3.
Soft Dry Operation
A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal setting
temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
•
Compressor OFF temperature = Compressor ON temperature.
•
The operation frequency changes every 30 seconds.
•
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
•
The Compressor stops when the intake air temperature reaches 3.5°C below internal setting temperature and continues for 3
minutes.
minutes.
•
When the Compressor stops operation, indoor fan stops for 330 seconds.
•
When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
•
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation immediately.
•
When the Compressor stops, the outdoor fan motor stops 30 seconds later.
21
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
B. Deodorizing Control
•
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available during anti-
freezing control.
freezing control.
•
When the compressor is in operation, the deodorizing status starts from 1
→
2.
•
When the compressor stops operation, the deodorizing status starts from 3
→
4
→
5.
•
If the compressor stops operation, indoor fan stops for 330 seconds.
C. Sensible Heat Control
•
This control is to improve the feeling in high fan speed and low operation frequency. When the operation frequency is less
than 33Hz (CU-G95KE) or 36Hz (CU-G125KE), the fan speed will reduce. When the operation frequency is increased to
40Hz (CU-C95KE) or 49Hz (CU-C125KE) continuously for 5 minutes, the fan speed will resume to normal condition. (During
Cooling operation).
than 33Hz (CU-G95KE) or 36Hz (CU-G125KE), the fan speed will reduce. When the operation frequency is increased to
40Hz (CU-C95KE) or 49Hz (CU-C125KE) continuously for 5 minutes, the fan speed will resume to normal condition. (During
Cooling operation).
22
S-G95KE CU-G95KE / CS-G125KE CU-G125KE
4.
Heating Operation
A. Room Temperature Control
•
During heating operation, the room temperature control depends on intake air temperature and internal setting temperature.
Basically it can be divided into 2 periods as shown below:
Basically it can be divided into 2 periods as shown below:
(i) When indoor fan speed is Medium of above.
23
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
(ii) When indoor fan speed is lower than Medium.
24
S-G95KE CU-G95KE / CS-G125KE CU-G125KE