Panasonic CS-TZ20TKEW / CS-TZ25TKEW / CS-TZ35TKEW / CS-TZ42TKEW / CS-MTZ16TKE / CU-TZ20TKE / CU-TZ25TKE / CU-TZ35TKE / CU-TZ42TKE Service Manual ▷ View online
61
13.5 Piping installation of R32
13.5.1 Pipe materials used and flaring
Copper pipes are used for refrigerant piping. Pipes
which comply with JIS Regulations need to be used.
Room air conditioners which use R410A and R32
have higher pressure; thus, using pipes which comply
with the Regulations is important.
The pipe thickness is regulated by revised JIS B 8607
“Flaring and brazing fittings for refrigerant” and the
pipe thickness for R410A, R32 is shown in the table.
which comply with JIS Regulations need to be used.
Room air conditioners which use R410A and R32
have higher pressure; thus, using pipes which comply
with the Regulations is important.
The pipe thickness is regulated by revised JIS B 8607
“Flaring and brazing fittings for refrigerant” and the
pipe thickness for R410A, R32 is shown in the table.
Pipe thickness
O and OL materials
Thickness (mm)
Diameter
Diameter
(mm)
R410A
R32
R22
1/4 6.35
0.80
3/8 9.52
0.80
1/2 12.70
0.80
5/8 15.88
1.00
Caution
For connection piping, use copper phosphate seamless pipes (1220T) as regulated in “JIS H 3300” and the pipe
thickness is 0.8 mm.
In the market, there are some pipes of 0.7 mm thickness, but do not use these pipes (0.8 mm thickness has to be
strictly followed).
It is recommended to use pipes whose adhesion amount of oil is at or less than 40 mg / 10 m.
At the same time, do not use pipes with dent, de-shape, and color change (especially inside).
13.5.2 Processing
and
connection of pipes
For refrigerant pipe installation, be aware of moisture and dirt do not get into the pipes, and make sure of no
refrigerant leakage.
◎
refrigerant leakage.
◎
The procedure of flaring and precautions
a) Cutting of pipes:use pipe cutter and cut the pipe slowly not to de-shape the pipe.
b) Removal of burrs on the edge of pipe (reamer or scraper)
b) Removal of burrs on the edge of pipe (reamer or scraper)
If the condition of pipe edge after the deburring is no good or if burrs attaches on the flaring, it may cause
refrigerant leakage. Turn the pipe end down and perform deburring carefully.
refrigerant leakage. Turn the pipe end down and perform deburring carefully.
c) Insert the flare nut (use the nut which is a part of the CZ parts)
d) Flaring
d) Flaring
Ensure the cleanliness of clump bar and pipe, and perform flaring carefully.
Use the existing flare tools or flare tools for R410A. Be aware that the sizes and dimensions of flaring is different
in each flaring tool. If you use the existing flaring tools, use flaring gauge to measure the length of the flaring part.
Use the existing flare tools or flare tools for R410A. Be aware that the sizes and dimensions of flaring is different
in each flaring tool. If you use the existing flaring tools, use flaring gauge to measure the length of the flaring part.
Piping
size
(mm)
Dimensions “a” (mm)
R22
Dimensions “a” (mm)
R410A/R32
a
Bar
Nut outer diameter (mm)
Flare tools
Flare tools
for R410A
Flare tools
Flare tools
for R410A
R22
R410A
Clutch type
Wing nut
type
Clutch type Clutch type
Wing nut
type
Clutch type
R32
6.35 (1/4")
0.5 ~ 1.0
1.0 ~ 1.5
0 ~ 0.5
1.0 ~ 1.5
1.5 ~ 2.0
0 ~ 0.5
17
17
9.52 (3/8")
0.5 ~ 1.0
1.0 ~ 1.5
0 ~ 0.5
1.0 ~ 1.5
1.5 ~ 2.0
0 ~ 0.5
22
22
12.70 (1/2")
0.5 ~ 1.0
1.5 ~ 2.0
0 ~ 0.5
1.0 ~ 1.5
2.0 ~ 2.5
0 ~ 0.5
24
26
15.88 (5/8")
0.5 ~ 1.0
1.5 ~ 2.0
0 ~ 0.5
1.0 ~ 1.5
2.0 ~ 2.5
0 ~ 0.5
27
29
62
13.6 Installation, Relocation, and Service
13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes)
using vacuum pump
(From the point of view of global environment protection, do not release CFCs into the atmosphere during installation
work)
