8.4. Automatic Mode Operation
 1. When the Automatic Mode Operation is selected, the indoor fan operates at SLo fan speed for 25 seconds to sense intake air
temperature and determine the 1st operation mode.
 2. Operation mode will be determine again after 1 hour of operation, if the room temperature reaches to set temperature and
compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running)
eventhough after 1 hour from automatic operation mode started.
Present
Judgement
Next Mode
Mode
Cooling
Soft Dry
Heating
O
O
Cooling
23°C
Cooling
(Judgement:
Not Applicable
(Judgement:
Heating
23°C & Above)
Below 23°C)
O
O
Soft Dry
20°C
Soft Dry
Not Applicable
(Judgement:
(Judgement:
Heating
20°C & Above)
Below 20°C)
O
O
Heating
Cooling
(Judgement:
Not Applicable
(Judgement:
25°C
Heating
Above 25°C)
25°C & below)
Automatic Set Temperature
Refer 3. as below.
 3. Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the “Room Temperature Setting
button”.
Operation
Hi
(Standard)
Lo
(+2°C)
(±0°C)
(-2°C)
Cooling
27°C
25°C
23°C
Soft Dry
24°C
22°C
20°C
Heating
23°C
21°C
19°C
  • The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at
indoor electronic controller.
29
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
8.5. Random Auto Restart Control
  • If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the
power is resumed. It will start with previous operation mode and airflow direction.
  • Restart time is decided randomly using 4 parameter:
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
  • Random Auto Restart Control is not available when Timer is set.
  • This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
8.6. Delay ON Timer Control
  • When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time, so that
the room will reach nearly to the set temperature by the desired time.
  • For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
  • For Heating mode, the operation will start 30 minutes before the set time.
  • For Automatic mode, the indoor fan will operate at SLo speed for 25 seconds, 30 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
8.7. Remote Control Signal Receiving Sound
  • Long beep sound will be heard when:-
  − Stopping the Air Conditioner using ON/OFF switch.
  − Stopping the Quiet Mode.
  − Stopping the Powerful Mode.
  − Stopping the Ion Mode.
  • Short beep sound will be heard for others.
  • To switch off the beep sound:-
Press the “Automatic Operation Button” continuously for 10 seconds or more (“beep” “beep” will be heard at the 10th second).
Repeat the above if you want to switch ON the beep sound.
However, if the “Automatic Operation Button” has been pressed the Automatic operation will be activated.
If you do not require this operation, you may change it by using the remote control.
8.8. Indoor Fan Speed Control
Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is shifted automatically between Stop to SHi depend on each operation as shown
below.
Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote
control.
30
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
31
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
 1. Vertical Airflow Direction
  • The louver swings up and down as shown above.
  • The louver does not swing when the Indoor Fan stops
during operation at the upper limit.
Heating Mode
  • When the intake air temp. reaches 38°C, the louver is
changed from upper to lower limit. When the intake air
temp falls to 35°C, the louver is changed from lower to
upper limit.
 2. Horizontal Airflow Direction
  • The louver can be selected between 14° - 36° (as
shown above) when pressing Manual Airflow Direction
Selection Button.
  • The louver can be selected between 0° - 61° (as shown
above)
when
pressing
Manual
Airflow
Direction
Selection Button.
8.9. Airflow Direction Control
Cooling, Ion and Soft Dry Mode
  • The left and right airflow direction louvers can be adjusted manually.
32