17.4.20  F17 (Indoor Standby Units Freezing Abnormality) 
Malfunction Decision Conditions 
š  When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor 
pipe temperature is below -1.0°C. 
 
Remark: 
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor 
unit and H39 to other indoor unit(s). 
 
Malfunction Caused 
š  Wrong wiring connection 
š Faulty 
sensor 
š  Faulty expansion valve 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
114 
17.4.21  F90 (Power Factor Correction Protection) 
Malfunction Decision Conditions 
š  To maintain DC voltage level supply to power transistor. 
š  To detect high DC voltage level after rectification. 
 
Malfunction Caused 
š  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at 
the outdoor unit main PCB senses abnormal DC voltage level for power transistors. 
š  When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level. 
š  When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFF 
relay RY-C. 
 
Troubleshooting 
 
 
 
 
 
 
115 
17.4.22  F91 (Refrigeration Cycle Abnormality) 
Malfunction Decision Conditions 
š  The input current is low while the compressor is running at higher than the setting frequency. 
 
Malfunction Caused 
š  Lack of gas. 
š  3-way valve close. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
116 
17.4.23  F93 (Compressor Rotation Failure) 
Malfunction Decision Conditions 
š  A compressor rotation failure is detected by checking the compressor running condition through the position 
detection circuit. 
 
Malfunction Caused 
š  Compressor terminal disconnect 
š  Faulty Outdoor PCB 
š Faulty 
compressor 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 