—32—
2. Pumping down
• Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of
the 3-way valve.
– Connect the charge hose with the push pin to
the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates
1kg/cm
1kg/cm
2
g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up
– Do this quickly so that the gauge ends up
indicating 3 to 5kg/cm
2
g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valve’s stem nuts and the
service port nut.
– Use torque wrench to tighten the service port
service port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Open
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
(High handle)
(High handle)
Close
2-Way
valve
valve
3-Way
valve
valve
OPEN
(Low handle)
(Low handle)
Manifold
Gauge
Gauge
CLOSE
—33—
1) Re-air purging
(Re-installation)
• Procedure
(1) Confirm that both the 2-way valve and the 3-
way valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the 3-way valve.
– Leave the valve on the gas cylinder closed.
– Leave the valve on the gas cylinder closed.
(3) Air purging.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare
nut on the 2-way valve approximately 45° for 3
seconds then closing it for 1 minute; repeat 3
times.
nut on the 2-way valve approximately 45° for 3
seconds then closing it for 1 minute; repeat 3
times.
– After purging the air, use a torque wrench to
tighten the flare nut on the 2-way valve.
(4) Check for gas leakage.
– Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and
discharge the refrigerant until the gauge
indicates 3 to 5 kg/cm
indicates 3 to 5 kg/cm
2
g.
(6) Disconnect the charge set and the gas
cylinder, and set the 2-way and 3-way valves
to the open position.
– Be sure to use a hexagonal wrench to operate
to the open position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
* CAUTION:
Do not leak the gas in the air during Air
Purging.
Purging.
Lo
Open
OPEN
(Low handle)
(Low handle)
Close
Gas cylinder
R22
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
(High handle)
(High handle)
2-Way
valve
valve
3-Way
valve
valve
Manifold
Gauge
Gauge
—34—
2) Balance refrigerant of the 2-way, 3-way valves
(Gas leakage)
• Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
– Leave the valve on the charge set closed.
– Connect the charge hose with the push pin to
– Leave the valve on the charge set closed.
– Connect the charge hose with the push pin to
the service port.
(3) Open the valve (Low handle) on the charge set
and discharge the refrigerant until the gauge
indicates 0 kg/cm
indicates 0 kg/cm
2
G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not
running is higher than 1 kg/cm
running is higher than 1 kg/cm
2
G), discharge
the refrigerant until the gauge indicates 0.5 to 1
kg/cm
kg/cm
2
G. if this is the case, it will not be
necessary to apply a evacuatin.
– Take care to discharge the refrigerant
gradually; if it is discharged too suddenly, the
refrigeration oil will also be discharged.
refrigeration oil will also be discharged.
Lo
Open
Open
3-Way
valve
valve
2-Way
valve
valve
Gas side
CLOSE
(High handle)
(High handle)
OPEN
(Low handle)
(Low handle)
Outdoor unit
Liquid side
Indoor unit
Manifold
Gauge
Gauge
—35—
3. Evacuation
(All amount of refrigerant leaked)
• Procedure
(1) Connect the vacuum pump to the charge set’s
center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Low handle) on the charge
set, turn off the vacuum pump, and confirm
that the gauge needle does not move
(approxima-tely 5 minutes after turning off the
vacuum pump).
that the gauge needle does not move
(approxima-tely 5 minutes after turning off the
vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
2-Way
valve
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
valve
CLOSE
(High handle)
(High handle)
OPEN
(Low handle)
(Low handle)
Manifold
Gauge
Gauge