-27-
6. Wrap the insulation material around the
connecting portion.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material.
Bind them together with vinyl tape so that there
is no gap.
1. Route the indoor tubing and the drain hose to the
required piping hole position.
2. Insert the piping, drain hose and the connecting
cable into the piping hole.
Plastic bands
Insulation material
Drain pipe
Connecting cable
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Vinyl tape
(wide)
Wrap with vinyl tape
Indoor 
unit pipe
Pipe
Torque wrench
Indoor unit tubing
Spanner (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
When extending the drain hose at the indoor
unit, install the drain pipe.
Tighten the flare nut with a wrench.
Wrap the area which accommodates the rear
piping housing section with vinyl tape.
Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range
within which they fit into the rear piping housing
section.
For right rear piping
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
12K
9K
9k, 12k
1/2"[5.5kg.m]
1/4"[1.8kg.m]
Pipe Size[Torque]
Capacity
(Btu/h)
GAS
LIQUID
-28-
3. Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
4. Tape the drain hose and the connecting cable.
Connecting cable
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of
the installation plate.
Insert the spacer etc. between the indoor unit
and the installation plate and separate the
bottom of the indoor unit from the wall.
Installation plate
Spacer
Indoor unit
8cm
6. Connecting the pipings to the indoor unit and the
drain hose to drain pipe.
Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Tighten the flare nut with a wrench.
7. Wrap the insulation material around the
connecting portion.
Overlap the connection pipe heat insulation and
the indoor unit pipe heat insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Indoor 
unit piping
Pipe
Vinyl tape
(wide)
Wrap with vinyl tape
Indoor unit tubing
Flare nut
Pipings
Torque wrench
Indoor unit tubing
Spanner (fixed)
Connection pipe
Flare nut
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
When extending the drain hose at the indoor
unit, install the drain pipe.
Wrap the area which accommodates the rear piping housing
section with vinyl tape.
12k
9k
9K, 12K
1/2"[5.5kg.m]
1/4"[1.8kg.m]
Pipe Size[Torque]
Capacity
(Btu/h)
GAS
LIQUID
-29-
3) Connection of the pipes-Outdoor
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrow on the wrench.
Outdoor unit 
Liquid side piping
(Smaller diameter)
Gas side
piping
(Bigger
diameter)
Torque wrench
8. Reroute the pipings and the drain hose across the
back of the chassis.
9. Set the pipings and the drain hose to the back of
the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.
10. Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Drain hose
Connecting
cable
Piping for
passage through
piping hole
Tubing
holder
Hook
1
Push
2
12k
9k
Wrap with 
vinyl tape(wide)
Drain hose
Vinyl tape(narrow)
Pipe
Bundle the piping and drain hose together by
wrapping them with cloth tape over the range
within which they fit into the rear piping housing
section.
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
9k, 12k
1/2"[5.5kg.m]
1/4"[1.8kg.m]
Pipe Size[Torque]
Capacity
(Btu/h)
GAS
LIQUID
-30-
3. Connecting the Cable Between Indoor Unit and Outdoor Unit
1) Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by
connecting the wires to the terminals on the
control board individually according to the
outdoor unit connection.
(Ensure that the color of the wires of the outdoor
unit and the terminal No. are the same as those
of the indoor unit.)
CAUTION
The power cord connected to the indoor unit
should be complied with the following
specifications
(Type H05VV-F approved by HAR or SAA).
RED
RED
BLUE
BLUE
1(L)
Terminals on the indoor unit
2(N)
3
1(L)
Terminals on the outdoor unit
2(N)
3
BROWN
GREEN/YELLOW
BROWN
GREEN/YELLOW
NORMAL
CROSS-SECTIONAL
AREA  9K:1.0mm
2
 
12K:1.5mm
2
 
NORMAL
CROSS-SECTIONAL
AREA  9K:1.0mm
2
 
12K:1.5mm
2
 
The connecting cable connected to the indoor
and outdoor unit should be complied with the
following specifications
(Type H07RN-F approved by HAR or SAA).
• Inverter model
Color of Wires
Color of Wires
The length of the power supply cord should be over 1.8m
measured from the power supply cord entry of the cabinet
to the middle of the live pin of the plug.
Air 
Conditioner
Main power source
If a power plug is not to be used, provide a circuit breaker between power source and
the unit as shown below.
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
CAUTION
Page of 75