Panasonic CS-E10HB4EA / CS-E15HB4EA / CS-E18HB4EA / CS-E21HB4EAS / CU-E10HBEA / CU-E15HBEA / CU-E18HBEA / CU-E21HBEA Service Manual ▷ View online

41
1. Press AUTO SW continuously for 11 seconds (buzzer
sound = pep pep pep)
2. After 11 seconds, release AUTO SW, then press Remo-
Con TIMER “
” SW continuously for 5 seconds. Reset
code will be transmitted. After the reset code is
transmitted, release TIMER “
” SW.
3. Press Remo-Con “OFF/ON” button. The new Remo-Con
No. will be accepted and memorized, after which the new
Remo-Con No. can be used.
1. Remove the batteries from the battery compartment of
the Remote Control.
2. On the left side of the battery compartment, there is a
small opening in the centre in which Jumper (J_A) can be
seen. In the accepted Remo-Con PCB shown beside,
Jumper (J_B) can be seen.
• Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature
control, etc.)
• With regards to installation of the parts sold separately, follow the installation manual which is provided with the parts sold
separately.
CHANGING THE REMOTE CONTROL TRANSMISSION
CODE
REMO-CON NO. CHANGE IN REMOTE CONTROL
J_A
J_B
Remo-Con No.
Short
Open
A (Default)
Open
Open
B
Short
Short
C
Open
Short
D
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Is the cooling/heating operation normal?
Has the heat insulation been carried out at flare nut connections?
Is the indoor unit properly secured to the installation plate?
Is the connecting cable being fixed to the terminal board firmly?
Is the power supply voltage complied with rated value?
Is the connecting cable being clamped firmly?
Is there any abnormal sound?
Is the drainage OK?
Is the thermostat operation normal?
Is the Earth wire connection properly done?
Is the remote control’s LCD operation normal?
HAND OVER
As to parts to be sold separately
42
12 Operation and Control
12.1. Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes,
automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the
microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature
shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that
judging the condition according to internal setting temperature and intake air temperature.
12.1.1.
Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes.
These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value
will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.
12.1.2.
Cooling Operation
12.1.2.1. Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5
°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
12.1.3.
Soft Dry Operation
12.1.3.1. Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperate < -2.0
°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
12.1.4.
Heating Operation
12.1.4.1. Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperate > +2.0
°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF
point.
43
12.1.5.
Automatic Operation
• This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control
operation mode, indoor intake air temperature and outdoor air temperature.
• During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to
detect the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.
Every 30 minutes, the indoor and outdoor temperature is judged. Based on remote control setting temperature, the value of T1 will
increase up to 10
°C, T2 will decreased by 3°C and T3 will decreased up to 8°C.
The Auto Operation Mode shifting will take place whenever operation mode changed from Cooling/Soft Dry to Heating or vice
versa.
12.1.6.
Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry]
• Fan motor’s number of rotation is determined according to remote control setting.
[Heating]
• Fan motor’s number of rotation is determined according to remote control setting.
ii. Auto Fan Speed
[Cooling, Dry]
• According to room temperature and setting temperature, indoor fan speed is determined automatically.
• The indoor fan will operate according to pattern below.
Remote Control
O
O
O
O
O
Tab (rpm)
Hi
Me+
Me
Me-
Lo
Remote Control
O
O
O
O
O
Tab (rpm)
Shi
Me+
Me
Me-
Lo
44
[Heating]
• According to indoor pipe temperature, automatic heating fan speed is determined as follows.
B. Feedback control
• Immediately after the fan motor started, feedback control is performed once every second.
• During fan motor on, if fan motor feedback   2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error counter
increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan motor error is detected.
Operation stops and cannot on back.
12.1.7.
Outdoor Fan Motor Operation
Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after compres-
sor stops operation.
12.2. Airflow Direction
1. There is one type of airflow, vertical airflow (directed by horizontal vane).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger
temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
12.2.1.
Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (
°)
1
2
3
4
5
Heating
Auto with Heat Exchanger 
A
Downward fix
70
B
Downward fix
70
Temperature
C
Upward fix
20
D
Upward fix
20
Manual
20
33
45
58
70
Cooling
Auto 
20 ~ 70
Manual
20
33
45
58
70
Soft Dry
Auto 
20 ~ 70
Manual
20
33
45
58
70
Page of 88