33
b. QLo fan speed
Dew formation may occurs at QLo cool, therefore QLo cool is operated only 1 hr 30 min (1 hr QLo, 30 min QLo +100
rpm). After that, it operates at QLo +180rpm (However Quiet LED remains on).
2. Norrowing
Vertical Airflow Direction
During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from 10° - 38° to 10° - 27° under
Cooling and Soft Dry operation mode.
During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 10°, 14°, 18°, 22°, 27° to
10°, 13°, 16°, 19°, 22° under Cooling and Soft Dry operation mode.
3. Narrowing
Horizontal Airflow Direction
During Anti-dew condensation prevention, Airflow Direction Auto-control angle change form 0° - 44° to 14° - 30° under 
Cooling and Soft Dry operation mode.
34
During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 0°, 11°, 22°, 33°, 44° to
14°, 18°, 22°, 26°, 30° under Cooling and Soft Dry operation mode.
(For 11.5.8 to 11.5.14 information applies only to Heating Operation)
12.5.8. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
12.5.9. Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between indoor heat
exchanger and intake air is 5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
▲ T = Indoor heat exchanger temperature - Intake air temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
12.5.10. Overload Protection Control
• Outdoor Fan Control
- If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor
Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as table below:
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
• Compressor High Pressure Control
- If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
- Time Delay Safety Control is activated before the compressor restart.
35
12.5.11. 4-Way Valve Control
• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.
12.5.12. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
12.5.13. Anti Cold Draft Control
12.5.14. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
• Normal Deicing
Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the outdoor
piping temperature drops to -4°C for 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minutes, deicing starts.
• Deicing ends when
(a) 12 minutes after deicing operation starts;
(b) The outdoor piping temperature rises to about 12°C.
• After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
36
a) Normal Deicing Time Diagram
(b) Overload Deicing Time Diagram