DOWNLOAD Panasonic CS-PC9CKH / CU-PC9CKH / CS-SC9CKH / CU-PC9CKH / CS-PC12CKH / CU-PC12CKH / CS-SC12CKH / CU-PC12CKH Service Manual ↓ Size: 10.71 MB | Pages: 76 in PDF or view online for FREE

Model
CS-PC9CKH CU-PC9CKH CS-SC9CKH CU-PC9CKH CS-PC12CKH CU-PC12CKH CS-SC12CKH CU-PC12CKH
Pages
76
Size
10.71 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
cs-pc9ckh-cu-pc9ckh-cs-sc9ckh-cu-pc9ckh-cs-pc12ckh.pdf
Date

Panasonic CS-PC9CKH / CU-PC9CKH / CS-SC9CKH / CU-PC9CKH / CS-PC12CKH / CU-PC12CKH / CS-SC12CKH / CU-PC12CKH Service Manual ▷ View online

(1) *
*
Connect the manifold gauge to the service port of 3-way
valve.
Measure the pressure.
(2) *
*
Keep it for 5-10 minutes.
Ensure that the pressure indicated on the gauge is the
same as that of measured during the first time.
4(A). Checking gas leakage for the left piping.
11.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT
 1. Remove the control board cover from the unit by loosening the screw.
 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (PC9CK, PC12CK,
SC9CK, SC12CK, E720K, E920K, E1220K) × 1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier cord.
 3. Secure the cable onto the control board with the holder (clamper).
 4. Attach the control board cover back to the original position with the screw.
11.3.6. PIPE INSULATION
 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
with thickness 6 mm or above.
45
CS-PC9CKH CU-PC9CKH / CS-SC9CKH CU-PC9CKH / CS-PC12CKH CU-PC12CKH / CS-SC12CKH CU-PC12CKH
CHECK THE DRAINAGE
     • 
• 
• 
• Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)
     • 
• 
• 
• Pour a glass of water into the drain tray-styrofoam.
     • 
• 
• 
• Ensure that water flows out from drain hose of the indoor
unit.
EVALUATION OF THE PERFORMANCE
     • 
• 
• 
• Operate the unit at cooling operation mode for fifteen
minutes or more.
     • 
• 
• 
• Measure the temperature of the intake and discharge air.
     • 
• 
• 
• Ensure the difference between the intake temperature and
the discharge is more than 8°C.
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut
connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable being clamped firmly?
Is the drainage OK?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal? (PC9CK,
PC12CK, E720K, E920K, E1220K)
CHECK ITEMS
46
CS-PC9CKH CU-PC9CKH / CS-SC9CKH CU-PC9CKH / CS-PC12CKH CU-PC12CKH / CS-SC12CKH CU-PC12CKH
12 2-way, 3-way Valve
2-way Valve (Liquid Side)
3-way Valve (Gas Side)
Works
Shaft Position
Shaft Position
Service Port
Shipping
Close
Close
Close
(With valve cap)
(With valve cap)
(With cap)
Evacuation
Close
Close
Open
(Installation and
(Counter-Clockwise)
(Clockwise)
(Push-pin)
Re-installation)
Operation
Open
Open
Close
(With valve cap)
(With valve cap)
(With cap)
Pumping down
Close
Open
Open
(Transferring)
(Clockwise)
(Counter-Clockwise)
(Connected manifold
gauge)
Evacuation
Open
Open
Open
(Servicing)
With vacuum pump
Gas charging
Open
Open
Open
(Servicing)
(With charging cylinder)
Pressure check
Open
(Servicing)
Open
Open
(Connected manifold
gauge)
Gas releasing
Open
(Servicing)
Open
Open
(Connected manifold
gauge)
47
CS-PC9CKH CU-PC9CKH / CS-SC9CKH CU-PC9CKH / CS-PC12CKH CU-PC12CKH / CS-SC12CKH CU-PC12CKH
Required tools: hexagonal wrench, adjustable wrench, torque
wrenches, wrench to hold the joints and gas leak detector.
The additional gas for air purging has been charged in the
outdoor unit.
However, if the flare connections have not been done correctly
and there gas leaks, a gas cylinder and the charge set will be
needed.
 1. Recheck the piping connections.
 2. Open the valve stem of the 2-way valve counter-
clockwise approximately 90°, wait 10 seconds, and
then set it to closed position.
     • 
• 
• 
• Be sure to use a hexagonal wrench to operate the valve
stem.
 3. Check for gas leakage.
     • 
• 
• 
• Check the flare connection for gas leakage.
 4. Purge the air from the system
     • 
• 
• 
• Set the 2-way valve to the open position and remove the
cap from the 3-way valve’s service port.
     • 
• 
• 
• Using the hexagonal wrench to press the valve core pin,
discharge for three seconds and then wait for one
minute.
Repeat this three times.
 5. Use torque wrench to tighten the service port cap to a
torque of 1.8 kg.m. (18 N.m).
The air in the indoor unit and in the piping must be purged. If air
remains
in
the
refrigeration
pipings,
it
will
affect
the
compressor, reduce the cooling capacity, and could lead to a
malfunction.
 6. Set the 3-way valve to the opened position.
 7. Mount the valve stem nuts to the 2-way and 3-way
valves.
 8. Check for gas leakage.
     • 
• 
• 
• At this time, especially check for gas leakage from the 2-
way and 3-way’s stem nuts, and from the service port
cap.
Caution
If gas leakage is discovered in step (3) above, take
the following measures:
If the leaks stop when the piping connections are
tightened further, continue working from step (4).
If the gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge
all of the gas through the service port, and then
recharge with the specified amount of gas from a gas
cylinder.
12.1. Air Purging of the Piping and Indoor Unit
12.1.1. Air purging (Installation)
Service port cap
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
leakage from the refrigeration cycle.
Procedure:
48
CS-PC9CKH CU-PC9CKH / CS-SC9CKH CU-PC9CKH / CS-PC12CKH CU-PC12CKH / CS-SC12CKH CU-PC12CKH
Page of 76
Display

Click on the first or last page to see other CS-PC9CKH / CU-PC9CKH / CS-SC9CKH / CU-PC9CKH / CS-PC12CKH / CU-PC12CKH / CS-SC12CKH / CU-PC12CKH service manuals if exist.