81 
 
Deice operation time diagram 
 
a.  Deice mode 1 control: 
 
OD fan
ID pump
Expansion valve
Four way valve
Compressor
Free
Free
ON
OFF
OFF
ON
ON
Free
5
7
6
4
9
8
3
2
1
ON
ON
Free
Free
max 9 minutes 30 seconds
deice 1
 
 
b.  Deice mode 2 control: 
 
OD fan
OD fan
Main
Expansion valve
Bypass
Expansion valve
Four way valve
Sequence
Pump
Gas Bypass SV
Compressor
Deice mode 2
max 30 minutes
Normal
Deice
4~6
OFF
ON
ON
OFF
OFF
0
ON
ON
OFF
Free
Free
Free
Free
ON
OFF
OFF
1
2
3
4
5
6
7
8
Heating
operation
 
 
82 
13.4  Protection Control for Cooling Operation 
13.4.1  Outdoor Air Temperature Control 
  The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
  This control will begin 1 minute after the compressor starts. 
  Compressor frequency will adjust base on outdoor air temperature. 
 
 
 
13.4.2  Freeze Prevention Control 1 
1  When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will 
stop operating. 
2  Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C. 
3  Indoor heat exchanger freeze prevention (H99) will memory in error history. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
83 
14.  Servicing Mode 
14.1  Remove The Cabinet Front Plate 
1.  Remove the 5 mounting screws as shown in the illustration. 
2.  Slide the cabinet front plate downward to release the pawls. 
Then, pull it toward front to remove it. 
 
Cabinet Front Plate
Mounting screws
Mounting
screws
 
14.2  Remove The Cabinet Top Plate 
1.  Remove the 11 mounting screws as shown in the illustration. 
2.  Lift the cabinet top plate upward to remove it. 
 
Cabinet Top Plate
Mounting
screws
 
14.3 Test Run 
1.  Fill up the Tank Unit with water. For details refer to Tank Unit installation instruction and operation instruction. 
2.  Antifreeze agent must be added into water circuit to prevent freezing of water when outdoor ambient 
temperatures is low. Recommended antifreeze: Propylene glycol: 40% (equivalent to -20°C) 
3.  Set ON to the Mono bloc unit and RCCB. Then, for remote control operation please refers to (Mono bloc) Air-
to-Water Heatpump’s operation instruction. 
4.  For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.3 MPa. If necessary, 
adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water 
pump speed cannot solve the problem, contact your local authorized dealer. 
5.  After test run, please clean the external filter. Reinstall it after finish cleaning. 
 
 
 
 
 
84 
14.4  Proper Pump Down Procedure 
  Strictly follow the steps below for proper pump down procedure. Explosion may occur if the steps are not 
followed as per sequence. 
1.  Press the “SERVICE” switch on remote control to enter SERVICE mode. Operate the system in Sr : 01 mode 
for pump down operation. 
2.  After 10~15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10°C)), fully close 2 way 
valve. 
3.  After 3 minutes, fully close 3 way valve. 
4.  Press the “OFF/ON” switch on remote control to stop pump down operation. 
5.  Remove the refrigerant piping. 
 
14.5  How To Adjust Water Flow Rate
 
Before adjust the water flow rate, make sure that the total water volume in the installation is 50 litres minimum for 
heating side. The default setting is SPEED 6 for WH-MXC16G9E8. Please ensure the minimum flow rate is not less 
than 13 l/min and not more than 50 l/min. 
The available external static pressure (kPa) in function of the water flow rate (l/min) is shown in the P-Q graph. 
Depend on the hydraulic system pressure loss and type, the water flow rate can be adjusted by remote control. 
1  When the Air-to-Water Heatpump is in stop operation, press SERVICE button for 5 seconds. 
2  Press  /  button to select menu S02 (PUMP SPEED ADJUST MODE) and press SET button to confirm the 
menu. 
3  Press SELECT button then press  /  button to change pump speed and press SET button to confirm the 
pump speed. 
4  Press OFF/ON button to exit PUMP SPEED ADJUST MODE. 
During PUMP SPEED ADJUST MODE, we can select AIR PURGE function by pressing FORCE button. 
In AIR PURGE function, the pump will operate ON and OFF for 10 minutes to purge the air in the hydraulic system. 
Press again the FORCE button to exit AIR PURGE function. PUMP SPEED ADJUST 
MODE will stop operation. 
 
0
10 13 20
30
40
50
60
70
1
2
3
4
5
6
7
110
120
130
100
90
80
70
60
50
40
30
20
10
0
WATER FLOW RATE (L/min)
EXTERNAL STAT
IC PRESSURE 
(kPa)
N
O
AP
PL
IC
AB
LE
 R
AN
GE
N
O
AP
PL
IC
AB
LE
 R
AN
GE
 
 
14.6  Expansion Vessel Pre Pressure Checking 
  Expansion Vessel with 10 L air capacity and initial pressure of 1 bar is installed in this Mono bloc unit. 
  Total amount of water in system should be below 200 L. 
(Note: This amount of water is not include the tank unit volume) 
  If total amount of water is more than 200L, please install additional expansion vessel (field supply). 
  Please keep the installation height difference of system water circuit within 10 m. 
(Inner volume of same Mono bloc unit is about 5 L) 
 
 
 
 
 
 
 
Page of 127