12.1.7.
Outdoor Fan Motor Operation
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation.
12.2. Airflow Direction
1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger
temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
12.2.1.
Vertical Airflow
1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depands on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions
of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close
position.
12.2.2.
Horizontal Airflow
• The horizontal airflow direction louvers can be adjusted manually by hand.
12.3. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
• When “quiet” button at remote control is pressed.
Quiet LED illuminates.
Operation Mode
Airflow Direction
Vane Angle (
q)
1
2
3
4
5
Heating
Auto with Heat Exchanger 
Temperature
A
28
B
45
C
28
Manual
4
20
35
51
66
Cooling and e-ion
Auto
12 ~ 40
Manual
12
19
26
33
40
Soft Dry
Auto
12
Manual
12
19
26
33
40
30
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a.Powerful button is pressed.
b.Stop by OFF/ON switch.
c.Timer “off” activates.
d.Quiet button is pressed again.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except ion only operation.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
C. Control contents
1. Auto fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
2. Manual fan speed for quiet operation is -1 step from setting fan speed.
12.3.1.
Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
• When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. Quiet button is pressed again.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, expected ion only
operation.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
C. Control contents
a. Fan speed auto
1. Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger. 
Auto fan speed is changed from normal setting to quiet setting of respective fan speed. 
This is to reduce sound of Hi, Me, Lo for 3dB.
b. Fan speed manual
1. Manual fan speed for quiet operation is -1 step from setting fan speed.
12.4. Powerful Mode Operation
A. Purpose
To achieve the setting temperature quickly.
B. Control Condition
a. Powerful operation start condition
When the “powerful” button at remote control is pressed, Powerful LED illuminates
b. Powerful operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed again
b. Quiet button is pressed
c. Stop by OFF/ON switch
d. Timer OFF is pressed again
31
2. When Powerful operation is stopped, operation is shifted to normal operation.
C. Control Contents
a. Fan speed
1. Indoor fan speed depends on indoor intake temperature and remote control setting temperature. Fan speed is changed
from normal setting to Powerful setting of respective fan speed.
b. Temperature shifting
1. Internal setting temperature shift depends on indoor pipe temperature. Temperature is decreased (Cooling and Soft Dry
operation) or increased (Heating operation) accordingly.
12.5. ON Timer Control
ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a
comfortable environment when reaching the set ON time.
70 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the
indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the judgment, the decided operation will start operate earlier than the set time as shown below.
12.6. OFF Timer Control
OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
12.7. Auto Restart Control
1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after
power supply resumes.
2. This type of control is not applicable during ON/OFF Timer setting.
12.8. Indication Panel
Note:
• If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode judgement,
or ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
LED
POWER
TIMER
Ion
Color
Green
Orange
Blue
Light ON
Operation ON
Quiet Setting ON
Ion ON
Light OFF
Operation OFF
Quiet Setting OFF
Ion OFF
32
12.9. Ionizer Operation
Purpose
To provide fresh air effect to users by discharging minus ion to air.
Control Condition
a. Ionizer Only Operation.
1. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at remote control is pressed.
Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1
o2)
However, fan speed can be adjusted later by customer during this operation.
Airflow direction (Horizontal Vane) control:
Follow vane direction control at cooling mode.
Horizontal vane can be changed by customer during ion only operation.
b. Operation Mode + Ionizer Operation
1. Ionizer Operation Start Condition.
When air conditioner unit is in “ON” condition (Heat, Cool, Dry, Auto mode) and ION operation button at remote control is
pressed. Ionizer on & ION LED illuminates. (3
o4)
Power LED also illuminates.
2. Ionizer Operation Stop Condition.
When one of the following condition is satisfied, ION operation stops.
a. Stopped by ON/OFF switch.
b. Timer OFF activates.
c. ION feedback signal shows error.
3. Ionizer operation status is not memorised by microcontroller. After OFF, when operation is “ON” again, air conditioner
operates without ionizer operation.
12.9.1.
Ionizer Error Detection
• There are 3 errors detect by the unit.
a. Connector Open Detection
- If the connector is pulled out during ionizer operation, ion LED blinks.
- Once the ionizer connector reconnect to the unit, ion LED stops blinking.
b. Ionizer Control Discharge Error Detection
- When ionizer generator is short circuit due to water or dust adhesion, power supplies to ionizer is stopped for 30 minutes
and resume power supply after 30 minutes. If this situation happens for 24 times, ion LED blinks.
- The connector resets when the ionizer operates normally for 10 minutes or the unit switched off.
Fan speed
Manual
Remote Control set fan speed
Auto
Repetition of 8 patterns as shown below.