15.2. Relationship Between The Condition Of The Air Conditioner And
Pressure And Electric Current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
Cooling Mode
Heating Mode
Condition of the
air conditioner
Low Pressure
High Pressure
Electric current 
during operation
Low Pressure
High Pressure
Electric current 
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or 
Strainer
Short circuit in the indoor 
unit
Heat radiation deficiency of
the outdoor unit
Inefficient compression
46
15.3. Breakdown Self Diagnosis Function
15.3.1.
Self Diagnosis Function (Three Digits Alphanumeric Code)
• Once abnormality has occurred during operation, the unit
will stop its operation, and Timer LED blinks.
• Although Timer LED goes off when power supply is turned
off, if the unit is operated under a breakdown condition, the
LED will light up again.
• In operation after breakdown repair, the Timer LED will no
more blink. The last error code (abnormality) will be stored in
IC memory.
• To make a diagnosis
1. Timer LED start to blink and the unit automatically
stops the operation.
2. Press the CHECK button on the remote controller
continuously for 5 seconds.
3. “- -” will be displayed on the remote controller display.
Note: Display only for “- -”. (No transmitting signal, no
receiving sound and no Power LED blinking.)
4. Press the “TIMER” 
 or 
 button on the remote
controller. The code “H00” (no abnormality) will be
displayed and signal will be transmitted to the main
unit.
5. Every press of the button (up or down) will increase
abnormality numbers and transmit abnormality code
signal to the main unit.
6. When the latest abnormality code on the main unit
and code transmitted from the remote controller are
matched, power LED will light up for 30 seconds and
a beep sound (continuously for 4 seconds) will be
heard. If no codes are matched, power LED will light
up for 0.5 seconds and no sound will be heard.
7. The breakdown diagnosis mode will be canceled
unless pressing the CHECK button continuously for 5
seconds or operation the unit for 30 seconds.
8. The LED will be off if the unit is turned off or the
RESET button on the main unit is pressed.
• To display memorized error (Protective operation)
status:
1. Turn power on.
2. Press the CHECK button on the remote controller
continuously for 5 seconds.
3. “- -” will be displayed on the remote controller display.
Note: Display only for “- -”. (No transmitting signal, no
receiving sound and no Power LED blinking.)
4. Press the “TIMER” 
 or 
 button on the remote
controller. The code “H00” (no abnormality) will be
displayed and signal will be transmitted to the main
unit. The power LED lights up. If no abnormality is
stored in the memory, three beeps sound will be
heard.
5. Every press of the button (up or down) will increase
abnormality numbers and transmit abnormality code
signal to the main unit.
6. When the latest abnormality code on the main unit
and code transmitted from the remote controller are
matched, power LED will light up for 30 seconds and
a beep sound (continuously for 4 seconds) will be
heard. If no codes are matched, power LED will light
up for 0.5 seconds and no sound will be heard.
7. The breakdown diagnosis mode will be canceled
unless pressing the CHECK button continuously for 5
seconds or operating the unit for 30 seconds.
8. The same diagnosis can be repeated by turning
power on again.
• To clear memorized error (Protective operation) status
after repair:
1. Turn power on (in standby condition).
2. Press the AUTO button for 5 seconds (A beep
receiving sound) on the main unit to operate the unit
at Forced Cooling Operation mode.
3. Press the CHECK button on the remote controller for
about 1 second with a pointed object to transmit
signal to main unit. A beep sound is heard from main
unit and the data is cleared.
• Temporary Operation (Depending on breakdown status)
1. Press the AUTO button (A beep receiving sound) on
the main unit to operate the unit. (Remote control will
become possible.)
2. The unit can temporarily be used until repaired.
Error Code
Operation
Temporary items
H23
Cooling
Emergency Operation with limited
power
H27, H28
Cooling, Heating
H26
Cooling, Heating
Emergency Operation without
power limit
47
15.4. Error Codes Table
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “CHECK” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one “beep” to four “beep” sounds.
Abnormality / Protection control
Abnormality
Judgement
Emergency 
operation
Primary location to verify
Diagnosis
display
H00
No abnormality detected
Normal operation
H11
Indoor / outdoor abnormal communication
> 1 min. after start-
ing operation
Indoor fan
operation only
• Internal / external cable connections
• Indoor / Outdoor PCB
H12
Connection capability rank abnormal
H14
Indoor intake air temperature sensor abnor-
mality
Continue for 5 sec.
• Intake air temperature sensor 
(defective or disconnected)
H15
Outdoor compressor temperature sensor 
abnormality
Continue for 5 sec.
• Compressor temperature sensor 
(defective or disconnected)
H16
Outdoor Current Transformer open circuit
• Outdoor PCB
• IPM (Power transistor) module
H19
Indoor fan motor merchanism lock
• Indoor PCB
• Fan motor
H21
Indoor float switch operation abnormal
H23
Indoor heat exchanger temperature sensor 1 
abnormality
Continue for 5 sec.
O
 (Cooling only)
• Heat exchanger temperature sensor 
1 (defective or disconnected)
H24
Indoor heat exchanger temperature sensor 2 
abnormality
Continue for 5 sec.
• Heat exchanger temperature sensor 
2 (defective or disconnected)
H27
Outdoor air temperature sensor abnormality
Continue for 5 sec.
O
• Outdoor temperature sensor 
(defective or disconnected)
H28
Outdoor heat exchanger temperature sensor 
abnormality
Continue for 5 sec.
O
• Outdoor heat exchanger temperature 
sensor (defective or disconnected)
H30
Discharge temperature sensor abnormality
Continue for 5 sec.
• Discharge temperature sensor
H33
Indoor/Outdoor wrong connection
• Indoor/Outdoor supply voltage
H35
Indoor drain water adverse current abnormal
H38
Indoor/Outdoor mismatch
H97
Outdoor Fan Motor lock abnormality
2 times occurrence 
within 30 minutes
• Outdoor PCB
• Outdoor Fan Motor
H98
Indoor high pressure protection
• Air filter dirty
• Air circulation short circuit
H99
Indoor heat exchanger anti-freezing 
protection
• Insufficient refrigerant
• Air filter dirty
F11
Cooling / Heating cycle changeover
abnormality
4 times occurrence 
within 30 minutes
• 4-way valve
• V-coil
F90
PFC control
4 times occurrence 
within 10 minutes
• Voltage at PFC
F91
Refrigeration cycle abnormality
2 times occurrence 
within 20 minutes
• No refrigerant
(3-way valve is closed)
F93
Outdoor compressor abnormal revolution
4 times occurrence 
within 20 minutes
• Outdoor compressor
F95
Cool high pressure protection
4 times occurrence 
within 20 minutes
• Outdoor refrigerant circuit
F96
IPM (power transistor) overheating protection
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
F97
Outdoor compressor overheating protection
4 times occurrence 
within 20 minutes
• Insufficient refrigerant
• Compressor
F98
Total running current protection
3 times occurrence 
within 20 minutes
• Excess refrigerant
• Improper heat radiation
F99
Outdoor Direct Current (DC) peak detection
7 times occurrence 
continuously
• Outdoor PCB
• IPM (Power transistor)
• Compressor
48
15.5. Self-diagnosis Method
15.5.1.
H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
• During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused
• Faulty indoor unit PCB.
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
units.
• Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting