DOWNLOAD Panasonic CS-E10HB4EA / CS-E15HB4EA / CS-E18HB4EA / CS-E21HB4EAS / CU-E10HBEA / CU-E15HBEA / CU-E18HBEA / CU-E21HBEA Service Manual ↓ Size: 6.86 MB | Pages: 88 in PDF or view online for FREE

Model
CS-E10HB4EA CS-E15HB4EA CS-E18HB4EA CS-E21HB4EAS CU-E10HBEA CU-E15HBEA CU-E18HBEA CU-E21HBEA
Pages
88
Size
6.86 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-e10hb4ea-cs-e15hb4ea-cs-e18hb4ea-cs-e21hb4eas-c.pdf
Date

Panasonic CS-E10HB4EA / CS-E15HB4EA / CS-E18HB4EA / CS-E21HB4EAS / CU-E10HBEA / CU-E15HBEA / CU-E18HBEA / CU-E21HBEA Service Manual ▷ View online

49
13 Protection Control
13.1. Protection Control For All Operations
13.1.1.
Restart Control (Time Delay Safety Control)
• The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by
pressing OFF/ON button at remote control within this period.
• This control is not applicable if the power supply is cut off and on again.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2.
30 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON button at the remote
control is permitted or the Auto OFF/ON button at indoor unit.
• The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
13.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
E10HB
E15HB
E18HB
E21HB
Operation Mode
 X (A)
Y (A)
 X (A)
Y (A)
 X (A)
Y (A)
 X (A)
Y (A)
Cooling/Soft Dry (A) & (C)
4.95
15.06
7.79
15.06
8.83
15.06
10.32
15.06
Cooling/Soft Dry (B)
4.43
15.06
6.06
15.06
7.79
15.06
9.17
15.06
Heating
6.21
15.06
9.00
15.06
10.08
15.06
11.53
15.06
50
13.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110
°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95
°C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 22.33 ± 5.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minutes. 
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
13.1.5.
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
If compressor discharge temperature exceeds 112
°C, compressor will be stop, occurs 4 times per 20 minutes, timer LED will be
blinking (“F97” is to be confirmed).
13.2. Protection Control For Cooling & Soft Dry Operation
13.2.1.
Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust base on Outdoor Air Temperature.
51
13.2.2.
Cooling Overload Control
i. Pipe temperature limitation/restriction
• Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)
• The compressor stop if outdoor pipe temperature exceeds 63
°C.
• If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection)
13.2.3.
Dew Prevention Control 1
1. To prevent dew formation at indoor unit discharge area.
2. This control activated if:
• Outdoor air temperature and Indoor pipe temperature judgment by microcontroller if fulfilled.
• When Cooling or Dry mode is operated more than 20 minutes or more.
3. This control stopped if:
• Compressor stopped.
• Remote control setting changed. (fan speed / temperature)
• Outdoor air temperature and indoor intake temperature changed.
4. Fan speed, angle of louver (vertical airflow angle) will be adjusted accordingly in this control.
• Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
• The angle of horizontal louver will be changed as table below:
13.2.4.
Dew Prevention Control 2
1. To prevent dew formation at indoor unit discharge area.
2. This control starts if all conditions continue for 20 minutes:
• Operated with Cooling or Soft Dry Mode.
• Indoor intake temperature is between 25
°C and 29°C.
• Outdoor air temperature is less than 30
°C.
• Quiet Lo fan speed.
3. This control stopped if:
• When receive air swing change signal from Remote Control.
4. The horizontal louver will be fixed at 24
° (regardless of Auto or Manual Airflow Direction Setting)
13.2.5.
Freeze Prevention Control
1. When indoor heat exchanger temperature is lower than 7
°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 13
°C.
3. At the same time, indoor fan speed will be higher than during its normal operation.
4. If indoor heat exchanger temperature is higher than 13
°C for 5 minutes, the fan speed will return to its normal operation.
Operation Mode
Airflow Direction
Vane Angle (
°)
1
2
3
4
5
Cooling
Auto 
30 ~ 60
Manual
30
37.5
45
52.5
60
52
13.3. Protection Control For Heating Operation
13.3.1.
Intake Air Temperature Control
Compressor will operate at maximum frequency if below conditions occur:
1. When the indoor intake air temperature is 30
°C or above.
13.3.2.
Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14
°C in order to avoid compressor
overloading.
13.3.3.
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
If the heat exchanger temperature exceeds 60
°C, compressor will stop.
13.3.4.
Cold Draught Operation
When indoor pipe temperature is low, cold draught operation start where indoor fan speed will be reduced.
13.3.5.
Deice Operation
When outdoor pipe temperature and outdoor temperature is low, deice operation start where indoor fan motor and outdoor fan
motor stop and operation LED blinks.
Page of 88
Display

Click on the first or last page to see other CS-E10HB4EA / CS-E15HB4EA / CS-E18HB4EA / CS-E21HB4EAS / CU-E10HBEA / CU-E15HBEA / CU-E18HBEA / CU-E21HBEA service manuals if exist.