9.2.
Outdoor Unit
18
10 Printed Circuit Board
10.1. Indoor Unit
10.1.1.
Printed Circuit Board
19
10.2. Outdoor Unit
10.2.1.
Main Printed Circuit Board
20
11 Installation Instruction
11.1. Select The Best Location
INDOOR UNIT
• Do not install the unit in excessive oil fume area such as
kitchen, workshop and etc.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
Example: For TE9HKE
If the unit is installed at 10 m distance, the quantity of additional
refrigerant should be 50g ...... (10 - 7.5) m x 20 g/m = 50 g
11.2. Indoor/Outdoor Unit 
Installation Diagram
Piping size
Rated
Length
(m)
Max
Elevation
(m)
Min. 
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional 
Refrigerant 
(g/m)
Model
Gas Liquid
TE9HKE 3/8” 1/4”
7.5
15
3
15
20
TE12HKE, 
TE15HKE
1/2” 1/4”
7.5
15
3
15
20