-33-
2) Connect the cable to the outdoor unit
1. Remove the control cover from the unit by loosen-
ing the screw.
Connect the wires to the terminals on the control
board individually.
2. Secure the cable onto the control board with the
cord clamp.
3. Refix the control cover to the original position with
the screw.
4. Use a recognized circuit breaker "A" 
between the power source and the unit. 
A disconnecting device to adequately disconnect
all supply lines must be fitted.
Over 5mm
Terminal block
(Pillar terminal)
Holder for
connecting 
cable
Control cover 
Connecting cable
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibra-
tions to which the unit is subjected during the course of transportation. Check them and make sure that
they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 32))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an
air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
7K, 12K
16
Circuit
Breaker
(A)
Grade
CAUTION
-38-
Operation 
Name and Function-Remote Control 
START/STOP BUTTON
Operation starts when this button is pressed and stops
when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps
low, medium, high and CHAOS.
JET COOL
Used to start or stop the speed 
cooling. (Speed cooling operates 
super high fan speed in cooling mode.)
CHAOS SWING BUTTON
Used to stop or start louver movement and set the
desired up/down airflow direction.
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained
and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
POWER SAVE COOLING BUTTON
Used to set Preheat mode.
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
PLASMA(OPTION)
Used to start or stop the plasma-purification function. 
RESET BUTTON
Used prior to resetting time or after replacing batteries.
HORIZONTAL AIRFLOW DIRECTION CONTROL
BUTTON (NOT ON ALL MODELS)
Used to set the desired horizontal airflow direction. 
The remote control transmits the signals to the system.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
OFF
PLASMA
SET
CANCEL
6
1
3
5
4
Cooling Operation
Auto Operation
Healthy Dehumidification Operation
Flip-up door
(opened)
Heating Operation
Signal transmitter
10
11
12
13
14
15
7
8
9
2
• Cooling Model(
), Heat Pump Model(
)
Remote Control
Operation Mode
Disassembly of the parts (Indoor unit)
-39-
Warning :
Disconnect the unit from power supply before making
any checks.
Be sure the power switch is set to “OFF”. 
To remove the Grille from the Chassis. 
• Set the up-and-down air discharge louver to open
position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Display 
P.C.B
Conductor
Step Motor
Conductor
Earth
Conductor
Motor
Conductor
Sensor
Conductor
-40-
2. To remove the Control Box.
• Remove securing screws. 
• Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
• Unhook the discharge gr ille and pull the
discharge grille out from the chassis carefully.
4. To remove the Evaporator. 
• Remove 3 screws securing the evaporator(at the
left 2EA in the Eva Holder, at the right 1EA).
Page of 101