121
TC: Cooling Capacity
IPT: Cooling Power Consumption
Model
Cooling capacities are based on conditions
CS-F50DB4E5
3 phase, 50Hz 400V
Cooling capacity
Indoor temp. 27
°C D.B. 19°C W.B.
13.5kW
Outdoor temp. 35
°C D.B.
Standard air volume 32 m
3
/min
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
25
°C
30
°C
35
°C
40
°C
43
°C
Air
TC
TC
TC
TC
TC
D.B.
W.B.
kW
kW
kW
kW
kW
17
14.05
13.50
12.70
11.75
11.06
23
19
14.84
14.38
13.64
12.72
12.07
22
16.21
15.77
15.05
14.08
13.41
17
13.89
13.35
12.58
11.66
11.00
25
19
14.86
14.34
13.57
12.64
11.98
22
16.20
15.71
14.94
13.91
13.29
17
13.72
13.19
12.45
11.58
10.95
27
19
14.88
14.31
13.50
12.56
11.88
22
16.19
15.64
14.82
13.77
13.16
17
13.69
13.20
12.42
11.67
11.09
29
19
14.85
14.31
13.51
12.65
12.03
22
16.12
15.57
14.73
13.79
13.15
17
13.67
13.20
11.55
11.73
11.18
32
19
14.82
14.31
13.51
12.72
12.12
22
16.08
15.53
14.71
13.80
13.15
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
25
°C
30
°C
35
°C
40
°C
43
°C
Air
IPT
IPT
IPT
IPT
IPT
D.B.
W.B.
kW
kW
kW
kW
kW
17
4.03
4.36
4.75
5.21
5.53
23
19
4.27
4.62
5.04
5.52
5.86
22
4.61
4.99
5.44
5.97
6.33
17
4.03
4.36
4.74
5.18
5.49
25
19
4.29
4.64
5.05
5.51
5.84
22
4.64
5.01
5.45
5.95
6.31
17
4.04
4.35
4.73
5.15
5.45
27
19
4.32
4.65
5.06
5.50
5.83
22
4.66
5.02
5.46
5.94
6.30
17
4.01
4.34
4.68
5.02
5.24
29
19
4.29
4.64
5.00
5.37
5.60
22
4.72
5.11
5.51
5.91
6.16
17
4.00
4.34
4.64
4.94
5.09
32
19
4.27
4.63
4.96
5.28
5.44
22
4.77
5.17
5.54
5.89
6.07
122
13.3.2.
Heating Performance
HC: Heating Capacity
IPT: Heating Power Consumption
Model
Heating capacities are based on conditions
CS-F24DB4E5
Single phase, 50Hz 230V
Heating capacity
Indoor temp. 20
°C D.B.
7.1kW
Outdoor temp. 7
°C D.B. 6°C W.B.
Standard air volume 18 m
3
/min
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
HC
HC
HC
HC
D.B.
kW
kW
kW
kW
15
5.18
6.21
7.46
8.66
20
4.90
5.86
7.10
8.52
25
4.62
5.54
6.75
8.17
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
IPT
IPT
IPT
IPT
D.B.
kW
kW
kW
kW
15
1.65
1.89
2.24
2.64
20
1.75
2.01
2.36
2.74
25
1.84
2.12
2.48
2.80
123
HC: Heating Capacity
IPT: Heating Power Consumption
Model
Heating capacities are based on conditions
CS-F28DB4E5
Single phase, 50Hz 230V, Three phase, 50Hz 400V
Heating capacity
Indoor temp. 20
°C D.B.
8kW
Outdoor temp. 7
°C D.B. 6°C W.B.
Standard air volume 20 m
3
/min
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
HC
HC
HC
HC
D.B.
kW
kW
kW
kW
15
5.84
7.00
8.40
9.76
20
5.52
6.60
8.00
9.60
25
5.20
6.24
7.60
9.20
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
IPT
IPT
IPT
IPT
D.B.
kW
kW
kW
kW
15
1.82
2.08
2.47
2.91
20
1.92
2.21
2.60
3.02
25
2.03
2.34
2.73
3.05
124
HC: Heating Capacity
IPT: Heating Power Consumption
Model
Heating capacities are based on conditions
CS-F34DB4E5
Single phase, 50Hz 230V
Heating capacity
Indoor temp. 20
°C D.B.
11.2kW
Outdoor temp. 7
°C D.B. 6°C W.B.
Standard air volume 27 m
3
/min
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
HC
HC
HC
HC
D.B.
kW
kW
kW
kW
15
8.18
9.80
11.76
13.66
20
7.73
9.24
11.20
13.44
25
7.28
8.74
10.64
12.88
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
IPT
IPT
IPT
IPT
D.B.
kW
kW
kW
kW
15
2.70
3.09
3.67
4.32
20
2.86
3.28
3.86
4.48
25
3.01
3.47
4.05
4.57