DOWNLOAD Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 (serv.man2) Service Manual ↓ Size: 12.65 MB | Pages: 127 in PDF or view online for FREE

Model
U-4LE1E5 U-4LE1E8 U-5LE1E5 U-5LE1E8 U-6LE1E5 U-6LE1E8 (serv.man2)
Pages
127
Size
12.65 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / MINI VRF SYSTEM
File
u-4le1e5-u-4le1e8-u-5le1e5-u-5le1e8-u-6le1e5-u-6le.pdf
Date

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 (serv.man2) Service Manual ▷ View online

2 - 7
1
2
3
4
5
6
7
8
9
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
Minimum indoor volume & floor area as against 
the amount of refrigerant is roughly as given in the 
following table.
CAUTION 
Pay special attention to any location, such as a basement, etc., where 
leaking refrigerant can accumulate, since refrigerant gas is heavier than air.
Table 1-10 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
L = Length, H = Height
Always check the gas density limit for the room in which the 
unit is installed.
WARNING 
1-12.  Check of Limit Density
When installing an air conditioner in a room, it is 
necessary to ensure that even if the refrigerant gas 
accidentally leaks out, its density does not exceed the 
limit level for that room.
If the density could exceed the limit level, it is 
necessary to provide an opening between the unit 
and the adjacent room, or to install mechanical 
ventilation which is interlocked with the leak detector.
(Total refrigerant charged amount: k
g)
(Min. indoor volume where the indoor unit is installed: m
3
)
< Limit density 0.3 (k
g/m
3
)
The limit density of refrigerant which is used in this 
unit is 0.3 k
g/m
3
 (ISO 5149).
The shipped outdoor unit comes charged with the 
amount of refrigerant fixed for each type, so add it 
to the amount that is charged in the field. (For the 
refrigerant charge amount at shipment, refer to the 
unit’s nameplate.)
40.5
54.0
27.0
13.5
0.0
20
10
0
30
40
60
70
80
90 100
50
67.5
81.0
94.5
108.0
121.5
135.0
148.5
162.0
175.5
189.0
202.5
216.0
229.5
243.0
256.0
270.0
m
2
m
3
15
10
5
0
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
283.5
297.0
310.5
324.0
337.5
k
g
Range below the 
density limit of 
0.3 k
g/m³
(Countermeasures 
not needed)
Range above the 
density limit of 0.3 
k
g/m³
(Countermeasures 
needed)
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceiling is 2.7 m high)
Items
Marks
Contents
Length (m)
Allowable tubing 
length
L1
Max. tubing 
length
Actual length
≤ 120
Equivalent length
≤ 140
ΔL (L2 – L3)
Difference between max. length and min. 
length from the No.1 distribution joint
≤ 40
1
,
2
...
n
Max. length of each distribution tube
≤ 30
1
,
2
...
n-1
+L1
Total max. tubing length including length of each 
distribution tube (only narrow tubing)
≤ 150
Allowable elevation 
difference
H1
When outdoor unit is installed higher than indoor unit
≤ 50
When outdoor unit is installed lower than indoor unit
≤ 40
H2
Max. difference between indoor units
≤ 15
TD831155-04_MINI VRF.indb   7
TD831155-04_MINI VRF.indb   7
2014/05/09   15:29:02
2014/05/09   15:29:02
2 - 8
1
2
3
4
5
6
7
8
9
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-13. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, 
elevation difference and other factors, select the correct model after taking into account the various correction values. 
When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit. 
Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final 
capacity of each indoor unit.
(A) Capacity correction for the outdoor unit temperature conditions (%)
Read the capacity correction for outdoor unit temperature, indoor unit temperature and indoor/ outdoor ratio as shown 
in the section “9. CAPACITY TABLE”.
(B) Capacity correction coefficient for outdoor unit tubing length (%)
From the graph of capacity change characteristics resulting from tubing length and elevation difference on page “ 2-11 ”, 
read the capacity correction coefficient.
