2. Pumping down 
• Procedure 
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.  
–  Remove the valve stem caps and confirm that
the valve stems are in the raised position. 
– Be sure to use a hexagonal wrench to operate
the valve stems. 
(2) Operate the unit for 10 to 15 minutes. 
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of
the 3-way valve.
–  Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
–  Open the low-pressure valve on the charge set
slightly to air purge from the charge hose. 
(5) Set the 2-way valve to the closed position. 
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates
1kg/cm
2
g.
(7) Immediately set the 3-way valve to the closed
position.
–  Do this quickly so that the gauge ends up
indicating 3 to 5kg/cm
2
g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valve’s stem nuts and the
service port nut. 
–  Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m. 
–  Be sure to check for gas leakage. 
Lo
Open
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
(High handle)
Close
2-Way
valve
3-Way
valve
OPEN
(Low handle)
Manifold
Gauge
CLOSE
—33—
1) Re-air purging 
(Re-installation)
• Procedure 
(1) Confirm that both the 2-way valve and the 3-
way valve are set to the closed position. 
(2) Connect the charge set and a gas cylinder to
the service port of the 3-way valve. 
–  Leave the valve on the gas cylinder closed. 
(3) Air purging. 
–  Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare
nut on the 2-way valve approximately 45° for 3
seconds then closing it for 1 minute; repeat 3
times. 
– After purging the air, use a torque wrench to
tighten the flare nut on the 2-way valve.
(4) Check for gas leakage.
–  Check the flare connections for gas leakage.  
(5) Discharge the refrigerant. 
–  Close the valve on the gas cylinder and
discharge the refrigerant until the gauge
indicates 3 to 5 kg/cm
2
g. 
(6) Disconnect the charge set and the gas
cylinder, and set the 2-way and 3-way valves
to the open position.
–  Be sure to use a hexagonal wrench to operate
the valve stems. 
(7) Mount the valve stem nuts and the service
port nut.
–  Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.  
*  CAUTION: 
Do not leak the gas in the air during Air
Purging.
Lo
Open
OPEN
(Low handle)
Close
Gas cylinder
R22
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
(High handle)
2-Way
valve
3-Way
valve
Manifold
Gauge
—34—
2) Balance refrigerant of the 2-way, 3-way valves  
(Gas leakage)
• Procedure 
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat. 
(2) Connect the charge set to the 3-way valve’s
port.  
–  Leave the valve on the charge set closed. 
– Connect the charge hose with the push pin to
the service port.  
(3) Open the valve (Low handle) on the charge set
and discharge the refrigerant until the gauge
indicates 0 kg/cm
2
G.
–  If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not
running is higher than 1 kg/cm
2
G), discharge
the refrigerant until the gauge indicates 0.5 to 1
kg/cm
2
G. if this is the case, it will not be
necessary to apply a evacuatin. 
– Take care to discharge the refrigerant
gradually; if it is discharged too suddenly, the
refrigeration oil will also be discharged. 
Lo
Open
Open
3-Way
valve
2-Way
valve
Gas side
CLOSE
(High handle)
OPEN
(Low handle)
Outdoor unit
Liquid side
Indoor unit
Manifold
Gauge
—35—
3. Evacuation 
(All amount of refrigerant leaked)
• Procedure 
(1) Connect the vacuum pump to the charge set’s
center hose 
(2) Evacuation for approximately one hour.  
–  Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).  
(3) Close the valve (Low handle) on the charge
set, turn off the vacuum pump, and confirm
that the gauge needle does not move
(approxima-tely 5 minutes after turning off the
vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump. 
–  Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed. 
Lo
Open
Open
Vacuum pump
2-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
(High handle)
OPEN
(Low handle)
Manifold
Gauge