11 Installation Instruction
11.1. Select The Best Location
INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
Example: For C7HKD
If the unit is installed at 10 m distance, the quantity of additional
refrigerant should be 25 g ...... (10 - 7.5) m x 10 g/m = 25 g
If the unit is installed at 10 m distance, the quantity of additional
refrigerant should be 25 g ...... (10 - 7.5) m x 10 g/m = 25 g
11.2. Indoor/Outdoor Unit
Installation Diagram
Piping size
Rated
Length
(m)
Max
Elevation
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Model
Gas Liquid
C7HKD
C9HKD
C9HKD
3/8”
1/4”
7.5
5
3
10
10
A7HKD
A9HKD
A9HKD
3/8”
1/4”
7.5
5
3
10
20
C12HKD 1/2”
1/4”
7.5
5
3
15
10
A12HKD 1/2”
1/4”
7.5
5
3
15
20