DOWNLOAD Panasonic CS-TZ50TKEW / CU-TZ50TKE Service Manual ↓ Size: 18.36 MB | Pages: 127 in PDF or view online for FREE

Model
CS-TZ50TKEW CU-TZ50TKE
Pages
127
Size
18.36 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-tz50tkew-cu-tz50tke.pdf
Date

Panasonic CS-TZ50TKEW / CU-TZ50TKE Service Manual ▷ View online

37 
AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM 
12.3.3  Evacuation of the Equipment 
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND 
PIPES in the following procedure. 
 
 
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. 
 
There is no extra refrigerant in the outdoor unit for air purging. 
 
OPEN
CLOSE
Gas side
Liquid side
Outdoor unit
Two-way valve
Three-way valve
Indoor unit
Vacuum 
pump
Close
Close
 
 
1  Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way 
valve. 
Be sure to connect the end of the charging hose with the push pin to the service port. 
2  Connect the center hose of the charging set to a vacuum pump. 
3  Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from  
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes. 
4  Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the 
gauge does not move after approximately five minutes. 
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE. 
5  Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve. 
6  Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench. 
7  Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” 
using a hexagonal wrench (4 mm). 
8  Mount valve caps onto the 2-way valve and the 3-way valve. 
Be sure to check for gas leakage. 
 
 
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure: 
If the leak stops when the piping connections are tightened further, continue working from step 3. 
If the leak does not stop when the connections are retightened, repair location of leak. 
Do not release refrigerant during piping work for installation and reinstallation. 
Take care of the liquid refrigerant, it may cause frostbite. 
 
 
 
 
 
 
 
 
38 
12.3.4  Connect the Cable to the Outdoor Unit 
1  Remove the control board cover from the unit by loosening the screw. 
2  Cable connection to the power supply through Isolating Devices (Disconnecting means). 
Connect approved type polychloroprene sheathed power supply cord 3 x 1.5 mm
(3/4 ~ 1.75HP),  
3 x 2.5 mm
2
 (2.0 ~ 2.5HP) type designation 60245 IEC 57 or heavier cord to the terminal board, and 
connect the others end of the cord to Isolating Devices (Disconnecting means). 
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or 
otherwise) is too short. 
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air 
conditioner shall be done by using approved socket and plug with earth pin rated 15/16A (3/4 ~ 1.75HP) 
or 16A (2.0HP) or 20A (2.5HP). Wiring work to both socket and plug must follow to national wiring 
standard. 
3  Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed  
4 x 1.5 mm
2
 flexible cord, type designation 60245 IEC 57 or heavier cord. Do not use joint connection cable. 
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short. Allowable connection 
cable length of each indoor unit shall be 30 m or less. 
4  Connect the power supply cord and connection cable between indoor unit and outdoor unit according to the 
diagram below. 
 
3
2
1
t
i
n
u
 
r
o
o
d
n
i
 
e
h
t
 
n
o
 
s
l
a
n
i
m
r
e
T
Colour of wires (connection cable)
Terminals on the outdoor unit
L
N
1
2
3
(Power supply cord)
Terminals on the isolating 
devices (Disconnecting means)
(L) (N)
 
 
5  Secure the power supply cord and connection cable onto the control board with the holder. 
6  Attach the control board cover back to the original position with screw. 
7  For wire stripping and connection requirement, refer to instruction 12.2.4 of indoor unit. 
 
Terminal 
Board
Holder
Isolating Devices
Indoor unit
Power 
supply 
cord
Indoor & 
outdoor 
connection 
cable
Earth wire 
longer 
than 
others 
AC wires 
for safety 
reason
 
 
 WARNING
 
 This equipment must be properly earthed.
 
Note 
  Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap. 
  Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason. 
  Always ensure all above connections compliant with national wire rules. 
 
 
 
 
39 
12.3.5 Piping 
Insulation 
1  Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation 
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 
2  If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by 
using POLY-E FOAM with thickness 6 mm or above. 
 
12.3.5.1 Cutting 
and 
Flaring the Piping 
1  Please cut using pipe cutter and then remove the burrs. 
2  Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end 
down to avoid the metal powder entering the pipe. 
3  Please make flare after inserting the flare nut onto the copper pipes. 
 
When properly fl ared, the internal surface of the 
fl are will evenly shine and be of even thickness. 
Since the fl are part comes into contact with the 
connections, carefully check the fl are fi nish.
 Improper  fl aring 
Inclined Surface 
damaged
Cracked Uneven 
thickness
1.  To cut
2.  To remove burrs
3.  To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper pipe
Reamer
Point down
Pipe
 
 
12.3.6 How 
to 
Take 
Out Front Grille 
Please follow the steps below to take out front grille if 
necessary such as when servicing. 
1  Set the vertical airflow direction louvers to the 
horizontal position. 
2  Remove the 2 caps (1/2 ~ 1.75HP) or 3 caps 
(2.0 ~ 2.5HP) on the front grille as shown in 
the illustration at right, and then remove the  
3 (1/2 ~ 1.75HP) or 4 (2.0 ~ 2.5HP) mounting 
screws. 
3  Pull the lower section of the front grille 
towards you to remove the front grille. 
 
When reinstalling the front grille, first set the 
vertical airflow direction louver to the horizontal 
position and then carry out above steps 2 - 3 in 
the reverse order. 
Screw
Screw
Vane
Cap
Test pen
Move 
the vane 
downward
 
• Use Test pen to 
remove Cap
(only for 2.0HP ~ 2.5HP 
model)
Front grille
Front grille
 
 
 
 
12.3.7  Disposal of Outdoor Unit Drain Water 
  If a drain elbow is used, the unit should be placed 
on a stand which is taller than 3 cm. 
  If the unit is used in an area where temperature 
falls below 0°C for 2 or 3 days in succession, it is 
recommended not to use a drain elbow, for the 
drain water freezes and the fan will not rotate. 
 
Hose
Install the hose at an angle so that the 
water smoothly fl ows out.
Drain elbow
 
7
 
 
12.3.8  Check the Drainage 
  Open front panel and remove air filters. (Drainage 
checking can be carried out without removing the 
front grille.) 
  Pour a glass of water into the drain tray-styrofoam. 
  Ensure that water flows out from drain hose of the 
indoor unit. 
 
Drain tray-styrofoam
 
 
 
40 
12.3.9  Evaluation of the Performance 
  Operate the unit at cooling/heating operation 
mode for fifteen minutes or more. 
  Measure the temperature of the intake and 
discharge air. 
  Ensure the difference between the intake 
temperature and the discharge is more than 8°C 
during Cooling operation or more than 14°C 
during Heating operation. 
 
Discharge air
 
 
12.3.10  Installation of Air Purifying Filter 
1  Open the front panel. 
2  Remove the air filters. 
3  Put the Air purifying filter into place as shown 
in illustration at right. 
 
1
3
2
Air fi lter
Air purifying filter 
8
 
 
Page of 127
Display

Click on the first or last page to see other CS-TZ50TKEW / CU-TZ50TKE service manuals if exist.