93 
Diagnosis 
display 
Abnormality / 
Protection control 
Abnormality 
Judgment 
Protection 
Operation 
Problem Check 
location 
H41 
Abnormal wiring or 
piping connection 
— — 
Wrong wiring and 
connecting pipe, expansion 
valve abnormality 
š Check indoor/outdoor 
connection wire and connection 
pipe 
š  Expansion valve and lead wire 
and connector 
H59 
ECONAVI sensor 
abnormality 
Continuous for 25s 
— 
ECONAVI sensor open or 
short circuit 
š  ECONAVI sensor (defective or 
disconnected) 
š ECONAVI PCB 
H64 
Outdoor high 
pressure sensor 
abnormality 
Continuous for 
1 minute 
— 
High pressure sensor open 
circuit during compressor 
stop 
š  High pressure sensor 
š  Lead wire and connector 
H70 
Light sensor 
abnormality 
Continuous for 
24 hours, 15days 
— 
Light sensor open or 
short circuit 
š  Light sensor (defective or 
disconnected) 
H97 
Outdoor fan motor 
mechanism lock 
2 times happen 
within 30 minutes 
— 
Outdoor fan motor lock or 
feedback abnormal 
š  Outdoor fan motor lead wire 
and connector 
š  Fan motor lock or block 
H98 
Indoor high pressure 
protection 
— — 
Indoor high pressure 
protection (Heating) 
š  Check indoor heat exchanger 
š  Air filter dirty 
š  Air circulation short circuit 
H99 
Indoor operating unit 
freeze protection 
— — 
Indoor freeze protection 
(Cooling) 
š  Check indoor heat exchanger 
š  Air filter dirty 
š  Air circulation short circuit 
F11 
4-way valve 
switching 
abnormality 
4 times happen 
within 30 minutes 
— 
4-way valve switching 
abnormal 
š 4-way valve 
š  Lead wire and connector 
F17 
Indoor standby units 
freezing abnormality 
3 times happen 
within 40 minutes 
— 
Wrong wiring and 
connecting pipe, expansion 
valve leakage, indoor heat 
exchanger sensor open 
circuit 
š Check indoor/outdoor 
connection wire and pipe 
š  Indoor heat exchanger sensor 
lead wire and connector 
š  Expansion valve lead wire and 
connector 
F90 
Power factor 
correction 
(PFC) circuit 
protection  
4 times happen 
within 10 minutes 
— 
Power factor correction 
circuit abnormal 
š  Outdoor PCB faulty 
F91 
Refrigeration cycle 
abnormality 
2 times happen 
within 20 minutes 
— 
Refrigeration cycle 
abnormal 
š  Insufficient refrigerant or valve 
close 
F93 
Compressor 
abnormal revolution 
4 times happen 
within 20 minutes 
— 
Compressor abnormal 
revolution 
š  Power transistor module faulty 
or compressor lock 
F94 
Compressor 
discharge overshoot 
protection 
4 times happen 
within 30 minutes 
— 
Compressor discharge 
pressure overshoot 
š  Check refrigeration system 
F95 
Outdoor cooling high 
pressure protection 
4 times happen 
within 20 minutes 
— 
Cooling high pressure 
protection 
š  Check refrigeration system 
š  Outdoor air circuit 
F96 
Power transistor 
module overheating 
protection 
4 times happen 
within 30 minutes 
— 
Power transistor module 
overheat 
š PCB faulty 
š  Outdoor air circuit (fan motor) 
F97 
Compressor 
overheating 
protection 
3 times happen 
within 30 minutes 
— Compressor 
overheat 
š Insufficient refrigerant 
F98 
Total running current 
protection 
3 times happen 
within 20 minutes 
— Total 
current 
protection 
š  Check refrigeration system 
š  Power source or compressor 
lock 
F99 
Outdoor direct 
current (DC) peak 
detection 
Continuous 
happen for 7 times 
— 
Power transistor module 
current protection 
š  Power transistor module faulty 
or compressor lock 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
94 
17.4 Self-diagnosis 
Method 
17.4.1  H11 (Indoor/Outdoor Abnormal Communication) 
Malfunction Decision Conditions 
š  During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal 
transmission is checked whether it is normal. 
 
Malfunction Caused 
š  Faulty indoor unit PCB. 
š  Faulty outdoor unit PCB. 
š  Indoor unit-outdoor unit signal transmission error due to wiring error. 
š  Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the 
indoor and outdoor units. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
95 
17.4.2  H12 (Indoor/Outdoor Capacity Rank Mismatched) 
Malfunction Decision Conditions 
š  During startup, error code appears when different types of indoor and outdoor units are interconnected. 
 
Malfunction Caused 
š  Wrong models interconnected. 
š  Wrong indoor unit or outdoor unit PCBs mounted. 
š  Indoor unit or outdoor unit PCBs defective. 
š  Indoor-outdoor unit signal transmission error due to wrong wiring. 
š  Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor 
and outdoor units. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
96 
17.4.3  H14 (Indoor Intake Air Temperature Sensor Abnormality) 
Malfunction Decision Conditions 
š  During startup and operation of cooling and heating, the temperatures detected by the indoor intake air 
temperature sensor are used to determine sensor errors. 
 
Malfunction Caused 
š Faulty 
connector 
connection. 
š Faulty 
sensor. 
š Faulty 
PCB. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 