Capacity of all the indoor units = Basic frequency of all the indoor units
coefficient of
indoor units
Load coefficient of indoor unit
Formula 5
Model
Total capacity of indoor units = capacity sum of each indoor unit
Formula 6
Basic frequency of all the indoor units
Table 16
1 H P
1.5HP
1.8HP
2 H P
2.5HP
3 H P
16Hz
24Hz
28Hz
32Hz
40Hz
48Hz
Mode coefficient of indoor units
Table 17
Wall-Mounted Type
Cassette Type
Hide-away Duct Type (Medium Static Pressure)
Hide-away Duct Type (Low Static Pressure)
Hide-away Direct-blow Type
1.03
1.10
0.92
0.97
1.10
Correction coefficient of outdoor air temperature
(decided by the outdoor temperature and the operation horsepower)
Outdoor air
temperature
Outdoor air temperature (
)
<-5
<0
<5
<10
>10
Table 18
~ 1HP
~3HP
~5HP
> 5HP
2.7
2.3
1
1
1
1.5
1.2
1
1
1
1.2
1
1
1
1
1
1
1
1
1
Compressor operation frequency for heating = total capacity of indoor unit
correction
coefficient of running indoor unit quantity
Formula 4
9.7. Normal control of outdoor fan
For cooling operation, normal control of outdoor fan follows start control. In normal control:
Normal Control A: The outdoor fan speed is determined by the operation frequency of
compressor and the outdoor air temperature ( for fan motor on/off status, see Table 7). (Table
19)
Normal control of outdoor fan (cooling)
operation
frequency of
compressor
Outdoor air temperature (
)
< 0
< 10
< 20
< 25
< 30
> 30
LL
LL
L
L
LL
L
L
ML
L
L
ML
ML
L
ML
M
M
ML
M
H
H
M
H
H
H
Table 19
89
For heating operation, the operation frequency of the compressor is determined by the basic
frequency of the indoor unit (Table 16), the coefficient of indoor unit model (Table 17), the heat
load coefficient of indoor unit and indoor unit capacity (Formula 5), total capacity of indoor unit
(Formula 6) and the correction coefficient of quantity of running indoor units (Table 18) etc.
CU-MP28DBH5/CU-MP50DBH5
The speed of the outdoor fan will be adjusted once every 15 seconds according to the above-
mentioned condition. Additionally, only if the temperature mentioned in the table above
remains for 2 minutes, the change of the temperature can be detected.
Control B: if the temperature of the outdoor heat exchanger exceeds 50
, the fan
speed will be different. When it falls under 45
, resume Control A. Seen as the following
graph:
in Control A
Conceptual graph of Control B
Control A
<45
>50
Control B
Control C: in Control A, if the temperature of the outdoor heat exchanger falls under 30
, the
fan speed will be different. When it exceeds 35
, resume Control A. Seen as the following
graph:
Conceptual graph of Control c
Control C
<30
>35
Control A
Normal control of outdoor fan (heating)
Operation
frequency of
compressor
Outdoor air temperature (
)
< -5
< 0
< 5
< 10
< 15
> 15
H
H
H
H
M
H
H
H
M
M
H
H
M
M
H
H
ML
M
M
H
L
ML
M
H
Table 20
The speed of the outdoor fan will be adjusted once every 15 seconds.
Control B: in Control A, if the temperature of the outdoor heat exchanger falls under -7
, the
fan speed will fall by one tap. When it exceeds -2
, resume Control A. Seen as the following
graph:
Conceptual graph of Control B
Control A
>-2
<-7
Control B
90
For heating operation, normal control of outdoor fan follows start control. In normal control:
Normal Control A: The outdoor fan speed is determined by the operation frequency of
compressor and the outdoor air temperature ( for fan motor on/off status , see Table 7). (Table
20)
CU-MP28DBH5/CU-MP50DBH5
Conceptual graph of Control C
Control C
>-2
<-7
Control B
Control C: in Control A, if the temperature of the outdoor heat exchanger falls under -7
and
lasts for 10 seconds, the fan speed will rise by one tap. When it exceeds -2
and lasts for 10
seconds, resume Control A. Seen as the following graph:
In control C, when the fan speed is H, a tap that will not rise.
9.8. Normal control of electromagnetic expansion valve
For cooling operation, the normal control of the electronic expansion valve follows the initial
setting. During cooling operation, the opening of the electromagnetic expansion valve will be
kept at 480 degrees (There will be correction coefficient for operation frequency, intake air
temperature, outlet temperature etc.)
Normal control of electromagnetic expansion valve (cooling)
For cooling operation, the normal control of the electronic expansion valve follows the initial
setting. During cooling operation, the opening of the electromagnetic expansion valve will be
set according to the running capacity. Seen as the following table (Table 21), control the
expansion valve between the lower and upper limit.
Normal control of electromagnetic expansion valve (heating)
running capacity (HP)
Lower limit of opening
Basic opening
Upper limit of opening
Table 21
<1.5HP
<1.5HP
<1.5HP
< 1.5HP
100
170
250
130
225
350
160
250
400
200
300
450
Control of the expansion valve is decided by the intake temperature and the outdoor heat
exchange SH (Outdoor heat exchange SH = Intake temperature - Outdoor heat exchanging
temperature). The following table will show the opening and closing of the outdoor
electromagnetic expansion valve. The opening of the electromagnetic expansion valve is
represented by relative opening. + is the direction of valve opening, while - is the direction of
closing the valve. When the running capacity is changing , refer to the basic opening in Table
21. The adjustment time of the electromagnetic expansion valve is 30 seconds each time.
Table 22
Outdoor heat exchange SH
<-10
<-5
<0
>0
<70
<80
<90
>90
-5
-3
0
+3
-5
-2
0
+3
-3
0
0
+5
-2
0
+3
+7
91
Outlet Temperature (
)
CU-MP28DBH5/CU-MP50DBH5
The longest time of heating oil-return control is 5 minutes. This control will be released in
5 minutes.
Table 24
Compressor
Outdoor electromagnetic expansion valve
Outdoor fan
4-way valve
Indoor electromagnetic expansion valve
operation fixed at 45Hz
Normal control (480)
Normal control
Normal control (ON)
Fixed at 480 degrees
Oil-return control (heating)
When the accumulative operation time exceeds 360 minutes, the durative operation time
exceeds 180 minutes, or 60 minutes after last heating oil-return control or deicing control
ended, or when the outlet temperature in heating overload control is over 115
for 5 minutes,
the compressor will enter heating oil-return control. Seen as the following table (Table 24):
9.10. Deicing operation
Note: When the accumulative operation time is reached, the heat exchanger temperature must be
kept in the range as shown in the following Table for 5 minutes.
Deicing Operation
According to the outdoor heat exchanger temperature T , the heating accumulative operation
time, the outdoor air temperature, etc., deicing operation will start as the following table
(Table 25).
The longest time of cooling oil-return control is 5 minutes. This control will be released in
5 minutes.
Table 23
Compressor
Outdoor electromagnetic expansion valve
Outdoor fan
4-way valve
Indoor electromagnetic expansion valve
Operation fixed at 50Hz
Normal control (480)
Normal control
Normal control (OFF)
Fixed at 280 degrees
Table 25
Outdoor air temperature
>-3
-3
>T>-10
<10
Heating accumulative
operation time (minute)
Heat exchanger
temperature (
)
75
45
100
70
115
85
-5
T>-7
-7
T7
-10
T>-12
-12
T
-20
T>-12
-22
T
9.9. Oil-return control
Oil-return control (cooling)
When the accumulative operation time exceeds 360 minutes or the durative operation time
exceeds 180 minutes, the compressor will enter cooling oil-return control. At this moment,
the compressor will run on the fixed frequency of 50Hz. The outdoor electromagnetic
expansion valve, the outdoor fan and 4-way valve are all in normal control. The indoor
electromagnetic expansion valve is fixed at 280 degrees. Seen as the following table (Table
23):
92
CU-MP28DBH5/CU-MP50DBH5
Page of 127