Time Delay Safety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
  • 
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
  • 
During Soft Dry operation, the Indoor Fan will operate at low speed.
  • 
The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
  • 
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
  • 
Same as Starting Current Control for Cooling Mode operation.
  • 
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
  • 
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
  • 
Fan speed off and on at Lo speed.
  • 
Deodorizing Control.
21
CS-VC75KE CU-VC75KE / CS-VC95KE CU-VC95KE / CS-VC125KE CU-VC125KE
Soft Dry Operation Time Diagram
22
CS-VC75KE CU-VC75KE / CS-VC95KE CU-VC95KE / CS-VC125KE CU-VC125KE
Air Circulation Mode Operation Time Diagram
Standard for Determining Operation Mode
8.3. Air Circulation Mode Operation
  • 
When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
8.4. Automatic Mode Operation
  • 
Indoor fan operates at Lo fan speed for 20 seconds.
  • 
After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
  • 
After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
  • 
Room temperature adjustment.
The following are added to the setting temperature specified as above.
  • 
The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX2 at indoor
electronic controller.
23
CS-VC75KE CU-VC75KE / CS-VC95KE CU-VC95KE / CS-VC125KE CU-VC125KE
Cooling or Soft Dry Operation
When you press the SLEEP Mode, the following movement will
start to avoid overcooling.
  • 
When
the
room
temperature
reaches
the
setting
temperature or after 1 hour of operation, sleep shift
operation starts and the airflow volume will automatically
change to low.
  • 
The setting temperature will be risen by 0.5°C at the start of
operation and by 0.5°C one hour later.
  • 
The operation will stop after 8 hours.
8.5. Sleep Mode Auto Operation
8.6. Powerful Mode Operation
  • 
Purpose of this operation is to obtain the setting temperature quickly.
  • 
When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature.
This operation automatically will be running under Super High Fan speed.
  • 
Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically swing down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
  • 
Powerful Mode will operate for 15 minutes only.
  • 
Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Economy mode button is pressed.
- Sleep mode is pressed.
- Operation mode button is changed.
8.7. Economy Mode Operation
  • 
Purpose of this operation is to save or reduced electrical power consumption of the room air conditioner.
  • 
When the Economy Mode is set, the set temperature will be automatically increased 0.5°C against the preset setting
temperature. This operation automatically will be running under Random Fan speed.
(Refer operation details no. 8.9)
  • 
Vertical Airflow Direction:-
In “Manual” or “Auto” setting, the vane will automatically change to Auto Air Swing.
  • 
Economy Mode will stop if:-
- Economy Mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Powerful mode button is pressed.
- Auto or Manual air swing button is pressed.
- Fan Speed control button is pressed.
- Sleep Mode button is pressed ON.
- Operation Mode is changed.
24