DOWNLOAD LG LS-J0762Y / S07LHN Service Manual ↓ Size: 6.28 MB | Pages: 101 in PDF or view online for FREE

Model
LS-J0762Y S07LHN
Pages
101
Size
6.28 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-j0762y-s07lhn.zip
Date

LG LS-J0762Y / S07LHN Service Manual ▷ View online

-37-
6. Test Running
1. Check that all tubing and wiring have been properly
connected.
2. Check that the gas and liquid side service valves are
fully open.
1. Prepare remote control
Remove the battery cover 
by pulling it according to the
arrow direction.
Insert new batteries making 
sure that the (+) and (–) of 
battery are installed correctly.
Reattach the cover by
pushing it back into position.
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use recharge-
able batteries.
• Remove the batteries from the remote control if the
system is not going to be used for a long time.
2. Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
In the case when the vibration of the unit is con-
veyed to the hose, secure the unit with an anti-
vibration rubber.
3. Evaluation of the performance
Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and dis-
charge of air.
NOTE: If the actual pressure are higher than shown, the
system is most likely over-charged, and charge
should be removed. If the actual pressure are low-
er than shown, the system is most likely under-
charged, and charge should be added. 
The air conditioner is now ready for use.
Bolt
Tubing connection
This is performed when the unit is to be relocated
or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the out-
door unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the
unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the
charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the
air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cool-
ing operation.
5. When the low-pressure gauge reading becomes 1 to
0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas
side valve stem and then quickly turn off the unit. At
that time, Pump Down has been completed and all
refrigerant gas will have been collected in the outdoor
unit.
PUMP DOWN
3. Ensure the difference between the intake tempera-
ture and the discharge is more than 8°C (Cooling) or
reversely (Heating).
4. For reference; the gas side pressure of optimum
condition is as below.(Cooling)
Discharge 
temperature
Discharge air
Intake temperature
R-22
35°C (95°F)
4.5~5.5kg/cm
2
G(63.9~78.1 P.S.I.G.)
R-410A
35°C (95°F)
8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side 
service valve.
-26-
3) How to fix installation plate
The wall you select should be strong and solid enough to
prevent vibration
1. Mount the installation plate on the wall with 
6 type "A" screws. If mounting the unit on a con-
crete wall, use anchor bolts.
Mount the installation plate horizontally by aligning
the centerline using a level.
2. Measure the wall and mark the centerline. It is also
important to use caution concerning the location
of the installation plate-routing of the wiring to
power outlets is through the walls typically. Drilling
the hole through the wall for piping connections
must be done safely.
Installation Plate
Type "A" screw
Installation plate
Ø70mm
Left rear piping
Right rear piping
C
D
B
A
Ø70mm
A
B
C
D
7k, 9k
50
20
80
20
12k, 18k
45
40
80
20
CHASSIS
(Grade)
Distance (mm)
4) Drill a hole in the wall
Drill the piping hole with a ø70mm hole core drill.
Drill the piping hole at either the right or the left with
the hole slightly slanted to the outdoor side.
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
-27-
2. Flaring work and connection of piping
1) Flaring work
Main cause for gas leakage is due to defect in flaring
Main cause for refrigerant leakage is due to defect in the
flaring work. Carry out correct flaring work using the fol-
lowing procedure.
1. Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased
locally.
Measure the distance between the indoor and the
outdoor unit.
Cut the pipes a little longer than the measured dis-
tance.
Cut the cable 1.5m longer than the pipe length.
2. Burrs removal
Completely remove all burrs from the cut cross sec-
tion of pipe/tube.
Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid drop-
3. Putting nut on
Remove flare nuts attached to indoor and outdoor
unit, then put them on pipe/tube having completed
burr removal.
4. Flaring work
Firmly hold copper pipe in a die in the dimension
shown in the table above.
Carry out flaring work using flaring tool as shown
below.
Flare nut
Copper tube
Copper
pipe
90
°
Slanted   Uneven  Rough
Pipe
Reamer
Point down
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
mm
inch
mm
Ø6.35
1/4
0~0.5
Ø9.52
3/8
0~0.5
Ø12.7
1/2
0~0.5
Outside diameter
A
5. Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
-28-
2) Connection of piping --Indoor
Preparing the indoor unit's piping and drain hose for
installation through the wall.
Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
Replace the plastic tubing holder in the original posi-
tion.(Optional)
1. Route the indoor tubing and the drain hose in the
direction of rear right.
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connec-
tion later.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are proper-
ly seated on the installation plate by moving it left
and right.
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
5. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
Align the center of the pipes and sufficiently tighten
the flare nut by hand.
3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
NOTE: If the drain hose is routed inside the room, insu-
late the hose with an insulation material* so that
dripping from "sweating"(condensation) will not
damage furniture or floors.
*Foamed polyethylene or equivalent is recom-
mended.
Tubing holder
Drain hose
Connecting 
cable
Loop
Gas side
piping
Liquid side
piping
Drain hose
1
2
Drain hose
Connecting
cable
Indoor unit tubing
Flare nut
Pipes
For right rear piping
CAUTION
When install, make sure that the
remaining parts must be removed
clearly so as not to damage the
piping and drain hose, especially
power cord and connecting cable.
Page of 101
Display

Click on the first or last page to see other LS-J0762Y / S07LHN service manuals if exist.