1. Connect the charging hose of manifold gauge to the service port of 3-way valve (pushing insect pin).
2. Fully open the handle Lo of manifold gauge and operate vacuum pump.
work)
1. Connect the charging hose of manifold gauge to the service port of 3-way valve (pushing insect pin).
2. Fully open the handle Lo of manifold gauge and operate vacuum pump.
(If the needle of the low-pressure gauge reaches the vacuum immediately, check 1 procedure again)
3. Perform vacuuming 15 minutes or more, and make sure low pressure gauge reaches to -0.1 MPa (-76cmHg).
When the vacuuming completes, fully open the handle Lo of manifold gauge and stop the operation of vacuum
pump, and leave it for 1 ~ 2 minutes. Then, remove the connection side of the charging hose of vacuum pump
adopter after checking the needle of manifold gauge does not turn back.
pump, and leave it for 1 ~ 2 minutes. Then, remove the connection side of the charging hose of vacuum pump
adopter after checking the needle of manifold gauge does not turn back.
4. Open the stem of 2-way valve to 90° in anti-clock wise, and close the 2-way valve after 10 seconds, and perform
gas leakage test.
5. Remove the charge hose from the service port of 3-way valve, and open the stems of 2-way and 3-way valves
(open the valves to anti-clock wise carefully, do not use full strength to open)
6. Tighten the service port cap with torque wrench 18
N•m (1.8 kgf•m)
Tighten the caps of 2-way and 3-way valves with torque wrench 18 N•m (1.8kg f•m)
7. After the tightening of each cap, check gas leakage around the cap.
Liquid side
Gas side
2-way valve
Valve stem caps
Service
port cap
port cap
Service port
valve core
valve core
-0.1 MPa
(-76cmHg)
Lo Handle
Vacuum pump
adaptor
Vacuum
pump
3-way valve
Manifold gauge
Hi Handle
High-pressure
gauge
gauge
Low-pressure
gauge
Charging hoses
Hex wrench
63
13.6.2 Process of refrigerant recovery
1. Connect the center charging hose of manifold gauge to the in-let side of recovery device.
2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose
2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose
(charging hose).
3. Connect the yellow float switch cable of the recovery device to the refrigerant cylinder.
4. Open the low pressure side valve of manifold gauge.
5. Slightly loosen the charging hose of in-let connecting side of recovery device and perform air purge.
6. Open the liquid valve of refrigerant cylinder and slightly loosen the charging hose in discharging side of recovery
4. Open the low pressure side valve of manifold gauge.
5. Slightly loosen the charging hose of in-let connecting side of recovery device and perform air purge.
6. Open the liquid valve of refrigerant cylinder and slightly loosen the charging hose in discharging side of recovery
device, and perform air purge (the recovery cylinder needs slight inside pressure).
7. Insert electric plug of recovery device into electrical outlet (the fan operation starts).
8. Turn the valve 1 and 2 of recovery device to pressure equalization point.
9. After a few seconds, turn back the valve 1 and 2 to the original position.
10. Turn the switch of the recovery device to “ON”. (the compressor operation starts)
11. When the low pressure of manifold gauge is close to “0”, close the low pressure side valve, turn “OFF” the
8. Turn the valve 1 and 2 of recovery device to pressure equalization point.
9. After a few seconds, turn back the valve 1 and 2 to the original position.
10. Turn the switch of the recovery device to “ON”. (the compressor operation starts)
11. When the low pressure of manifold gauge is close to “0”, close the low pressure side valve, turn “OFF” the
recovery device switch.
