29
12.3. Soft Dry Operation
• Soft Dry operation can be set using remote control.
• Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
• This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
• When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown in
below figure.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
12.3.1. Soft Dry Operation Time Diagram
30
12.4. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• Operation mode will be determine again for judgement after 1 hour of operation, if the room temperature reaches to set
temperature and compressor off time is over 7 minutes 30 seconds continuously.
*
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps
running) eventhough after 1 hour from automatic operation mode started.
• Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as
shown in below table by pressing on the temperature up or temperature down button at remote control.
Standard for Determining Operation Mode
2nd Judgement onwards
Present
Mode
Judgement
Next Mode
Cooling
Soft Dry
Heating
Cooling
O
(Judgement:
23
°C & Above)
Not Applicable
O
(Judgement:
Below 23
°C)
23
°C
Cooling
Heating
Soft Dry
Not Applicable
O
(Judgement:
20
°C & Above)
O
(Judgement:
Below 20
°C)
20
°C
Soft Dry
Heating
Heating
O
(Judgement:
25
°C & Above)
Not Applicable
O
(Judgement:
Below 25
°C)
25
°C
Cooling
Heating
Operation
Hi
(Standard)
Lo
(+2
°C)
(±0
°C)
(-2
°C)
Cooling
27
°C
25
°C
23
°C
Soft Dry
24
°C
22
°C
20
°C
Heating
23
°C
21
°C
19
°C
31
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX03 at printed circuit board indoor unit.
12.5. Operation Control
(For 11.5.1. to 11.5.7. information applies only to Cooling and Soft Dry Operation)
12.5.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
12.5.2. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
12.5.3. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
32
12.5.4. Freezing Prevention Control
• If the temperature of the indoor heat exchanger falls below 2
°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10
°C (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
12.5.5. Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5
°C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
▲ T = Intake air temperature - Indoor heat exchanger temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
12.5.6. Starting Current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to oper-
ate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
12.5.7. Anti-Dew Formation Control
• Purpose is to prevent dew formation on indoor unit air discharge area.
• When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formation will
activate:
- Remote Control setting temperature is less than 25°C.
- Compressor is on.
- Cooling operation mode.
-
Indoor Fan motor operate at Low fan speed or QLo.
• This control is cancelled immediately when above condition is changed.
• Anti-Dew formation is control by:
1. Increasing Air Flow Volume
a. Lo fan speed
Lo fan speed is changed to Lo+ after 30 min to prevent dew formation.
Page of 70