REMARKS
B
: BLUE
BR
: BROWN
BL
: BLACK
W
: WHITE
R
: RED
O
: ORANGE
P
: PINK
Y/G
: YELLOW/GREEN
Resistance of Indoor Fan Motor Windings
MODEL
CS-MA75KE
CS-MA125KE
CONNECTION
CWA921033
CWA921031
YELLOW-BLUE
707.1
450.7
YELLOW-BROWN
71.1
68.2
BROWN-ORANGE
64.7
56.7
ORANGE-WHITE
15.7
56.9
WHITE-RED
116.2
102.0
Resistance of Outdoor Fan Motor Windings
MODEL
CU-MA195KE
CONNECTION
CWA95245
BLUE-YELLOW
260.5
YELLOW-RED
446.0
Resistance of Compressor Windings
MODEL
CS-MA75KE/
CU-MA195KE
CS-MA125KE/
CU-MA195KE
CONNECTION
2RS122D5AB02
2KS224D5AC02
C-R
5.627
2.454
C-S
12.190
3.856
17
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
  • 
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
  • 
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
  • 
When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
  • 
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
  • 
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • 
When the compressor, outdoor fan motor & indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
  • 
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
s
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
18
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Compressor Protection Control
Automatic Fan Speed Mode
  • 
After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
  • 
If the above phenomenon is repeated for 3 times, the compressor will stops.
  • 
The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
  • 
Fan speed rotates in the range of Hi to Me.
  • 
Deodorizing Control.
19
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Cooling Operation Time Diagram
20
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE