Time graph of deicing
Deicing Operation
ON
OFF
ON
OFF
ON
OFF
Normal control
Normal control
Normal control
Normal control
Normal control
Normal control
Compressor
4-way valve
Outdoor fan
Outdoor
expansion valve
Gas bypass
valve
Start control
Liquid bypass
valve
Indoor expansion
valve
Indoor fan
Sensor
Normal control
Releasing temperature value
Stop
The maximal is 9 minutes and 30 seconds
Normal control
Control judging signal
Control releasing signal
Start control
Start control
Start control
ON
Start control
Start control
ON
OFF
30Hz
90Hz
480
480
1
3
30S
30S
30Hz
50Hz
70Hz
93
CU-MP28DBH5/CU-MP50DBH5
When the heat exchanger temperature reaches the values shown in the following table(Table
26) or lasts for 10 minutes and 30 seconds, deicing operation will end.
Table 26
Outdoor air temperature
>-3
-3
>T>-10
<10
Heat exchanger
temperature (
)
Maximum deicing time
T
11
T
5
T
3
9.11. Overload control
Overload control/outlet pressure upper limit protection (cooling)
Control A
normal control
Normal
overload control
60.5
56.5
When heat exchanger temperature is less than 56.5
, this control will be released.
Overload control/intake pressure lower limit protection (heating)
For heating operation, the outdoor unit will enter overload control if the intake pressure is the
value in the following table. At this moment, the operation frequency of the compressor is 90%
or less of the operation frequency in normal control (the lower limit frequency is 30Hz). Seen
as the following graph:
When heat exchanger temperature is less than 56.5
, this control will be released.
Control A
calculating frequency
1.0kg/2G
Value in Table 27
overload control
normal control
Table 27
Running capacity
(HP)
intake pressure
Outdoor air temperature (
)
< -5
< 0
< 5
< 10
< 15
> 15
1.20
1.20
1.20
1.20
1.20
1.20
9.12. Low load control
Low load control/intake pressure lower limit protection (cooling)
For cooling operation, if the intake pressure is less than 2.5 kg/cm G, the operation frequency
of the compressor will be 90% or less of the operation frequency calculated in normal control
(the lower limit frequency is 30Hz); when the intake pressure reaches 3.50 kg/cm G, normal
control will be resumed.
2
2
94
10 Min 30 Seconds
10 Min 30 Seconds
10 Min 30 Seconds
During cooling operation, if the outdoor heat exchanger temperature exceeds 60.5
for 10
seconds, the overload control is activated. The operation frequency of the compressor will be
90% of the frequency in normal control or lower.( The lower limit is 30 Hz). See the diagram
below.
CU-MP28DBH5/CU-MP50DBH5
For
heating operation, if any running indoor unit receives low load signal, the operation
frequency of the compressor will be 90% or less of the operation frequency in normal control
(the lower limit frequency is 30Hz); when all the indoor units are released from low load signal,
normal control will be resumed.
Overload control/outlet pressure upper limit protection (heating)
When the air-conditioer is running, if the compressor outlet temperature is detected to be over
105
, the liquid bypass valve will be opened; if the outlet falls under 80
or the compressor
is stopped, the liquid bypass valve will be closed.
When the air-conditioner is running, if the compressor outlet temperature is detected to be
over 110
, the operation frequency of the compressor (detected once every 3 minutes) will be
90% or less of the operation frequency in normal control (the lower limit frequency is 30Hz); if
the outlet temperature falls under 95
or the compressor is stopped, normal control will be
resumed. When it continues to fall under 80
, the liquid bypass valve will be closed.
For cooling operation, if the outdoor heat exchanger temperature is detected to be under 25
for 60 seconds, the outdoor fan will stop for 30 seconds.
Condensation or evaporation temperature control
/ outlet pressure upper limit protection
Condensation or evaporation temperature control/ intake
pressure upper limit protection
When the air-conditioner is running, if the intake pressure is detected to be over 7.70 kg/cm G
for 10 seconds, the compressor will run with 30Hz for 30 seconds.
2
Compressor outlet temperature control
For heating operation, if the running indoor unit detects the
condensation or evaporation
temperature control signal, the outdoor fan will run with high speed.
9.13. Functions of operation buttons
(Wireless remote control of wall-mounted type, Hide-away Direct-blow Type and
cassette type units are the same)
AUTO OFF/ON button
The operation mode depends on the time for pressing.
Seen as the following graph:
AUTO
OFF/ON
POWER
TIMER
FILTER
Refrigerant distributor
address selecting mode
Refrigerant distributor
address selecting mode
Test Run
ON
Auto
Forced
Cooling
Remote control
Number setting
Mode
Refrigerant distributor
Address confirmation
Mode
Receiver sound
Control
later press
preferential
Beep
Beep
2
Beep
3
Beep
4
Beep
5
Beep
6
8Sec.
11Sec.
16Sec.
21Sec.
26Sec.
31Sec.
95
Forced
Heating
CU-MP28DBH5/CU-MP50DBH5
Remote Control Address Number
Beep
ADDRESS NO. 1
ADDRESS NO. 2
ADDRESS NO. 3
Beep-
Refrigerant distributor address confirmation mode: press the AUTO OFF/ON button for 16 to
21 seconds and release it, the refrigerant distributor address will be shown on the display of
the wall-mounted type indoor unit for 5 minutes, but not for other types.
Refrigerant distributor address selecting mode (only for wall-mounted type): press the AUTO
OFF/ON button for 21 to 26 seconds and release it, the address will be shown on the display of
the indoor unit as the graph.
Display
on
Display
off
1
2
3
1
2s
0.5s
0.5s
0.5s
0.5s
2s
2s
2s
Receiver sound control mode: press the AUTO OFF/ON button for 26 to 31 seconds and
release it. The receiver sound can be switched on or off.
Mute
Long "beep"
Soniferous
Short "beep"
Operation of remote
control buttons
Mute
Long "beep"
In various kinds of modes, if there is not any operation within 5 minutes, it will remove
automatically.
Press for 1 second to run automatic operation.
Press for 5 seconds to run forced cooling operation and 8 seconds to run forced heating
operation ;
Press for 11 seconds to run with the previous settings;
If the indoor intake temperature is under 16
, the system will automatically run in heating mode;
Remote control number setting mode: the remote control can be set to be corresponding to
one or more units; in the operation process, adjust the wireless remote control to be the
required number and press the test operation button. When you hear three continuous beeps,
release it and press the temperature adjusting button of the wireless remote control.
Actions of the indoor unit when pressing OFF/ON button on the wireless remote controller
Actions of remote control
Actions of air-conditioner
Cooling + TEST RUN
Forced cooling operation (Fan speed: Hi)
Soft Dry + TEST RUN
Forced cooling operation (fan speed: Hi)
Heating + TEST RUN
Forced heating operation
(fan speed: wall-mounted type: Shi other: Hi)
Air Circulation + TEST RUN
Forced fan operation (fan speed: Hi)
Auto + TEST RUN
Forced fan operation (fan speed: Hi)
96