Automatic Fan Speed Mode
Heating Operating Time Diagram
When Automatic Fan Speed is selected at Remote Control during heating operation.
  • Fan speed rotates in the range of Me → SLo according to the heat exchanger temperature.
  • If use Manual Fan Speed,
at above diagram will operate with setting Fan Speed.
25
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
  • Normal Deicing
Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for
50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
  • Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
  • Deicing ends when
 1. 12 minutes after deicing operation starts;
 2. TRS senses the outdoor piping temperature rises to 4°C (TRS OPEN).
 3. Deicing will not end immediately as time delay (Td) is valid as shown below.
  • Once deicing operation starts, it will not end for 60 seconds.
  • After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
26
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
Normal Deicing Time Diagram
Overload Deicing Time Diagram
27
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5
Quiet Operation Control
(For Heating Mode)
  • Purpose of this operation is to provide quite heating operation compare to normal operation.
  • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically
decreased 2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation.
  • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
  • Manual Airflow Direction:-
  − Rpm control during Lo, Me & Hi Cool
  • Auto Airflow Direction:-
  − Rpm control depends on the piping air temperature sensor of Indoor heat exchanger
  • Quiet Mode Operation will stop if:-
  − Quiet mode button is pressed again.
  − Stopped by ON/OFF switch.
  − Timer OFF activates.
  − Powerful mode button is pressed.
28