12.6. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
12.6.1. Fan Speed Rotation Chart
12.6.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
- Fan speed rotates in the range of Hi, Me and Lo-.
- Deodorizing Control will be activated.
Speed
CS-A24GKD
CS-A18GKD
Cool, Dry
Heat
S Hi
Hi
1650
1430
Hi
1570
1400
Me
Me
1480
1320
Lo+
Lo
1380
1270
Lo
1280
1190
Lo-
Lo-
1070
980
S Lo
S Lo
830
760
SS Lo
300
300
Q SHi
Q Hi
1550
1330
Q Hi
1470
1300
Q Me
Q Me
1380
1220
Q Lo
1280
1170
Q Lo
1180
1090
38
• Auto Fan Speed during Cooling operation:
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher volume of refrigerant
in liquid form returning to the compressor.
5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the
room. 
This is to obtain the actual reading of the intake air temperature.
6. For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and lesser noise
environment, after 70 seconds from the restart of compressor.
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
• Auto Fan Speed during Heating operation.
1. Indoor fan will rotate in the range of SLo 
→ Me according to the heat exchanger temperature.
39
12.6.3. Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
• There are 3 types of fan speed settings: Lo, Me, Hi.
12.7. Outdoor Fan Speed Control
• There is 2 speed for outdoor fan motor. Outdoor fan speed can be changed to Hi or Lo according to outdoor temperature.
• For Cooling or Soft Dry operation when outdoor temperature reaches to 31
°C (Hi-speed), 29°C (Lo-speed).
• For Heating operation when outdoor temperature reaches to 13.5
°C (Hi-speed), 15.5°C (Lo-speed)
• When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
• Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
12.8. Vertical Airflow Direction Control
12.8.1. Auto Control
(e-ion, Cooling and Soft Dry Operation condition)
• When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
• When stopped with remote control, the discharge vent is
reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that condition,
the louver will stop swinging and rest at the upper limit.
Cooling and Soft Dry Operation
(Heating Operation condition)
• When the piping air temperature reaches 38°C, the
• louver is changed from upper to lower limit. When the
• piping air temperature falls to 35°C, the louver is changed
from lower to upper limit.
Heating Operation
12.8.2. Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stopped with remote control, the discharge vent is reset, and stop at the closing position.
Cooling and Soft Dry Operation
Heating Operation
40
12.9. Horizontal Airflow Direction Control
12.9.1. Auto Control
• When the horizontal airflow direction is set to Auto using the
remote control, the vanes swings left and right for Cooling
and Soft Dry (0°-44°), Heating (8°-36°) as shown in the
diagram.
• When stopped with remote control, the discharge vane is
reset, and stop at the reset position.
• During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that condition,
the vane will stop swinging and rest at 22° angle.
• During Heating operation, the piping air temperature
reaches 38°C, the vanes swings left and right. When the
piping air temperature falls to 35°C, the vanes will stop
swing and rest at 22°.
12.9.2. Manual Control
• When the horizontal airflow direction is set to Manual using
the remote control, the automatic airflow is released and the
airflow direction vane move left and right in the range shown
in the diagram.
The louver can be adjusted by pressing the button to the
desired vane position.
• When stopped with remote control, the vanes is reset, and
stopped at reset position.