ii. Auto Fan Speed
 1. Cooling, Ion, Oxygen
 2. Heating
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1160 rpm (XE9DK), 1330 rpm (XE12DK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1160 rpm (XE9DK), 1330 rpm (XE12DK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 840 rpm (XE9DK), 1100 rpm (XE12DK).
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
21
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
iii. Max Capacity Condition
a) During Cooling operation, if all to the following condition is fulfilled, the indoor fan speed is set to Shi.
 1. Indoor intake temperature
24°C.
 2. Operation frequency 39 Hz (XE9DK), 52 Hz (XE12DK) & above.
 3. Remote Control setting temperature 16°C.
 4. Remote Control setting fan speed Hi.
 5. Outdoor temperature
30°C.
 6. Operation start
within 30 minutes.
* If any of above conditions is not valid, the condition is ended.
b) During Heating operation, if all to the following condition is fulfilled, the indoor fan speed is set to SSHi.
 1. Indoor intake temperature is 17°C or above and less than 23°C.
 2. Operation frequency 56 Hz (XE9DK), 68.5 Hz (XE12DK) & above.
 3. Remote Control setting temperature 30°C.
 4. Remote Control setting fan speed Hi.
 5. Outdoor temperature < 4°C.
 6. Operation start
2 hours.
* If any of above conditions is not valid, the condition is ended.
C. Fan Motor Control
i. Motor specification
High voltage PWM Sensorless Motor
ii. Feedback Control
 1. Rotation speed feedback
Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed every 1s.
iii. Abnormal Detection
1. Condition
*
*
Step out signal input
Feedback rotation speed is more than 2550 rpm or below 50 rpm.
However, 10s after fan start, rotation abnormality is not detected.
2. Control
* Fan stop
3. Return
* Restart after 5s
However, in case the fan is stopped by the above conditions within 25s after fan has started, and happened
continuously for 7 times, restart will not be performed.
→ Indoor fan motor lock abnormal (H19)
iv. Restart Prohibition Control
Prohibit to restart within 5s after fan stop.
(except when power is ON)
22
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed setting.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON
1
→ 2 → 3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
→ 5 → 4 ←→ 5
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
8.1.8. Outdoor Fan Motor Operation
  • 6 pole induction, 1 speed 780 rpm (XE9DK), 810 rpm (XE12DK).
  • It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
23
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
8.1.9. Airflow Direction
 1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
 2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature
and intake air temperature) and manual (angles of direction can be adjusted using remote control).
Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (°)
1
2
3
4
5
Heating
Auto with Heat Exchanger
17
Temperature
58
7
Manual
7
17
33
49
67
Cooling, Soft Dry and Fan, Ion, O
2
Auto
7 ~ 37
Manual
7
17
25
33
41
Mode Judgement in Auto
Auto
7
Manual
7
17
25
33
41
 1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
 2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the
positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to
close position.
Horizontal Airflow
 1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
Operation Mode
Vane Angle (°)
Heating, with heat exchanger temperature
A
55 ~ 125
B
90
Cooling, Soft Dry and Fan, Ion, O
2
55 ~ 125
24
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE
Page of 108