1. Outdoor Unit Control PCB
PCB and Functions
7 - 11
• The outdoor unit maintenance remote controller can be used to check the alarm display.
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm display.
(Refer to "Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.")
Alarm 
Code
Alarm Meaning
E01
E02
E03
E04
E05
E06
Error in the Outdoor Unit Receiving Signal from the Indoor Unit
Error in Indoor Unit Transmitting Signal to the Outdoor Unit
Error in Indoor Unit Receiving Signal from the Outdoor unit
Error in Indoor Unit Receiving Signal from Remote Controller (central)
Remote Controller Transmission Error
Remote Controller Reception Error
E07
E08
E09
E12
E13
E15
Auto-Address Alarm (not enough units)
Error in Indoor Unit Transmitting Signal to Remote Controller
Start of Auto Address Setting Prohibited Due to Auto Address Setting Being in Progress
More Than One Remote Controller Set to Main Error
E16
E18
E20
E30
Outdoor Unit Serial Transmission Error
No Indoor Units Error
Faulty Communication in Group Control Wiring
Auto-Address Alarm (too many units)
F04
F06
F07
Heat Exchanger Inlet Temperature Sensor (C1) Error
Outdoor Air Intake Temperature Sensor Error
Compressor Discharge Temperature Sensor Error
F08
F12
F16
F31
Outdoor Unit Nonvolatile Memory (EEPROM) Error
High Pressure Sensor Error
Compressor Intake Temperature Sensor (TS) Error
Outdoor Air Temperature Sensor (TO) Error
H01
H02
H03
H31
HIC Error
Compressor CT Sensor (Current Sensor) Unplugged
L04
L10
Outdoor Unit Capacity Not Yet Setup Error
L18
4-way valve operation failure
Duplicated Setting of Outdoor System Address Error
PAM Error
Primary Current (Input) Detect of Overcurrent
Duplicate Indoor Unit Address Settings Error
Error in Outdoor Unit Transmitting Signal to the Indoor Unit
P03
P04
P05
P13
P14
P16
Overcurrent of Inverter Compressor
O
2
 Sensor
Forgot-to-open Valve Alarm
Power Supply Error
Actuation of High Pressure Switch
Compressor Discharge Temperature Error
P22
P29
INV Compressor Start-up Failed (including lock) Due to INV Compressor Wiring Open Phase, Faulty DCCT, etc.
Outdoor Fan Motor Error
TD831155-04_MINI VRF.indb   11
TD831155-04_MINI VRF.indb   11
2014/01/07   11:47:24
2014/01/07   11:47:24
7 - 12
– MEMO –
TD831155-04_MINI VRF.indb   12
TD831155-04_MINI VRF.indb   12
2014/01/07   11:47:24
2014/01/07   11:47:24
1
2
3
4
5
6
7
8
9
8 - 1
Contents
1. Precautions on Renewal Design & Installation ................................................................. 8-2
1. General .............................................................................................................................. 8-2
2. Basic Points for Using Existing Tubing ............................................................................... 8-2
3. VRF Renewal Kit with High-pressure SW Kit and Sight Glass  ......................................... 8-3
4. Procedure for Renewal ...................................................................................................... 8-4
5. Judging Whether Possible to Reuse Existing Tubing: Judgments 1 to 5 ........................... 8-5
6. Heating Test Run and Cooling Test Run ............................................................................ 8-9
2. Reference ........................................................................................................................... 8-10
1. Purposes for Attaching VRF Renewal Kit ........................................................................ 8-10
2. Type of oil......................................................................................................................... 8-10
3. Oil discoloration ............................................................................................................... 8-10
4. Oil color standards for renewal ........................................................................................ 8-11
5. Standards for judging refrigerant with sight glass ............................................................ 8-11
3. INSTALLATION  INSTRUCTIONS (VRF Renewal Kit) ...................................................... 8-12
Contents
Renewal
8. RENEWAL
TD831155-04_MINI VRF.indb   1
TD831155-04_MINI VRF.indb   1
2014/01/07   11:47:24
2014/01/07   11:47:24
1
2
3
4
5
6
7
8
9
8 - 2
Renewal
1. Precautions on Renewal Design & Installation
1. General
VRF 
*1
 adopts the refrigerant R410A that has a higher pressure than conventional refrigerants, but it uses high-
precision microcomputer control to enable operation at a "design pressure of 3.3 MPa," which is around the same 
as that before the refrigerant R410A was adopted. This means that you can use refrigerant tubing for R22 
*2
.
Furthermore, if certain conditions are satisfi ed, you can reuse existing tubing by attaching one VRF Renewal Kit
(CZ-SLK2) to each outdoor unit.
When performing the work, check the "DESIGN of VRF SYSTEM" section together with this section.
NOTE
*1.  Systems for 2WAY VRF (ME1E81 series: only 8HP ~ 16HP), MINI VRF and 3WAY VRF.
*2.  Refrigerant tubing R22 has a maximum working pressure of 3.45 MPa and can be used for refrigerants such as 
R22 and R407C.
2. Basic Points for Using Existing Tubing
For existing tubing to be reused, the condition of the tubing needs to satisfy the basic points of "Safety" and
"Cleanliness". First, confi rm that the condition of the existing tubing satisfi es the following check items.
 
 Safety
• The existing unit shall be an air conditioner for use with R22/R407C/R410A refrigerant.
The reuse of existing tubing and the like that has been used for an application other than air conditioning 
(refrigerating device, etc.) is prohibited because it is diffi cult to know the situation.
• The tubing shall not be dented, cracked, corroded, etc.
Checking whether existing tubing is damaged, dented, and the like and the reliability of tubing strength is the 
responsibility of the installer performing the installation and is not guaranteed by us.
• The maximum working pressure of branches shall be 3.3 MPa or more. Furthermore, the branches shall be our 
genuine products.
We do not guarantee the tubing strength of any branch that is not a genuine product of us.
• The thermal insulation material shall not be decayed and peeling off.
If there is no thermal insulation installed on the liquid tubing, thermal insulation needs to be installed.
 
 Cleanliness
• The oil of the existing unit shall be any one of the following.
Mineral oil 
: Suniso, Freol S and MS
Synthetic fl uid : Alkyl benzene-type (HAB, Barrel-freeze), ester-type, ether-type (PVE only)
If the existing unit is GHP, cleaning of the tubing is required.
• The existing tubing shall be connected to the indoor unit and outdoor unit and be air tight.
Using tubing that is dirty inside as is may cause a failure of the new equipment.
• Trouble with foreign material contaminating the inside of the tubing shall not have occurred during the period
with which the existing unit was used (layer short in compressor, clogging caused by moisture freezing, oxide
scale, etc.). If such trouble has occurred, appropriate measures shall have been taken.
Using tubing that is dirty inside as is may cause a failure of the new equipment.