Panasonic CS-F14DB4E5 / CU-B14DBE5 / CS-F18DB4E5 / CU-B18DBE5 Service Manual ▷ View online
37
9.8.8.
Four-way Valve Error Detection Control
• The four-way valve error detection control starts when:
- During cooling operation, when indoor heat exchanger temperature exceeds 45°C in 5 minutes after compressor starts.
- During heating operation, when indoor heat exchanger temperature is below 5°C in 5 minutes after compressor starts.
- During heating operation, when indoor heat exchanger temperature is below 5°C in 5 minutes after compressor starts.
• During four-way valve error, compressor is shut down and indoor unit is set to thermo-off status.
• After 3 occasions, four-way valve error is displayed; all operation stopped except outdoor fan remaining heat removal control.
• After 3 occasions, four-way valve error is displayed; all operation stopped except outdoor fan remaining heat removal control.
9.8.9.
Valve Error Detection Control
• This control is to protect the compressor.
• Valve error is detected if comply with condition below:
• Valve error is detected if comply with condition below:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 7 minutes).
- Indoor heat exchanger temperature at compressor start -3°C < current heat exchanger temperature for 1 minutes.
• During this error, four-way valve error is displayed; compressor is shutdown.
9.8.10.
High-pressure Switch Disconnection Error Detection Control
• High-pressure switch disconnection is detected when high-pressure switch input continuously open for 1 minutes while the com-
pressor shutdown.
• During this error, high-pressure switch error is displayed.
9.8.11.
Low-pressure Switch Disconnection Error Detection Control
• Low-pressure switch disconnection is detected when low-pressure switch input continuously open for 1 minutes while compres-
sor shutdown.
• During this error, low-pressure switch error is displayed.
9.9.
Test Run
• Test run is necessary after installation is completed.
• To enable forced cooling test run, at outdoor PCB, set the DS1 to ON position and DS2 to OFF position.
• To enable forced cooling test run, at outdoor PCB, set the DS1 to ON position and DS2 to OFF position.
• To enable forced heating test run, at outdoor PCB, set the DS1 to ON position and DS2 to ON position.
• Press Test Run button at outdoor pcb for 1 second.
38
10 Installation Instruction
10.1. Pipe length
• CORRECTION OF CAPACITIES
1. Correction of capacities according to the connecting pipe length.
The data of rated capacities (marked on the name plate) are based on 7.5 meters connecting pipe and horizontal installation.
2. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
Note :
Piping elevation B = outdoor unit installed at top
Piping elevation C = outdoor unit installed at bottom
Piping elevation B = outdoor unit installed at top
Piping elevation C = outdoor unit installed at bottom
Piping Size / Length & Elevation
Model No.
Piping size
Piping
length
length
(A)
Piping
elevation
(B)
Piping
elevation
(C)
Piping
Chargeless
Add
Refrigerant
Liquid /
High
Valve
Gas /
Low
Valve
Max(m)
Max(m)
Max(m)
Max(m)
(g/m)
Cassette
R410A CS-F14DB4E5
6.35
3-ways
12.70
3-ways
30
30
20
20
20
type
CS-F18DB4E5
39
10.2. Refrigerant additional charge
1. Piping installation by standard piping
• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 20 m.
(Refer the following table)
But when the piping length exceeds 20m, additional charge is required according to the following table.
Example:
CU-B24DBE5
In case of 30m long pipe (one way), the amount of refrigerant to be replenished is: (30 - 20) x 20 = 200g
But when the piping length exceeds 20m, additional charge is required according to the following table.
Example:
CU-B24DBE5
In case of 30m long pipe (one way), the amount of refrigerant to be replenished is: (30 - 20) x 20 = 200g
10.3. Position of the centre gravity
Model Name
Standard piping specification
Liquid piping
(dia.mm)
Gas piping
(dia.mm)
Gas chargeless
length (m)
Additional gas
volume (g/m)
CU-B14DBE5
6.35
12.70
20
20
CU-B18DBE5
6.35
12.70
20
20
MODEL NAME
OUTSIDE DIMENSIONS
NET WEIGHT
CENTRE OF GRAVITY
WIDTH (mm)
DEPTH (mm)
HEIGHT (mm)
kg
X (mm)
Y (mm)
Z (mm)
CU-B14DBE5
900
320
795
69
560
150
320
CU-B18DBE5
900
320
795
69
560
150
320
40
10.4. Indoor unit installation
• Precautions shown here are differentiated between
Warnings and
Cautions. Those that have much chances for leading to
significant result such as fatality or serious injury if wrong installation would have been carried out are listed compiling them
especially into the column of
Warnings.
