How to pull the piping and drain hose out, in case of the
embedded piping.
embedded piping.
•
In case of left piping how to insert the
connection cable and drain hose.
connection cable and drain hose.
Rear view for left piping installation
Adjust the piping slightly
downwards.
downwards.
Drain hose
Connection cable
Exchange the drain hose and
the cap
the cap
(For the right piping, follow the same procedure)
Drain cap
Drain hose
PVC tube for
drain hose
drain hose
Indoor unit
55mm (1/2 ~ 1.75Hp) or
80mm (2.0 ~ 2.5Hp)
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
caulking material
to seal the wall
opening.
Connection cable
Piping
More than
470 mm
More than 950mm
(1/2 ~ 1.75Hp) or
1150mm (2.0 ~ 2.5Hp)
PVC tube (VP-65) for piping and
connection cable
connection cable
PVC tube for drain hose (VP-30)
PVC tube for
drain hose (VP-20)
drain hose (VP-20)
More than 700 mm
Drain hose
from main unit
from main unit
Cable
45°
Drain hose
Piping
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 950mm
(1/2 ~ 1.75Hp) or
1150mm (2.0 ~ 2.5Hp)
(1/2 ~ 1.75Hp) or
1150mm (2.0 ~ 2.5Hp)
12.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connection cable can be connected without removing the front grille.
2 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
2 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
4 x 1.5 mm
2
flexible cord, type designation 60245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short. Allowable connection
cable length of each indoor unit shall be 30 m or less.
cable length of each indoor unit shall be 30 m or less.
3 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the
escapement.
4 Remove the tapes and connect the connection cable between indoor unit and outdoor unit according to the
diagram below.
Terminals on the outdoor unit
L
N
1
2
3
Colour of wires
Terminals on the indoor unit
1
2
3
34
5 Secure the connection cable onto the control board with the holder.
o
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s
respectively.
respectively.
o
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
Connection cable
Indoor & outdoor
connection cable
Escapement
Terminal Board
Recommended
length (mm)
Earth Wire
longer than
others AC
wires for
safety reason
longer than
others AC
wires for
safety reason
Holder
Indoor & outdoor
connection cable
connection cable
Outdoor unit
Tape
Recommended
length (mm)
length (mm)
a
b
c
d
35
35
35 55
WARNING
This equipment must be properly earthed.
12.2.4.1 Wire Stripping Connecting and Requirement
WARNING
OR
Use complete wire
without joining.
Use approved socket
and plug with earth pin.
Wire connection in this
area must follow to
national wiring rules.
national wiring rules.
Wire stripping
No loose strand
when inserted
when inserted
10 ± 1 mm
RISK OF FIRE
JOINING OF WIRES
MAY CAUSE
OVERHEATING AND
FIRE.
MAY CAUSE
OVERHEATING AND
FIRE.
5 mm or more
(gap between wires)
Indoor/outdoor
connection
terminal board
connection
terminal board
Do not joint wires
OR
OR
Conductor
fully inserted
Conductor over
inserted
Conductor not
fully inserted
ACCEPT
PROHIBITED
PROHIBITED
35
12.3 Outdoor Unit
12.3.1 Install the Outdoor Unit
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt, screws or nails.
A
B
C
D
Model A
B
C
D
TZ20***, TZ25***, TZ35*** 570 mm 105 mm 18.5 mm 320 mm
TZ42***, TZ50***
TZ42***, TZ50***
540 mm 160 mm 18.5 mm 330 mm
12.3.2 Connect the Piping
12.3.2.1 Connecting
the Piping to Indoor
For connection joint location at outside building of all
model (except R32 model)
Please make flare after inserting flare nut (locate at
joint portion of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
model (except R32 model)
Please make flare after inserting flare nut (locate at
joint portion of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
Align the center of piping and sufficiently tighten
the flare nut with fingers.
Further tighten the flare nut with torque wrench in
specified torque as stated in the table.
Torque
wrench
wrench
Spanner or
Wrench
Wrench
For connection joint location at inside building for R32
model only
model only
Decide the length.
Cut and remove the tube connectors at indoor
copper pipings (both gas and liquid piping) by
using pipe cutter. Remove burrs from cut edge.
using pipe cutter. Remove burrs from cut edge.
Use pipe expander to expand the end of long
piping.
Align the center of piping and braze the piping
joints.
Indoor
copper pipe
copper pipe
Tube connector
(40~50mm)
Brazing point
1. Cut and
Remove
2. Expand long
pipe
3. Braze both
pipe
12.3.2.2 Connecting
the
Piping to Outdoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make flare after inserting the flare nut (locate at valve)
onto the copper pipe.
Align center of piping to valve and then tighten with
torque wrench to the specified torque as stated in the
table.