* Indoor unit temperature is indoor unit rated capacity - weighted average temperature.
Rated capacity-weighted average temperature =
((a)×(b))
(a)
= 17.1WB
* The indoor/ outdoor ratio should be selected according to the real rated capacity.
* Use the lowest capacity changing ratio. Usually, the furthest and highest or the lowest indoor unit is used.
(C) Surplus capacity correction coefficient for outdoor unit temperature conditions (%)
From the graph of surplus capacity characteristics resulting from outdoor temperature on page “ 2-10 ”, read the capacity 
correction coefficient.
(D) Capacity correction coefficient for outdoor unit frosting and defrosting during heating operation (%)
From the outdoor unit heating capacity correction coefficient during frosting / defrosting on page “ 2-10 ”, read the capacity 
correction coefficient.
Example
Cooling operation
Example
There are 4 indoor units for class 22, 28, 45, 56 and the outdoor unit HP is 6 (15.5kW in the cooling-mode, 18.0kW in the 
heating-mode).
(a) Rated capacity
(b) Intake temperature
(a) × (b)
2.2 kW
19 WB
41.8
2.8 kW
50.4
18 WB
4.5 kW
17 WB
76.5
5.6 kW
16 WB
89.6
1. Outdoor unit capacity correction
Outdoor unit capacity correction (kW) = Rated capacity × (A) × (B) × (C) × (D)
Rated cooling capacity
Rated heating capacity
2.2 kW
2.5 kW
2.8 kW
3.2 kW
4.5 kW
5.0 kW
5.6 kW
6.3 kW
No.
1
2
3
4
No.
1
2
3
4
15.1 kW
17.0 kW
97.4%
94.4 %
Total
I/O ratio
TD831155-04_MINI VRF.indb   8
TD831155-04_MINI VRF.indb   8
2014/05/09   15:29:02
2014/05/09   15:29:02
2 - 9
1
2
3
4
5
6
7
8
9
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
(E) Capacity correction for the indoor unit temperature conditions (kW)
From the graph of indoor capacity characteristics on page “ 2-11 ”, read the capacity correction coefficient for indoor unit 
temperature conditions.
(H) Capacity correction coefficient for tubing length and elevation difference (%)    
From the graph of capacity change characteristics resulting from tubing length and elevation difference on page “ 2-11 ”, 
read the capacity correction coefficient.
(E) = Capacity correction coefficient for indoor unit temperature conditions × Rated capacity  
(F) Calculate the Capacity distribution ratio (%)
(F) =
(E)
(E)
(G) Distribute the outdoor unit capacity among each indoor unit (kW)
(G) = (A) × (F) × rated capacity of outdoor unit (kW)
2. Indoor unit capacity correction coefficient
Indoor unit capacity correction (kW) = (G) × (H) × (C) ×  (D)
*
Indoor unit capacity correction 
 (G)
TD831155-04_MINI VRF.indb   9
TD831155-04_MINI VRF.indb   9
2014/05/09   15:29:02
2014/05/09   15:29:02
2 - 10
1
2
3
4
5
6
7
8
9
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
Surplus capacity correction coefficient (%)
Note : 
This capacity graph is used for the calculation of the tubing length correction.
Therefore, this is different from the outdoor unit’s capacity graph.
Outdoor air intake temp.( °C WB)
 
Outdoor air intake temp.( °C DB)
Surplus capacity correction coefficient (%)
Surplus capacity correction coefficient (%)
5. Graph of capacity correction coefficients
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (4))
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity 
found from the capacity graph by the correction coefficient from the table above.
*
Outdoor intake 
air temp.
Correction 
coefficient
–1
0
1
2
3
4
5
6
0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95
1.0
0.91
0.94
0.96
0.97 0.97 0.97
(°CWB, RH85%)
–20
–15
–10
–8
–6
–2
–4
–5
-20 -15 -10
-5
0
5
10
15
90
95
100
110
105
120
115
125
90
95
100
105
110
115
120
125
g
n
i
t
a
e
h
g
n
il
o
o
c
-5
0
5
10
15
20
25
30
35
40
45
46
18
TD831155-04_MINI VRF.indb   10
TD831155-04_MINI VRF.indb   10
2014/05/09   15:29:02
2014/05/09   15:29:02
Page of 127
Display

Click on the first or last page to see other U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 (serv.man2) service manuals if exist.