However, even in the case of items which are listed in the column of
Cautions, such items also have a chance for leading to
significant result depending on the situations.
In either case, important descriptions regarding the safety are listed, then observe them without fail.
In either case, important descriptions regarding the safety are listed, then observe them without fail.
• As to indications with illustration
• After installation work has been completed, do not only make sure that the unit is free from any abnormal condition through the
execution of try run but also explain how to use and how to perform maintenance of this unit to the customer according to the
instruction manual.
In addition, request the customer to keep this manual for installation work together with instruction manual.
instruction manual.
In addition, request the customer to keep this manual for installation work together with instruction manual.
FOUR WAY CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS
Precautions in terms of safety
Carry out installation work with reliability after thorough reading of this “Precautions in terms of safety”.
This mark means “Caution” or “Warning”.
This mark means “Earth”.
Warnings
The appliance must be installed by technician, who takes into
account the requirements given by ISO5149 or eventual equivalent
requirements.
account the requirements given by ISO5149 or eventual equivalent
requirements.
If installing inside a small room, measures should be taken to pre-
vent refrigerant levels from building up to critical concentrations in
the event of a refrigerant leak occurring. Please discuss with the
place of purchase for advice on what measures may be necessary
to prevent critical concentrations being exceeded. If the refrigerant
leaks and reaches critical concentration levels, there is the danger
that death from suffocation may result.
vent refrigerant levels from building up to critical concentrations in
the event of a refrigerant leak occurring. Please discuss with the
place of purchase for advice on what measures may be necessary
to prevent critical concentrations being exceeded. If the refrigerant
leaks and reaches critical concentration levels, there is the danger
that death from suffocation may result.
As to installation, request the distributor or vendor to perform it.
Imperfection in installation caused by that having been carried out
by the customer himself may lead to water leakage, electric shock,
fire, etc.
Imperfection in installation caused by that having been carried out
by the customer himself may lead to water leakage, electric shock,
fire, etc.
Securely attach the protective covers for the outdoor unit connec-
tion cables and power cord so that they do not lift up after installa-
tion. If the covers are not properly attached and installed, the
terminal connections may overheat, and fire or electric shock may
result.
tion cables and power cord so that they do not lift up after installa-
tion. If the covers are not properly attached and installed, the
terminal connections may overheat, and fire or electric shock may
result.
Carry out the installation work with reliability according to this
manual for installation work.
Imperfection in installation leads to water leakage, electric shock,
fire, etc.
manual for installation work.
Imperfection in installation leads to water leakage, electric shock,
fire, etc.
Switch off all supplies before accessing any electrical part.
Carry out the installation work with reliability on the place that can
bear the weight of this unit sufficiently. Insufficient strength leads to
injury due to falling of the unit.
bear the weight of this unit sufficiently. Insufficient strength leads to
injury due to falling of the unit.
If refrigerant gas escapes during installation, ventilate the affected
area. If the refrigerant gas comes into contact with sparks or naked
flames, it will cause toxic gases to be generated.
area. If the refrigerant gas comes into contact with sparks or naked
flames, it will cause toxic gases to be generated.
Carry out predetermined installation work in preparation for strong
wind such as typhoon, earthquake. Imperfection in installation
work may lead to accidents arisen from overturn, etc.
wind such as typhoon, earthquake. Imperfection in installation
work may lead to accidents arisen from overturn, etc.
Once installation work is completed, check that there are no refrig-
erant gas in the room that can come into contact with sparks or
flames from a fan heater, stove or kitchen range, which will cause
toxic gases to be generated.
erant gas in the room that can come into contact with sparks or
flames from a fan heater, stove or kitchen range, which will cause
toxic gases to be generated.
Click on the first or last page to see other CS-F14DB4E5 / CU-B14DBE5 / CS-F18DB4E5 / CU-B18DBE5 service manuals if exist.