Sharp AE-A18 (serv.man12) Service Manual ▷ View online
29
AH/AY-AP18DR
AH/AY-AP24DR
AH/AY-AP24DR
For AY-AP18DR/AE-A18DR, AH-AP18DR/AU-A18DR
The room is not cooled at all
or not cooled.
The compressor does not operate.
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may be leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may be leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
Push the button "AUX." on
the indoor unit, for more than 5 sec.
the indoor unit, for more than 5 sec.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
Fig. 1
Using a tester, measure voltage at
the terminals on the terminal board.
the terminals on the terminal board.
100
80
60
40
20
0
-10
0
10
20
30
40
Resistance
Thermistor
Room temperature
Heat exchange
Color
Yellow
Orange
To measure the resistance, first remove
the connector as shown at right.
the connector as shown at right.
Room temperature
thermistor TH1
Tester
Connector
No. 3 to 4
No. 1 to 2
Fig. 1 Temperature properties of indoor thermistors
K
Heat exchange thermistor
TH2 (orange)
25
TH2 (orange)
25
°C resistance 15 K
Room temperature
thermistor TH1 (yellow)
25
thermistor TH1 (yellow)
25
°C resistance 10 K
Heat exchange
thermistor TH2
Tester
4
1 CN4
AH/AY-AP18DR
AH/AY-AP24DR
AH/AY-AP24DR
30
For AY-AP24DR/AE-A24DR, AH-AP24DR/AU-A24DR
The room is not cooled at all
or not cooled.
The compressor does not operate.
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may be leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may be leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
Push the button "AUX." on
the indoor unit, for more than 5 sec.
the indoor unit, for more than 5 sec.
Is the
voltage between
terminal of black lead
wire on the relay in the out door
unit and terminal "N"on the
terminal board the power
supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
YES
NO
NO
Replace the PWB ass'y with a new one.
Replace the relay in the outdoor unit
with a new one.
with a new one.
Using a tester, measure voltage at
the terminals on the terminal board.
the terminals on the terminal board.
Is the voltage
between terminal "N" and
"4"("2" ..... AU-A24DR) in the outdoor
unit the power
supply voltage ?
31
AH/AY-AP18DR
AH/AY-AP24DR
AH/AY-AP24DR
For AY-AP24DR/AE-A24DR, AY-AP18DR/AE-A18DR
The room is not heated at all or not heated.
The compressor does not operate.
The compressor does not operate.
The control circuit board is normal.
Refrigerant may be leaked.
The running capacitor may be defective.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The thermistor may be defective.
Refrigerant may be leaked.
The running capacitor may be defective.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The thermistor may be defective.
Is the voltage
between terminal "N" and
"4"("1" ..... AY-AP18DR) of the
terminal board the power
supply voltage ?
NO
Replace the PWB ass'y with a new one.
Push the button of "AUX" on the indoor
unit, for more than 5 sec.
unit, for more than 5 sec.
Using a tester, measure voltages at the
terminals on the terminal board.
terminals on the terminal board.
Select HEAT MODE with remote controller.
And then start operation.
And then start operation.
Is the voltage
between terminal "N" and
"2" of the terminal board the
power supply voltage ?
Is the voltage
between terminal "N" and
"3" of the terminal board the
power supply voltage ?
YES
YES
YES
NO
NO
AH/AY-AP18DR
AH/AY-AP24DR
AH/AY-AP24DR
32
REFRIGERATION CYCLE
Figure R-1. Refrigeration Cycle for AH-AP18CE/AH-AP24CE
Figure R-2. Flow of Refrigerant for AY-AP18DR AND AY-AP24DR
1
2
Capillary tube
3
Outdoor unit
Condenser
Evaporator
Indoor unit
Compressor
Flare coupling
Flare coupling
4
3-way
valve
valve
2-way
valve
Accumulator
s
1
4
C
2
Capillary
tube A
tube A
Capillary
tube B
tube B
Capillary
tube D
(Lower row)
tube D
(Lower row)
Capillary
tube C
(Upper row)
tube C
(Upper row)
Accumulator
3
Strainer
Heating
Cooling
Outdoor unit
Condenser
Evaporator
Indoor unit
Reverse valve
Comp-
ressor
Flare coupling
Flare coupling
3-way
valve
2-way
valve
Silencer
Coil
Click on the first or last page to see other AE-A18 (serv.man12) service manuals if exist.