JBL ON BEAT RUMBLE EMC - CB Certificate ▷ View online
Issue Date:
2013-01-09
Page 31 of 41
Report Reference #
E204594-A39-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
3.1.1
Permissible combinations of internal
wiring/external cable sizes for overcurrent and
short circuit protection.
N/A
3.1.1
All interconnecting cables protected against
overcurrent and short circuit.
N/A
3.2
Wiring methods permit connection of
equipment to primary power supply in accordance
with the NEC and CEC, Part 1.
Class III unit. No direct
connection to mains supply.
N/A
3.2.1
Permitted use for flexible cords and plugs.
N/A
3.2.1
Flexible cords provided with attachment
plug rated 125% of equipment current rating.
N/A
3.2.1
Any Class II equipment provided with 15 or
20 A standard supply outlets, Edison-base
lampholders or single pole disconnect device
provided with a polarized type attachment plug.
N/A
3.2.1.2
Equipment intended for connection to DC
mains supply power systems complies with special
wiring requirements (e.g., no permanent
connection to supply by flexible cord).
N/A
3.2.1.2
Equipment with one pole of the DC mains
supply connected to both the equipment mains
input terminal and the main protective earthing
terminal provided with special instructions and
construction provisions for earthing.
N/A
3.2.1.2
Equipment with means for connecting
supply to earthing electrode conductor has no
switches or protective devices between supply
N/A
Issue Date:
2013-01-09
Page 32 of 41
Report Reference #
E204594-A39-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
connection and earthing electrode connection.
3.2.1.2
Special markings and instructions for
equipment with provisions to connect earthed
conductor of a DC supply circuit to earthing
conductor at the equipment.
N/A
3.2.1.2
Special markings and instructions for
equipment with earthed conductor of a DC supply
circuit connected to the earthing conductor at the
equipment.
N/A
3.2.1.2
Terminals and leads provided for
permanent connection of DC powered equipment
to supply marked to indicate polarity if reverse
polarity may result in a hazard.
N/A
3.2.3
Permanently connected equipment has
provision for connecting and securing a field wiring
system (i.e. conduit, or leads etc.) per the NEC and
CEC, Part 1.
N/A
3.2.3
Permanently connected equipment may
have terminals or leads not smaller than No. 18
AWG (0.82 mm²) and not less than 150 mm in
length for connection of field installed wiring.
N/A
3.2.3
If supply wires exceed 60 °C, marking
indicates use of 75 °C or 90 °C wiring for supply
connection as appropriate.
N/A
3.2.3
Equipment compatible with suitable trade
sizes of conduits and cables.
N/A
3.2.5
Power supply cords are required to be no
longer than 4.5 m in length.
N/A
Issue Date:
2013-01-09
Page 33 of 41
Report Reference #
E204594-A39-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
Minimum cord length is required to be 1.5 m, with
certain constructions such as external power
supplies allowed to consider both input and output
cord lengths into the requirement.
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and Tables
11 and 12 of the CEC.
3.2.5
Conductors in power supply cords sized
according to NEC and CEC, Part I.
N/A
3.2.5
Power supply cords and cord sets
incorporate flexible cords suitable for the particular
application.
N/A
3.2.6
Strain relief provided for non-detachable
interconnecting cables not supplied by a limited
power source.
N/A
3.2.9
Adequate wire bending space and volume
of field wiring compartment required to properly
make the field connections.
N/A
3.2.9
Equipment intended solely for installation in
Restricted Access Locations using low voltage d.c.
systems may not need provision for connecting and
securing a field wiring system. A method of
securing wiring or instructions provided to ensure
the wiring is protected from abuse.
N/A
3.3
Field wiring terminals provided for
interconnection of units for other than LPS or Class
2 circuits also comply with 3.3.
Class III equipment, no
wiring terminal provided.
N/A
3.3
Interconnection of units by LPS or Class 2
conductors may have field wiring connectors other
N/A
Issue Date:
2013-01-09
Page 34 of 41
Report Reference #
E204594-A39-CB-1
IEC 60950-1:2005
SubClause Difference + Test
Result - Remark
Verdict
This report issued under the responsibility of UL
than those specified in 3.3 if wiring is reliably
separated.
separated.
3.3.1
Terminals for the connection of neutral
conductor identified by a distinctive white marking
or other equally effective means.
N/A
3.3.3
Wire binding screw terminal permitted for
connection of No. 10 AWG (5.3 mm²) or smaller
conductor if provided with upturned lugs, cupped
washer or equivalent retention.
N/A
3.3.4
Terminals accept wire sizes (gauge) used
in the U.S. and Canada.
N/A
3.3.4
Terminals accept current-carrying
conductors rated 125% of the equipment current
rating.
N/A
3.3.5
First column of Table 3E requirement:
“Smaller of the RATED CURRENT of the
equipment or the PROTECTIVE CURRENT
RATING of the circuit under consideration.”
N/A
3.3.6
Field wiring terminals marked to indicate
the material(s) of the conductor appropriate for the
terminals used.
N/A
3.3.6
Connection of an aluminum conductor not
permitted to terminal for equipment earthing
conductor.
N/A
3.3.6
Field wiring connections made through the
use of suitable pressure connectors (including set
screw type), solder lugs or splices to flexible leads.
N/A
Click on the first or last page to see other ON BEAT RUMBLE service manuals if exist.