1. Outdoor Unit Control PCB
PCB and Functions
7 - 3
HIC PCB (HIC-6LE1E5)
CN-VDC+
P
U
V
W
NU
CN-VDC-
4WAY Valve
(CN-20S)
Crankcase 
heater
(CN-CH)
TD831155-04_MINI VRF.indb   3
TD831155-04_MINI VRF.indb   3
2014/01/07   11:47:18
2014/01/07   11:47:18
1
2
3
4
5
6
7
8
9
PCB and Functions
1. Outdoor Unit Control PCB
7 - 4
A.ADD
MODE
D303
(LED2)
D302
(LED1)
S003
JP001
TERMINAL
CN-PRY2
CN-PRY1
S002
S004
TEST
AP
RUN
STOP
CHK
1-2. 3-Phase Unit
CR-6LE1E8
CN-OPT1
CN-OPT2
EMG plug 
(CN-EMG)
SILENT 
(CN-
SILENT)
LED for 
EEPROM 
memory 
IC
(D330)
POWER LED
(D514)
High-pressure 
sensor
(CN-HPS)
Outdoor air 
temp
(CN-TO)
Comp discharge
temp
(CN-TD)
RC plug 
(CN-RC)
Liquid temp
(CN-C1)
Suction 
temp
(CN-TS)
High-pressure
switch plug
(CN-63PH)
OC plug
(CN-OC)
MOV plug
(CN-MOV1)
EEPROM memory IC
(IC18)
TD831155-04_MINI VRF.indb   4
TD831155-04_MINI VRF.indb   4
2014/01/07   11:47:20
2014/01/07   11:47:20
1
2
3
4
5
6
7
8
9
1. Outdoor Unit Control PCB
PCB and Functions
7 - 5
HIC PCB (HIC-6LE1E8)
U
P
PIN1
(VDC+)
PIN2
(VDC-)
V
W
NU
4WAY Valve
(CN-20S)
Crankcase 
heater
(CN-CH)
TD831155-04_MINI VRF.indb   5
TD831155-04_MINI VRF.indb   5
2014/01/07   11:47:22
2014/01/07   11:47:22
1
2
3
4
5
6
7
8
9
PCB and Functions
1. Outdoor Unit Control PCB
7 - 6
CN-A.ADD
setting if wiring is connected only to an outdoor unit and indoor units in a single 
system and the inter-unit control wiring does not cross multiple systems.
The setting is “1” at the time of shipment. It is not necessary to change the 
If wiring links the inter-unit control wiring for multiple systems to the same 
communications lines, then a different address must be set for each refrigerant 
tubing system.
•In the case of link wiring which combines the inter-unit control wiring for 
multiple systems into a single communications circuit, leave the connecting 
socket in place at only one of the outdoor units, and move the socket from the 
“SHORT” side to the “OPEN” side at all other outdoor units. If multiple 
connecting sockets are left in place, communications trouble will occur.
Rotary switch (10 positions, yellow): Outdoor system address setting switch
switch and S002.

If 10 systems or more are set, the setting is made by a combination of this DIP
If 10 – 19 systems are set, set switch 1 (10s digit) to ON.
If 20 – 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s 
digit) to OFF.
1-3.  Functions of Outdoor Unit PCB
2P plug : Automatic address setting pin
Short-circuit this pin for 1 second or longer to automatically set the addresses 
at the indoor units that are connected to that outdoor unit and are within the 
same system.
The system address is “1” at the time of shipment. Automatic address setting is 
necessary even for communications lines in a single system where the inter-
unit control wiring does not cross to any other systems.
While automatic address setting is in progress, the 2 LEDs (LED1, 2: red) on 
the outdoor unit control PCB blink alternately. (Short-circuiting this pin while 
automatic address setting is in progress will stop the automatic address setting 
operation.)
If wiring links multiple systems, a maximum of 30 systems (up to 64 indoor 
units) can be connected. This setting can be set up to “39,” however control will 
be for 30 systems even if the setting is set to higher than 30. An alarm will be 
displayed if system addresses are duplicated. (For details, refer to Table 1.)
DIP switch (2P): Switches for setting system address 10s digit and 20s digit
If 30 systems are set, set both switch 1 (10s digit) and switch 2 (20s digit) to 
ON.
(For details concerning S002 and S003, refer to Table 1.)
Rotary switch (16 positions, Red): Switch for setting the number of connected 
indoor units.
In order to allow the outdoor unit to manage indoor units in the same refrigerant 
system, set the number of connected indoor units. (For details, refer to Table 2.)
Jumper wire
3P plug : For communications circuit impedance matching
A connecting socket (3P, black) is attached to the terminal plug at the time of 
shipment from the factory.
TERMINAL
JP001
S004
S003
S002