45 
12.2.3  Indoor Unit Installation 
  
● Do not turn over the unit without it’s shock absorber during pull out the piping.
It may cause intake grille damage.
  
● Use shock absorber during pull out the piping to protect the intake grille from damage.
Piping
Intake grille
Shock absorber
Piping
pull out 
the p
ipin
g
pull o
ut th
e p
ipin
g
 
 
12.2.3.1 
For the Right Rear Piping 
Install the Indoor Unit
Pull out the Indoor piping
Step-2
Secure the Indoor Unit
Insert the connection cable
Step-1
Step-3
Step-4
 
12.2.3.2 
For the Right and Right  
         Bottom Piping 
Install the Indoor Unit
Pull out the Indoor piping
Step-2
Insert the connection cable
Secure the Indoor Unit
Step-1
Step-3
Step-4
 
12.2.3.3 
For the Embedded Piping 
• Use a spring bender or equivalent to bend the piping so that the piping is not 
    crushed.
• When determining the dimensions of the piping, slide the unit all the way to the  
    left on the installation plate.
• Refer to the section “Cutting and flaring the piping”.
Bend the embedded piping
Cut and flare the embedded piping
Replace the drain hose
Pull the connection cable into Indoor Unit
• The inside and outside connection cable can be connected without removing 
  the front grille.
Step-1
Step-2
Step-3
Step-4
• Please refer to “Connecting the piping” column in outdoor unit section. 
    (Below  steps  are  done after connecting the outdoor piping and gas-leakage 
    confirmation.)
Connect the piping
• Please refer to “Insulation of piping connection” column as mentioned in
  indoor/outdoor unit installation.
Install the Indoor Unit
Secure the Indoor Unit
Insulate and finish the piping
Step-5
Step-6
Step-7
Step-8
 
Right Rear piping
How to keep the cover
In case of the cover is cut, keep the cover at the rear 
of chassis as shown in the illustration for future 
reinstallation.
(Left, right and 2 bottom covers for piping.)
Install the indoor unit
Hook the indoor unit onto the upper 
portion of installation plate. (Engage 
the indoor unit with the upper edge 
of the installation plate). Ensure the 
hooks are properly seated on the 
installation plate by moving it in left 
and right.
Secure the Indoor Unit
Right and Right Bottom piping
Insert the connection cable
Press the lower left and right side of the unit
against the installation plate until hooks
engages with their slot (sound click).
Cover for the 
bottom piping
Cover for the 
bottom piping
Tape it with piping in a 
position as mentioned in 
Fig. below.
Cover for 
the right 
piping
Piping
Drain 
hose
Cover for 
the left 
piping
Cover for 
the bottom 
piping
Tape it with piping in a 
position as mentioned in 
Fig. below.
Cover for the 
right piping
Piping
Drain hose
Cover for 
the left 
piping
Drain hose
Sleeve for 
piping hole
Indoor unit
Hooks at 
installation 
plate
Piping
Cover for piping
Guide 
surface
Connection 
cable
About 
70 – 80 mm
Connection cable
Gas side piping
Liquid side piping
Drain hose
Installation 
plate
Unit’s hook
To take out the unit, push the 
 marking at 
the bottom unit, and pull it slightly towards you to 
disengage the hooks from the unit.
g
n
i
k
r
a
m
 
 
 
(This can be used for left rear piping and left bottom 
piping also.) 
46 
 
How to pull the piping and drain hose out, in case of the 
embedded piping.
 
In case of left piping how to insert the 
connection cable and drain hose.
Rear view for left piping installation
Adjust the piping slightly 
downwards.
Drain hose
Connection cable
Exchange the drain hose and 
the cap
(For the right piping, follow the same procedure)
Drain cap
Drain hose
 
PVC tube for 
drain hose
Indoor unit
55mm (1/2 ~ 1.75Hp) or 
80mm (2.0 ~ 2.5Hp)
Piping
Cable
Apply putty or 
caulking material 
to seal the wall 
opening.
Connection cable
Piping
More than 
470 mm
More than 950mm 
(1/2 ~ 1.75Hp) or 
1150mm (2.0 ~ 2.5Hp)
PVC tube (VP-65) for piping and 
connection cable
PVC tube for drain hose (VP-30)
PVC tube for 
drain hose (VP-20)
More than 700 mm
Drain hose 
from main unit
Cable
45°
Drain hose
Piping
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 950mm 
(1/2 ~ 1.75Hp) or 
1150mm (2.0 ~ 2.5Hp)
12.2.4  Connect the Cable to the Indoor Unit 
1  The inside and outside connection cable can be connected without removing the front grille. 
2  Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed  
4 x 1.5 mm
2
 flexible cord, type designation 60245 IEC 57 or heavier cord. Do not use joint connection cable. 
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short. Allowable connection 
cable length of each indoor unit shall be 30 m or less. 
3  Bind all the indoor and outdoor connection cable with tape and route the connection cable via the 
escapement. 
4  Remove the tapes and connect the connection cable between indoor unit and outdoor unit according to the 
diagram below. 
 
