Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: over the reated
current
Temp. difference
: over 8°C
Operating Current
• All amount of refrigerant leaked
out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
• Excessive amount of refrigerant
• Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice :
1. The suction pressure is usually 4.0~6.0 kg/cm
2
G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
Defective compressor
Current is low.
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of
operation.
Insufficient amount of
Current is low.
Lower
Higher
refrigerant (Leakage)
Clogging
Current is low.
High
Higher
-47-
-56-
Does the LED01M of outdoor PCB Ass'y
blink 6 times?
Check the state of connecting cable (3 line)
between indoor and outdoor uint.
When compressor does not operate normally.
DC Peak Error(Error Code
)
Trouble 7-1
NO
YES
Is the connecting state of connectors in
outdoor Sub. PCB Ass'y right?
(CN-UNW, CN-IPM)
• Electrical wiring diagram (Colors)
• Check the connecting state of connectors
in PCB Ass'y(Main/Sub)
• If CN-UWV is connected, the comprressor
can be operated a opposite direction.
NO
YES
Is the power module in Sub PCB Ass'y
right?
• Check the short P-N of IPM, P-U, V, W,
and N-U, V, W and then collector, emiter
of IGBT
• Replace the Sub PCB Ass'y.
NO
YES
Is the voltage of CN-AC over than
AC170V?
Check the supplied voltage.
NO
YES
Is the voltage of CN-DC over than about
DC380V?
• Check CN-IPM connector(Pin No. 12)
• Replace the Sub PCB Ass'y.
NO
YES
Is the refrigerant pressure right?
Replace the PCB Ass'y.
• Main PCB Ass'y
• Sub PCB Ass'y
• Control Box Ass'y
Supply the refrigerant.
NO
NO
-57-
When compressor does not oprate normally.
Communication error between Indoor and Outdoor (Error Code
)
Trouble 7-2
Does the operating LED in display PCB
Ass'y blink 5 times?
• Check the state of connecting cable
(3 line) bewteen indoor and outdoor unit .
• Check Fuse, Noise Filter, PTC, etc.
NO
YES
Is the voltage of CN-POWER Pin No. 1,2
AC220/240V in Main PCB Ass'y.
• Electrical wiring diagram(Colors)
• Check the connecting state
of connectors in PCB Ass'y (Main/Sub)
• Check the Fuse of outdoor Control Box.
NO
YES
Is the voltage of CN-AC AC220/240V in
SUB PCB Ass'y?
• Check the connecting state of connectors
in PCB Ass'y(Main/Sub).
NO
YES
Is the voltage of CN-DC over than
DC380V?
Replace the Sub PCB Ass'y.
NO
YES
Is the connection of CN-DATA between
indoor and outdoor unit right?
Replace the PCB Ass'y.
• Main PCB Ass'y (Indoor/Outdoor)
• Control Box Ass'y.
• Reconnect the cable to terminal block.
• Check the PCB pattern(Resoldering).
NO
YES
-58-
When compressor does not oprate normally.
CT Error (Error Code
)
Trouble 7-3
Does the operating LED in Display PCB
Ass'y blink 7 times?
• Check the state of connecting cable
(3 line) bewteen Indoor and Outdoor Unit .
• Check fuse, Noise Filter, PTC, etc.
NO
YES
Is the courrent transformer(CT) in Main
PCB Ass'y right?
Check the PCB pattern(resoldering)
NO
YES
Is the indoor/outdoor fan locked?
Check the motor.
NO
YES
Is the discharge temperature of Indoor unit
right(11°C~17°C)?
Check the compressor.
NO
YES
Is the refrigerant pressure right?
Supply the refrigerant
NO
YES
Replace the PCB Ass'y.
• Main PCB Ass'y(Outdoor)
• Control Box Ass'y(Outdoor)
Page of 75