Time Delay Safety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Compressor Protection Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
•
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
then Soft Dry operation will start.
•
During Soft Dry operation, the Indoor Fan will operate at low speed.
•
The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
off, it stops for 6 minutes.
•
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
•
Same as Starting Current Control for Cooling Mode operation.
•
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
stops.)
•
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
is valid during compressor stops.)
•
Same as Compressor Protection Control for Cooling Mode Operation.
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
•
Fan speed off and on at Lo speed.
•
Deodorizing Control.
21
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Soft Dry Operation Time Diagram
22
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Heating in operation according to Remote Control setting.
Time Delay Safety Control
30 minutes Time Save Control
Overload Protection Control
Compressor Reverse Rotation Protection Control
4-way Valve Control
Outdoor Fan Motor Control
8.3. Heating Mode Operation
•
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
•
When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.
•
The compressor will start automatically if it has stopped for 30 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
ON temperature and OFF temperature.
•
If the temperature of the indoor heat exchanger rises to 51°C, Outdoor Fan stops.
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
•
If the indoor heat exchanger becomes 65°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
•
If the compressor is operating continuously for 5 minutes or longer and temperature difference between intake air and indoor
heat exchanger is 5°C or less for 2 minutes, compressor will stop and restart automatically.
heat exchanger is 5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
s
T = Indoor heat exchanger temperature - intake air temperature.
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
•
4-way valve always ON during Heating operation. (Except Deicing operation)
•
When the unit is switched to “OFF” during Heating operation, 4-way valve stay at Heating position for 5 minutes.
•
When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds.
(30 seconds Forced Operation).
23
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Hot Start Control
Anti Cold Draft Control
When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
Hot Start is completed when indoor heat exchanger rises to 39°C.
•
This operation is to prevent the Cold Draft during Heating mode operation.
•
The operation will start when compressor OFF (Thermo OFF) during Heating operation.
•
For the first 30 sec from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
exchanger temperature as shown below:
Note: SSLo: Fan will be running at Lo speed with Indoor heat exchanger temperature 1.5 sec ON and 5.5 sec OFF.
•
After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
•
Anti Cold Draft Control will stop when:
−
Intake temperature < set temperature -1.5°C. (Time Delay Safety Control 4 minutes waiting is valid)
−
After 30 minutes time saved control.
(see page 22).