Remove burrs from cut edge.
Make flare after inserting the flare nut (locate at valve)
onto the copper pipe.
Align center of piping to valve and then tighten with
torque wrench to the specified torque as stated in the
table.
Do not overtighten, overtightening may cause gas leakage.
Piping size
Torque
6.35 mm (1/4")
[18 N•m (1.8 kgf•m)]
9.52 mm (3/8")
[42 N•m (4.3 kgf•m)]
12.7 mm (1/2")
[55 N•m (5.6 kgf•m)]
15.88 mm (5/8")
[65 N•m (6.6 kgf•m)]
19.05 mm (3/4")
[100 N•m (10.2 kgf•m)]
36
12.3.2.3 Connecting the Piping to Outdoor Multi
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge. Make flare after inserting the
flare nut (locate at valve) onto the copper pipe. Align center
of piping to valve and then tighten with torque wrench to
the specified torque as stated in the table.
* For Gas side piping please refer table and diagram below
Remove burrs from cut edge. Make flare after inserting the
flare nut (locate at valve) onto the copper pipe. Align center
of piping to valve and then tighten with torque wrench to
the specified torque as stated in the table.
* For Gas side piping please refer table and diagram below
Connection pipe
(female side)
Auxiliary pipe
(male side)
Flare Nut
Hall Union
Liquid side
Outdoor Multi Combination Model
Pipe size (refer
to diagram)
R32 Model
R410A Model
CS-MTZ16***,
CS-TZ20***,
CS-TE20***,
CS-TZ25***,
CS-TE25***,
CS-TZ35***,
CS-TE35***
CS-TZ20***,
CS-TE20***,
CS-TZ25***,
CS-TE25***,
CS-TZ35***,
CS-TE35***
CU-2Z35***,
CU-2Z41***,
CU-2Z50***,
CU-3Z52***,
CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***,
CU-2TZ41***,
CU-2TZ50***,
CU-3TZ52***
CU-2Z41***,
CU-2Z50***,
CU-3Z52***,
CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***,
CU-2TZ41***,
CU-2TZ50***,
CU-3TZ52***
CU-2E12***,
CU-2E15***,
CU-2E18***,
CU-3E18***,
CU-3E23***,
CU-4E23***,
CU-4E27***,
CU-5E34***,
CU-2RE15***,
CU-2RE18***,
CU-3RE18***
CU-2E15***,
CU-2E18***,
CU-3E18***,
CU-3E23***,
CU-4E23***,
CU-4E27***,
CU-5E34***,
CU-2RE15***,
CU-2RE18***,
CU-3RE18***
CS-TZ42***,
CS-TE42***,
CS-TZ50***,
CS-TE50***
CS-TE42***,
CS-TZ50***,
CS-TE50***
CU-2Z50***,
CU-3Z52***,
CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***,
CU-2TZ50***,
CU-3TZ52***
CU-3Z52***,
CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***,
CU-2TZ50***,
CU-3TZ52***
CU-2E18***,
CU-3E18***,
CU-3E23***,
CU-4E23***,
CU-4E27***,
CU-5E34***,
CU-2RE18***,
CU-3RE18***
CU-3E18***,
CU-3E23***,
CU-4E23***,
CU-4E27***,
CU-5E34***,
CU-2RE18***,
CU-3RE18***
(CZ-MA1P)
CS-TZ60***,
CS-TE60***
CS-TE60***
CU-4Z68***,
CU-4Z80***,
CU-5Z90***
CU-4Z80***,
CU-5Z90***
CU-4E23***,
CU-4E27***,
CU-5E34***
CU-4E27***,
CU-5E34***
(CZ-MA2P)
CS-TZ71***
CU-4Z80***,
CU-5Z90***
CU-5Z90***
CU-4E27***,
CU-5E34***
CU-5E34***
(CZ-MA2P) &
(CZ-MA3P)
Hall Union
Connection pipe
(female side)
Auxiliary pipe
(male side)
Flare Nut
Hall Union
Packing
Connection pipe
(female side)
Auxiliary pipe
(male side)
Pipe size reducer (CZ-MA1P)
Flare Nut
Auxiliary pipe
(male side)
(Outdoor)
Auxiliary pipe
(male side)
(Indoor)
Hall Union
Hall Union
Packing
Connection pipe
(female side)
Pipe size expander
(CZ-MA2P)
Flare Nut
Auxiliary pipe
(male side)
(Outdoor)
Auxiliary pipe
(male side)
(Indoor)
Hall Union
Hall Union
Packing
Packing
Connection pipe
(female side)
Pipe size expander
(CZ-MA2P)
Flare Nut
Pipe size reducer
(CZ-MA3P)
Gas side