DOWNLOAD Panasonic CS-Z25UD3EAW / CS-Z35UD3EAW / CS-Z50UD3EAW / CS-Z60UD3EAW / CU-Z25UBEA / CU-Z35UBEA / CU-Z50UBEA / CU-Z60UBEA Service Manual ↓ Size: 22.46 MB | Pages: 127 in PDF or view online for FREE

Model
CS-Z25UD3EAW CS-Z35UD3EAW CS-Z50UD3EAW CS-Z60UD3EAW CU-Z25UBEA CU-Z35UBEA CU-Z50UBEA CU-Z60UBEA
Pages
127
Size
22.46 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-z25ud3eaw-cs-z35ud3eaw-cs-z50ud3eaw-cs-z60ud3ea.pdf
Date

Panasonic CS-Z25UD3EAW / CS-Z35UD3EAW / CS-Z50UD3EAW / CS-Z60UD3EAW / CU-Z25UBEA / CU-Z35UBEA / CU-Z50UBEA / CU-Z60UBEA Service Manual ▷ View online

45 
12.1.4  Connecting the Drain Piping 
  Lay the drain piping so as to ensure drainage. 
  Use a locally purchased VP20 general rigid PVC pipe (outer diameter ø26) for the drain piping and firmly 
connect the indoor unit and the drain piping using supplied hose band to ensure that no leakage occurs. 
  Drain piping located indoor should always be insulated by wrapping with locally purchased insulation (foamed 
polyethylene with a thickness of 10 mm or more). 
  The drain piping should have a downward gradient (1/100 or more) and should be secured by using pipe hanging 
equipment to avoid creating hills or traps partway. 
  Should there be any obstacle preventing the drain piping from being extended smoothly, the drain piping can be 
raised outside of the main unit as shown in the illustration below. 
 
Rise
Hill
Trap
 
 
300 mm or less
(not a downward gradient)
500 mm or less
Good
At least 1/100
Drain insulator 
0
 
 
 
 
Drain hose 
8
Hard PVC pipe (VP20)
Hose band 
9
Unit drain port
Do not use adhesive.
Adhere with 
PVC adhesive.
 
 
 CAUTION
 
  Strictly do not install and extend the drain piping from the main unit drain water outlet horizontally or upward or raised it 50 cm or more. 
Doing so may result in poor drainage or drain motor failure. 
  Do not use drain hose bent at 90° angle. (The maximum permissible bend is 45°.) 
12.1.5  Insulating the Refrigerant Piping 
  After the piping is connected, insulate. (Refer to the illustration) 
 
Wrap fi rmly 
with vinyl tape, 
leaving no gaps.
Unit side
Wrap fi rmly 
with vinyl tape, 
leaving no gaps.
Flare insulator 
6
Clamper 
7
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
46 
12.1.6  Connecting the Indoor/Outdoor Connection Cable 
  Remove the control box cover and insert the 
connection cable into the control box. 
  Check the color of the wires on the terminal board 
and secure them with screws. 
  Secure the outer sheath of the connection cable 
with the cord clamp. 
  Reattach the control box cover to its original 
position. 
 
 CAUTION
 
When the wall is hollow, please be sure to use the 
sleeve for tube ass’y to prevent dangers caused by 
mice biting the connection cable. 
 
  Connection cable between indoor unit and 
outdoor unit should be approved polychloroprene 
sheathed 4 x 1.5 mm
2
 flexible cord, designation 
type 60245 IEC 57 (H05RN-F) or heavier cord. 
Allowable connection cable length of each indoor 
unit shall be 30 m or less. 
o  Ensure that the terminal numbers on the 
indoor unit are connected to the same 
terminal numbers on the outdoor unit by the 
right coloured wires as shown in the diagram. 
o  Earth lead wire should be longer than the 
other lead wires as shown in the diagram for 
electrical safety purpose in case the cord slips 
out from the anchorage. 
o  Secure the cable onto the control board with 
the holder (clamper). 
 
Terminals on the indoor unit
1
2
3
Colour of wires
Terminals on the outdoor unit
1
2
3
 
  Ensure the colour of wires of outdoor unit and the 
terminal Nos. are the same to the indoor’s 
respectively. 
  Earth wire shall be Yellow/Green (Y/G) in colour 
and longer than other AC wires for safety reason. 
 
 WARNING
 
 This equipment must be properly earthed.
 
Earth wire
Earth wire
(connection cable)
Holder for 
connection cable
Indoor/outdoor 
connection terminal
Indoor/outdoor 
connection cable
(remote control cable)
Wire remote control 
connector
FAN switch (SW2)
“DRAIN TEST” switch
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
47 
12.1.6.1  Wire Stripping and Connecting Requirement  
 
WARNING
RISK OF FIRE
JOINING OF WIRES MAY CAUSE 
OVERHEATING AND FIRE.
  Do not joint wires
OR
OR
OR
  Use complete wire without joining.
  Use approved socket and plug with earth pin.
   Wire connection in this area must follow to national 
wiring rules.
Conductor 
over inserted
Conductor 
fully inserted
Conductor not 
fully inserted
5 mm 
or more
Indoor/outdoor 
connection 
terminal board
(gap between wires)
ACCEPT
PROHIBITED
PROHIBITED
Wire stripping
No loose strand 
when inserted
10 ± 1 mm
 
 
12.1.7  Connect the Piping 
12.1.7.1 Connecting 
the Piping to Indoor 
For connection joint of all model (except R32 model) 
Please make flare after inserting flare nut (locate at 
joint portion of tube assembly) onto the copper pipe. 
(In case of using long piping) 
 
Connect the piping 
  Align the center of piping and sufficiently tighten 
the flare nut with fingers. 
  Further tighten the flare nut with torque wrench in 
specified torque as stated in the table. 
 
