DOWNLOAD Panasonic CS-TZ20TKEW / CS-TZ25TKEW / CS-TZ35TKEW / CS-TZ42TKEW / CS-MTZ16TKE / CU-TZ20TKE / CU-TZ25TKE / CU-TZ35TKE / CU-TZ42TKE Service Manual ↓ Size: 23.23 MB | Pages: 127 in PDF or view online for FREE

Model
CS-TZ20TKEW CS-TZ25TKEW CS-TZ35TKEW CS-TZ42TKEW CS-MTZ16TKE CU-TZ20TKE CU-TZ25TKE CU-TZ35TKE CU-TZ42TKE
Pages
127
Size
23.23 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-tz20tkew-cs-tz25tkew-cs-tz35tkew-cs-tz42tkew-cs.pdf
Date

Panasonic CS-TZ20TKEW / CS-TZ25TKEW / CS-TZ35TKEW / CS-TZ42TKEW / CS-MTZ16TKE / CU-TZ20TKE / CU-TZ25TKE / CU-TZ35TKE / CU-TZ42TKE Service Manual ▷ View online

41 
11.2.3 CU-TZ42TKE 
 
CN-HOT
CN-STM
CN-TH
CN-MTR1
CN-MTR2
CN-TANK
AC-BLK
DATA
AC-WHT
POWER
TRANSISTOR
(IPM)
CURRENT
TRANSFORMER
(CT)
 
 
 
 
 
 
 
 
 
 
 
 
 
42 
12. Installation 
Instruction 
12.1  Select the Best Location 
12.1.1 Indoor 
Unit 
  Do not install the unit in excessive oil fume area 
such as kitchen, workshop and etc. 
  There should not be any heat source or steam 
near the unit. 
  There should not be any obstacles blocking the air 
circulation. 
  A place where air circulation in the room is good. 
  A place where drainage can be easily done. 
  A place where noise prevention is taken into 
consideration. 
  Do not install the unit near the door way. 
  Ensure the spaces indicated by arrows from the 
wall, ceiling, fence or other obstacles. 
  Recommended installation height for indoor unit 
shall be at least 2.5 m. 
12.1.2 Outdoor 
Unit 
  If an awning is built over the unit to prevent direct 
sunlight or rain, be careful that heat radiation from 
the condenser is not obstructed. 
  There should not be any animal or plant which 
could be affected by hot air discharged. 
  Keep the spaces indicated by arrows from wall, 
ceiling, fence or other obstacles. 
  Do not place any obstacles which may cause a 
short circuit of the discharged air. 
  If piping length is over the [piping length for 
additional gas], additional refrigerant should be 
added as shown in the table. 
 
Table A 
Model 
Capa- 
city 
W  
(HP) 
Piping size 
Std. 
Lengt
h (m) 
Max 
Eleva-
tion (m) 
Min.   
Piping 
Length 
(m) 
Max.  
Piping 
Length 
(m) 
Addi-
tional 
Refri-
gerant 
(g/m) 
Piping 
Length 
for 
add. 
gas 
(m) 
Indoor 
A
min
 
(m
2
Gas Liquid 
MTZ16*** 1/2HP 
Refer to installation manual at outdoor unit 
TZ20*** 3/4HP 9.52 
mm 
(3/8
"
6.35 
mm 
(1/4
"
15 3 15 
10 
7.5 
0.41 
TZ25*** 1.0HP 
15 
15  10  7.5  0.53 
TZ35*** 1.5HP 
15 
15  10  7.5  0.68 
TZ42*** 1.75HP 12.7 
mm 
(1/2
"
15 3 15 
10 
7.5 
0.83 
TZ50*** 2.0HP 
15 
20  15  7.5  1.68 
 
* Table “A” only applicable for single split connection. 
* In case of connection to outdoor multi inverter, refer  
   to installation manual at outdoor unit. 
 
Example: For TZ25*** 
If the unit is installed at 10 m distance, the quantity of 
additional refrigerant should be 25 g .... (10-7.5) m x 
10 g/m = 25 g. 
 
 
 
 
 
A
min
 = (M / (2.5 × (LFL)
(5/4)
 × h
0
)) 
2
 
 
 
A
min
  = Required minimum room area, in m
2
 
= Refrigerant charge amount in appliance, in kg
LFL  = Lower flammable limit (0.306 kg/m
3
) 
h
0
 
= Installation height of the appliance (1.8 m for 
   wall mounted) 
 
