Panasonic CS-G95KE / CS-G125KE / CU-G95KE / CU-G125KE Service Manual ▷ View online

3.
Soft Dry Operation
A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal setting
temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
  • 
Compressor OFF temperature = Compressor ON temperature.
  • 
The operation frequency changes every 30 seconds.
  • 
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
  • 
The Compressor stops when the intake air temperature reaches 3.5°C below internal setting temperature and continues for 3
minutes.
  • 
When the Compressor stops operation, indoor fan stops for 330 seconds.
  • 
When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
  • 
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation immediately.
  • 
When the Compressor stops, the outdoor fan motor stops 30 seconds later.
21
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
B. Deodorizing Control
  • 
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available during anti-
freezing control.
  • 
When the compressor is in operation, the deodorizing status starts from 1
2.
  • 
When the compressor stops operation, the deodorizing status starts from 3
4
5.
  • 
If the compressor stops operation, indoor fan stops for 330 seconds.
C. Sensible Heat Control
  • 
This control is to improve the feeling in high fan speed and low operation frequency. When the operation frequency is less
than 33Hz (CU-G95KE) or 36Hz (CU-G125KE), the fan speed will reduce. When the operation frequency is increased to
40Hz (CU-C95KE) or 49Hz (CU-C125KE) continuously for 5 minutes, the fan speed will resume to normal condition. (During
Cooling operation).
22
S-G95KE CU-G95KE / CS-G125KE CU-G125KE
4.
Heating Operation
A. Room Temperature Control
  • 
During heating operation, the room temperature control depends on intake air temperature and internal setting temperature.
Basically it can be divided into 2 periods as shown below:
(i) When indoor fan speed is Medium of above.
23
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
(ii) When indoor fan speed is lower than Medium.
24
S-G95KE CU-G95KE / CS-G125KE CU-G125KE