 
Terminals on the outdoor unit
L
N
1
2
3
Colour of wires
Terminals on the indoor unit
1
2
3
 
 
 
 
 
 
 
 
 
 
 
47 
5  Secure the connection cable onto the control board with the holder. 
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s 
respectively. 
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason. 
 
Connection cable
Indoor & outdoor 
connection cable
Escapement
Terminal Board
Recommended 
length (mm)
Earth Wire 
longer than 
others AC 
wires for 
safety reason
Holder
Indoor & outdoor 
connection cable
Outdoor unit
Tape
Recommended 
length (mm)
a
b
c
d
35
35
35 55
 
 
 WARNING
 
 This equipment must be properly earthed. 
 
12.2.4.1  Wire Stripping Connecting and Requirement 
 
WARNING
OR
   Use complete wire 
without joining.
   Use approved socket 
and plug with earth pin.
   Wire connection in this 
area must follow to 
national wiring rules.
Wire stripping
No loose strand 
when inserted
10 ± 1 mm
RISK OF FIRE
JOINING OF WIRES 
MAY CAUSE 
OVERHEATING AND 
FIRE.
5 mm or more 
(gap between wires)
Indoor/outdoor 
connection 
terminal board
 Do not joint wires
OR
OR
Conductor 
fully inserted
Conductor over 
inserted
Conductor not 
fully inserted
ACCEPT
PROHIBITED
PROHIBITED
 
 
 
 
 
 
 
 
 
 
 
 
48 
12.3 Outdoor Unit 
12.3.1  Install the Outdoor Unit 
  After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. 
1  Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 
2  When installing at roof, please consider strong wind and earthquake. 
Please fasten the installation stand firmly with bolt, screws or nails. 
 
A
B
C
D
 
Model A 
TZ20***, TZ25***, TZ35***  570 mm  105 mm  18.5 mm 320 mm
TZ42*** 
540 mm  160 mm  18.5 mm 330 mm
12.3.2  Connect the Piping  
12.3.2.1 Connecting 
the Piping to Indoor 
For connection joint location at outside building of all 
model (except R32 model) 
Please make flare after inserting flare nut (locate at 
joint portion of tube assembly) onto the copper pipe. 
(In case of using long piping) 
 
Connect the piping 
  Align the center of piping and sufficiently tighten 
the flare nut with fingers. 
  Further tighten the flare nut with torque wrench in 
specified torque as stated in the table. 
 
Torque 
wrench
Spanner or 
Wrench
 
For connection joint location at inside building for R32 
model only 
  Decide the length. 
  Cut and remove the tube connectors at indoor 
copper pipings (both gas and liquid piping) by 
using pipe cutter. Remove burrs from cut edge. 
  Use pipe expander to expand the end of long 
piping. 
  Align the center of piping and braze the piping 
joints. 
 
Indoor 
copper pipe
Tube connector
(40~50mm)
Brazing point
1. Cut and 
Remove
2. Expand long 
pipe
3. Braze both 
pipe
 
12.3.2.2 Connecting 
the 
Piping to Outdoor 
Decide piping length and then cut by using pipe cutter. 
Remove burrs from cut edge. 
Make flare after inserting the flare nut (locate at valve) 
onto the copper pipe. 
Align center of piping to valve and then tighten with 
torque wrench to the specified torque as stated in the 
table. 
 
 
 
 
Do not overtighten, overtightening may cause gas leakage. 
 
 
Piping size 
Torque 
6.35 mm (1/4") 
[18 N•m (1.8 kgf•m)] 
9.52 mm (3/8") 
[42 N•m (4.3 kgf•m)] 
12.7 mm (1/2") 
[55 N•m (5.6 kgf•m)] 
15.88 mm (5/8") 
[65 N•m (6.6 kgf•m)] 
19.05 mm (3/4") 
[100 N•m (10.2 kgf•m)] 
 
 
 
 
 
 
 
Page of 127