Torque wrench
Spanner or 
Wrench
 
 
 
 
 
 
 
For connection joint of R32 models 
  Decide the length. 
  Cut and remove the tube connectors at indoor 
copper pipings (both gas and liquid piping) by 
using pipe cutter. Remove burrs from cut edge. 
  Use pipe expander to expand the end of long 
piping. 
  Align the center of piping and braze the piping 
joints. 
 
Indoor copper pipe
Tube connector
(40~50mm)
Brazing point
1. Cut and Remove
2.  Expand long pipe
3.  Braze both pipe
 
 
  Braze the piping joints carefully so that the indoor 
unit is not damaged by brazing flame. 
If necessary, cover with wet clothes to prevent 
parts unintentionally overburnt. 
 
 
 
 
 
 
48 
12.1.7.2 Connecting 
the 
Piping to Outdoor 
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the 
flare nut (locate at valve) onto the copper pipe. Align center of piping to valve and then tighten with torque wrench to 
the specified torque as stated in the table. 
12.1.7.3  Connecting the Piping to Outdoor Multi 
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the 
flare nut (locate at valve) onto the copper pipe. Align center of piping to valve and then tighten with torque wrench to 
the specified torque as stated in the table. 
 
For Gas side piping please refer table and diagram below
Outdoor Multi Combination Model 
R410A Model
Pipe size (refer 
to diagram)
R32 Model
Pipe size (refer 
to diagram)
CS-MZ20*
CS-Z25*
CS-Z35*
CU-2E12*
CU-2E15*
CU-2E18*
CU-3E18*
CU-3E23*
CU-4E23*
CU-4E27*
CU-5E34*
CU-2Z35*
CU-2Z41*
CU-2Z50*
CU-3Z52*
CU-3Z68*
CU-4Z68*
CU-4Z80*
CU-5Z90*
CS-Z50*
CU-2E18*
CU-3E18*
CU-3E23*
CU-4E23*
CU-4E27*
CU-5E34*
(CZ-MA1P)
CU-2Z50*
CU-3Z52*
CU-3Z68*
CU-4Z68*
CU-4Z80*
CU-5Z90*
CS-Z60*
CU-3E23*
CU-4E23*
CU-4E27*
CU-5E34*
(CZ-MA2P)
CU-3Z68*
CU-4Z68*
CU-4Z80*
CU-5Z90*
(CZ-MA2P)
Kindly contact authorized dealer for connectivity validity.
Connection pipe
(female side)
Auxiliary pipe
(male side)
Flare Nut
Hall Union
Liquid side
Connection pipe (female side)
Auxiliary pipe (male side)
Flare Nut
Hall Union
Hall Union
Packing
Connection pipe 
(female side)
Auxiliary pipe
 (male side)
Pipe size reducer (CZ-MA1P)
Flare Nut
Auxiliary pipe
 (male side)
 (Outdoor)
Auxiliary pipe
 (male side)
 (Indoor)
Hall Union
Hall Union
Packing
Connection pipe (female side)
Pipe size expander (CZ-MA2P)
Flare Nut
Auxiliary pipe
 (male side)
 (Outdoor)
(Indoor)
Hall Union
Brazing point
Connection pipe (female side)
Flare Nut
Auxiliary pipe (male side)
 (Outdoor)
(Indoor)
Hall Union
Brazing point
Connection pipe (female side)
Flare Nut
Packing
Pipe size expander (CZ-MA2P)
Gas side
 
 
12.1.8 Switching 
the 
High State Switch (SW2) 
  To increase the air volume, open the control box and on the control board, switch the FAN switch (SW2) to “HI”. 
  See the diagram for “Connecting the Indoor/Outdoor Connection Cable”. 
12.1.9  Note: Enabling long-range remote control 
  To maintain EMC emission limits, cabling interconnecting the HA terminal and subsequent opto-coupler, must be 
no more than 1.9 m length. 
  Loop four turns of this cable through a suitable small EMC ferrite toroid, and protect with a short length of large 
diameter heat-shrink tube. 
  There is no similar length limit for cable following on from the opto-coupler isolation.  
12.1.10  Check the Drainage 
Check after connecting the power supply. 
  Pour approximately 600 cc of water into the drain pan of the main unit using a squeeze bottle, etc. 
  Press the drain test run switch on the control board in the control box to start the drain motor and check whether 
the water drains normally. 
(The drain motor operates for approximately 5 minutes and then stops automatically.) 
(See the diagram for “Connecting the Indoor/Outdoor Connection Cable”.) 
 
Heat 
exchanger
Drain pan
Squeeze bottle
Approximately 
600 cc of water
 
 
 
Page of 127
Display

Click on the first or last page to see other CS-Z25UD3EAW / CS-Z35UD3EAW / CS-Z50UD3EAW / CS-Z60UD3EAW / CU-Z25UBEA / CU-Z35UBEA / CU-Z50UBEA / CU-Z60UBEA service manuals if exist.