.
Horizontal vane can be changed by customer during ion only operation.
b. Operation Mode + Ionizer Operation.
 1. Ionising Operation Start Condition
When an air conditioner unit is in “ON” condition (Heat, Cool, Dry, Fan, Auto mode) and an ION operation button at remote
28