21 
Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way 
valve. 
Be sure to connect the end of the charging hose with the push pin to the service port. 
Connect the center hose  of the charging set to a vacuum pump. 
Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 
0cmHg (0 Mpa) to -76cmHg (-0.1Mpa). Then evacuate the air approximately ten minutes. 
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure the needle in the 
gauge does not move after approximately five minutes. 
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE. 
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve. 
Tighten the service port caps of the 3-way valve at a torque of 18N
ym with a torque wrench. 
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” 
using a hexagonal wrench (4mm). 
Mount valve caps onto the 2-way valve and the 3-way valve. 
Be sure to check for gas leakage. 
 
Caution 
•  If gauge needle does not move from 0cmHg (0Mpa) to -76cmHg (-0.1Mpa), in step 3 above take the following 
measure: 
•  If the leak stops when the piping connections are tightened further, continue working from step 3. 
•  If the leak does not stop when the connections are retightened, repair location of leak. 
•  Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, 
it may cause frostbite. 
9.3.4 
Connect the cable to the outdoor unit 
 
Remove the control board cover from the unit by loosening the screw. 
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5x 1.0 
mm
2
.( PA7KKD,PA9KKD) or 5 x 1.5mm
2
 (PA12KKD, PA16KKD) flexible cords, type designation 245 IEC 57 
or heavier cord. 
 
 
 
 
 
 
Secure the cable onto the control board with the holder (clamper). 
Attach the control board cover back to the original position with the screw. 
For wiring stripping and connection requirement, refer to instruction 9.2.4.1 of indoor unit. 
 
9.3.5 Piping 
insulation 
Please carry insulation at piping connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. 
Please wrap the insulated piping end to prevent water from going inside the piping. 
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by 
using POLY-E-FOAM with thickness 6mm or above. 
22 
10. Operation 
Control 
10.1 Cooling Operation 
Cooling Operation can be set using remote control. 
This operation is applied to cool down the room temperature to the setting temperature set on the 
remote control. 
The remote control setting temperature, which takes the reading of intake air temperature sensor, can 
be adjusted from 16℃ to 30℃ 
During cooling operation, the compressor will stop and restart as shown in figure below: 
 
10.1.1  Time Graph for Cooling Operation. 
 
 
 
23 
10.2  Soft Dry Operation 
Soft Dry Operation can be set using remote control. 
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. 
When selecting Soft Dry operation, the operation will be cooling until the room temperature reaches the set 
temperature on remote control, and then soft Dry will be activated. 
The Soft Dry operation runs for less tan 10 minutes and once stop it will not be activated within 6 minutes. 
Dry operation area is shown as follows:- 
 
 
10.2.1  Time Graph for Soft Dry operation. 
10.3 Heating Operation 
z  Heating operation can be set using remote control. 
z  This operation is applied to warm the room temperature reaches the setting temperature set on the remote 
control. 
z  The remote control setting temperature, which takes the reading of intake air temperature sensor, can be 
adjusted from 16℃ to 30℃ 
z  During heating operation, the compressor will stop running and restart as shown in below figure. 
 
24 
 
10.3.1  Time Graph for Heating Operation. 
10.3.2 Deice 
Control 
Deice operation is to protect the outdoor unit from freezing. Operation is determined by outdoor pipe temperature and 
operation time.  
 
Deicing operation ends under any one of conditions below:- 
A.  Deicing operation has operated for 12 minutes. 
B.  Outdoor piping temperature rises to 12℃ or above for  10 seconds. 
 
z  Normal Deice Operation. 
Deicing starts 30 minutes after heating mode operation or 60 minutes after the latest deicing operation. If outdoor 
piping tested by pipe sensor falls to -3℃ or below for continuously 50 seconds, deicing operation starts. 
 
[Time Graph] 
 
 
 