17.4.16  H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) 
Malfunction Decision Conditions 
š  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. 
 
Malfunction Caused 
š  Operation stops due to short circuit inside the fan motor winding. 
š  Operation stops due to breaking of wire inside the fan motor. 
š  Operation stops due to breaking of fan motor lead wires. 
š  Operation stops due to Hall IC malfunction. 
š  Operation error due to faulty outdoor unit PCB. 
 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
110 
17.4.17  H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED 
flashing) 
Malfunction Decision Conditions 
š  Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is 
operating in heating operation. 
š  Phenomena: unit is stopping and re-starting very often in heating mode. 
 
Malfunction Caused 
š  Indoor heat exchanger thermistor 
š  Clogged air filter or heat exchanger 
š  Over-bent pipe (liquid side) 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
111 
17.4.18  H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) 
Error Code will not display (no Timer LED blinking) but store in EEPROM 
 
Malfunction Decision Conditions 
š  Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) 
 
Malfunction Caused 
š  Air short circuit at indoor unit 
š  Clogged indoor unit air filter 
š  Dust accumulation on the indoor unit heat exchanger 
š  2/3 way valve closed 
š  Faulty indoor unit fan motor 
š Refrigerant 
shortage 
(refrigerant leakage) 
š  Clogged expansion valve or strainer 
š  Faulty indoor pipe temperature sensor 
š  Faulty indoor unit PCB 
 
Troubleshooting 
 
 
 
 
 
 
 
112 
17.4.19  F11 (4-way Valve Switching Failure) 
Malfunction Decision Conditions 
š  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during 
cooling and compressor operating, the 4-way valve is detected as malfunction. 
 
Malfunction Caused 
š  Indoor heat exchanger (pipe) thermistor 
š  4-way valve malfunction 
 
Troubleshooting 
 
 
 
* Check gas side pipe – for hot gas flow in cooling mode 
 
 
 
 
 
 
 
Page of 127