12. Remove the center charging hose of manifold gauge from the recovery device.
(Liquid side)
(Indoor unit)
(Outdoor unit)
(Gas side)
Two-way valve
Close
Close
Three-way valve
Hi
Lo
Vacuum
Pump
64
13.6.3 Relocation
1. Removing the air conditioning unit
a) Recovery of outdoor unit refrigerant by pumping down
Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed,
and this name is unified within the air conditioning industry), and then you are able to start cooling operation
in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
1. Check the valve stems of two-way and three-way valves are open by being turned to anti-clockwise
and this name is unified within the air conditioning industry), and then you are able to start cooling operation
in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
1. Check the valve stems of two-way and three-way valves are open by being turned to anti-clockwise
(Remove the caps, and confirm the bars are fully open. Use hexagon wrench <4 mm> to open and close
the valves).
the valves).
2. Press the “Emergency Operation” button of the indoor units for five seconds and release [Forced cooling
operation] (for old models, press “forced cooling” button). Then, operate the air conditioning unit for about
10 minutes.
10 minutes.
3. Turn the stem of the two-way valve to the clock-wise and close the valve.
4. After about 2 ~ 3 minutes, turn the stem of the three-way valve quickly to the clock-wise, and stop the
4. After about 2 ~ 3 minutes, turn the stem of the three-way valve quickly to the clock-wise, and stop the
operation.
Caution: In the pump down operation, stop the compressor before removing the refrigerant pipes.
If you do not stop the compressor operation, and if the valve is open and remove the refrigerant pipes, the air
may be sucked into the system and causes extreme high temperature in the refrigerant cycle. This may result in
rupture or injury, etc.
If you do not stop the compressor operation, and if the valve is open and remove the refrigerant pipes, the air
may be sucked into the system and causes extreme high temperature in the refrigerant cycle. This may result in
rupture or injury, etc.
5. Attach and tighten the caps of two-way and three-way valves with torque wrench.
6. Remove the connecting pipes (liquid side and gas side).
6. Remove the connecting pipes (liquid side and gas side).
b) Removal of indoor and outdoor units
1. Remove the connecting pipes and wires between the indoor and outdoor units.
2. Attach capping flare nuts on the edges of the pipes, connecting the indoor and outdoor units, in order to
prevent dust and moisture get into the pipes.
3. Remove the indoor and outdoor units.
2. Unit
installation
Use new refrigerant pipes for the installation, and perform air purging using vacuum pump and gas
leakage testing stated in 14.5.1.
leakage testing stated in 14.5.1.
13.6.4 Replacement of air conditioning units and evacuation (when re-using the existing
pipes)
When replacing the air conditioning units, you might use the existing pipes, but it is recommended to perform flaring
again. In case of unit replacement, even if the unit is new refrigerant air conditioner, if the refrigerant oil is different, it
may cause problem. Further, when re-using the existing refrigerant pipes, it is recommended to evacuate the pipes
as much as possible, due to the reason that much refrigerant oil may be attached on the surface of the pipes. If the
pipes are used without evacuation, the remaining refrigerant oil may cause under-performance and abnormal
refrigerant cycle caused by non-compatibility of those oils.
again. In case of unit replacement, even if the unit is new refrigerant air conditioner, if the refrigerant oil is different, it
may cause problem. Further, when re-using the existing refrigerant pipes, it is recommended to evacuate the pipes
as much as possible, due to the reason that much refrigerant oil may be attached on the surface of the pipes. If the
pipes are used without evacuation, the remaining refrigerant oil may cause under-performance and abnormal
refrigerant cycle caused by non-compatibility of those oils.
13.6.5 Inter-changeability of refrigerant
Do not operate air conditioning units inserting wrong (or mixed) refrigerant (R22, R410A, R32). It may cause mal-
function of the units, and at the same time, may cause serious incident such as rupture of the refrigerant cycle.
function of the units, and at the same time, may cause serious incident such as rupture of the refrigerant cycle.
Click on the first or last page to see other CS-TZ20TKEW / CS-TZ25TKEW / CS-TZ35TKEW / CS-TZ42TKEW / CS-MTZ16TKE / CU-TZ20TKE / CU-TZ25TKE / CU-TZ35TKE / CU-TZ42TKE service manuals if exist.