12.1.3  Indoor/Outdoor Unit Installation 
Diagram 
 
 
d
n
e
b
 
o
t
 
t
o
n
 
n
o
i
t
n
e
t
t
A
n
o
i
t
c
e
r
i
d
 
g
n
i
p
i
P
up drain hose
(Front side)
Right
Right 
Rear
Right 
bottom
Left 
Rear
Left bottom
Left
Additional drain hose
Gas side piping 
Connection cable
Liquid side piping 
Power supply cord 
It is advisable to 
avoid more than 2 
blockage directions. 
For better ventilation 
& multiple-outdoor 
installation, please 
consult authorized 
dealer/specialist.
300 mm 
or more
100 mm 
or more
100 mm 
or more
1000 mm 
or more
WARNING
Flare connection only 
at outside of building
 )
(
 )
(
 )
(
 )
(
(Left and right are identical)
Installation plate 
1
Sleeve (   )
Bushing-Sleeve (   )
Bend the pipe as closely 
on the wall as possible, 
but be careful that it 
doesn’t break.
Saddle  
 )
Floor
Putty (   )
(Gum Type Sealer)
Installation parts you 
should purchase (   )
65 mm 
or more
50 mm 
or more
2.5 m (min)
Vinyl tape (wide) (   )
 
• Apply after carrying 
out a drainage test.
 
• To carry out the 
drainage test, 
remove the air filters
and pour water into 
the heat exchanger.
 
Carry out insulation after 
checking for gas leaks and 
secure with vinyl tape.
 Vinyl tape
Remote control holder 
5
Remote control holder fi xing screws 
6
Remote 
control 
3
Insulation of piping connections
Attaching the remote control holder to the wall
(
 
 
  This illustration is for explanation purposes only. 
The indoor unit will actually face a different way. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
43 
12.2 Indoor Unit 
12.2.1  How to Fix Installation Plate 
The mounting wall shall be strong and solid enough to prevent it from vibration. 
 
3
4
B
A
C
Ceiling
Wall
Wall
Installation 
plate 
1
2  screw
More than 
1
More than 
1
Measuring Tape
Indoor unit
184 mm
128 mm
222 mm
128 mm
More 
than 
2
PIPE 
HOLE 
CENTER
PIPE 
HOLE 
CENTER
128mm TO 
PIPE HOLE 
CENTER
128mm TO 
PIPE HOLE 
CENTER
For best strength of 
INDOOR unit installation, 
it is highly recommended 
to locate “ ” at 5 position 
as shown. 
 
 
Model 
Dimension 
1
 
2
 
3
 
4
 
5
 
6
 
MTZ16***, 
TZ20***, TE20*** 
TZ25***, TE25*** 
TZ35***, TE35*** 
TZ42***, TE42*** 
470 mm 
90 mm 
380 mm 
420 mm 
45 mm 
95 mm 
 
3
4
5
6
Ceiling
Wall
Wall
Installation plate 
1
2 screw
More than 
1
More than 
1
Measuring Tape
Indoor unit
256 mm
128 mm
128 mm
256 mm
128 mm
More 
than 
2
For best strength of 
INDOOR unit installation, 
it is highly recommended 
to locate “ ” at 5 position 
as shown. 
 
 
Model 
Dimension 
1
 
2
 
3
 
4
 
5
 
6
 
TZ50***, TE50*** 
TZ60***, TE60*** 
TZ71*** 
605 mm 
95 mm 
550 mm 
550 mm 
270 mm 
320 mm 
 
The center of installation plate should be at more than 1 at right and left of the wall. 
The distance from installation plate edge to ceiling should more than 2. 
From installation plate center to unit’s left side is 3. 
From installation plate center to unit’s right side is 4. 
 
B
 
: For left side piping, piping connection for liquid should be about 5 from this line. 
 
: For left side piping, piping connection for gas should be about 6 from this line. 
 
1  Mount the installation plate on the wall with 5 screws or more (at least 5 screws). 
(If mounting the unit on the concrete wall, consider using anchor bolts.) 
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using 
a level gauge. 
2  Drill the piping plate hole with ø70 mm hole-core drill. 
Line according to the left and right side of the installation plate. The meeting point of the extended line is 
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram 
above. The hole center is obtained by measuring the distance namely 128 mm for left and right hole 
respectively. 
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor 
side. 
44 
12.2.2  To Drill a Hole in the Wall and 
Install a Sleeve of Piping 
1  Insert the piping sleeve to the hole. 
2  Fix the bushing to the sleeve. 
3  Cut the sleeve until it extrudes about 15 mm 
from the wall. 
 
  
CAUTION
 
   
           
   When the wall is hollow, please be sure to use 
      the sleeve for tube assembly to prevent dangers 
  caused by mice biting the connection cable. 
 
4  Finish by sealing the sleeve with putty or 
caulking compound at the final stage. 
 
 
15 mm
Putty or caulking compound
ø70 mm through hole
Indoor
Outdoor
Sleeve for tube 
assembly
Approx. 5 - 7 mm
Bushing for tube 
assembly
Wall
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other CS-TZ20TKEW / CS-TZ25TKEW / CS-TZ35TKEW / CS-TZ42TKEW / CS-MTZ16TKE / CU-TZ20TKE / CU-TZ25TKE / CU-TZ35TKE / CU-TZ42TKE service manuals if exist.