 2. Heating
Note:
 a. UP:
     • 
• 
• 
• 
If move from Lo, the fan speed will be shifted to Maximum 1,520 rpm.
     • 
• 
• 
• 
If move from Maximum, the fan speed no change.
     • 
• 
• 
• 
In up zone, 10 rpm is added for every 10 seconds until Maximum 1,520 rpm.
 b. DOWN:
     • 
• 
• 
• 
The fan speed will be decreased one step every 10 seconds until Minimum 1,270 rpm.
 c. Current Output Fixed:
     • 
• 
• 
• 
Maintain at present fan speed.
 d. Instantaneous Maximum:
     • 
• 
• 
• 
Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
C. Fan Motor Control
 1. Motor specification
High voltage PWM Motor
 2. Feedback Control
 a. Number-of -rotations feedback
Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed. For high voltage
PWM motor. It is done once every 0.5 seconds.
 b. Offset duty T max/min limit
High voltage PWM motor has maximum offset duty.
(Refer to indoor fan motor control basic rotation speed.)
 3. Abnormal detection Control
Conditions:
 a. Out of rhythm signal input
 b. If feedback number of rotations exceeded 2,550 rpm or when less than 50 rpm.
Control: Fans stop.
Return: Restart after 5 seconds.
* It will not detect out of rhythm condition within 5 seconds for phase control motor (PWM motor is when duty = 0) after start.
A fan stops when condition (1) and (2) happen within 25.0 seconds after fan starting, and if this happens for continuously
7 times, it will not retry.
FM lock processing
 4. Restart Prohibition Control
Restart is prohibited within 5 seconds for phase control motor (PWM motor is when duty = 0) after dan stop (except re-ON
the power supply)
45
CS-ME7DKEG CS-ME10DD3EG / CS-ME10DTEG CS-E15DB4EW
D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follows.
* When COMP is ON
1
2
3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
5
6
7
6
←→
7
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
9.1.1.8. Airflow Direction
 1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
 2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature
and intake air temperature) and manual (angles of direction can be adjusted using remote control).
Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (°)
1
2
3
4
5
Heating
Auto with Heat Exchanger
A
Upward fix
3
Temperature
B
Downward fix
64
C
Downward fix
3
D
Downward fix
3
Manual
3
17
33
49
63
Cooling, Soft Dry and Ion
Auto
8 ~ 36
Manual
8
15
22
30
36
Mode judgment in Auto
Auto
8
Manual
8
15
22
30
36
 1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
 2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the
positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to
close position.
46
CS-ME7DKEG CS-ME10DD3EG / CS-ME10DTEG CS-E15DB4EW
Horizontal Airflow
 1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
Operation Mode
Vane Angle (°)
Heating, with heat exchanger temperature
A
65 ~ 115
B
90
Cooling, Soft Dry and Ion
65 ~ 115
 2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern
1
2
3
4
5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
90
65
78
102
115
9.1.1.9. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
     • 
• 
• 
• 
When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. Timer “off” activates.
 d. Quiet button is pressed again.
47
CS-ME7DKEG CS-ME10DD3EG / CS-ME10DTEG CS-E15DB4EW
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
C. Control contents
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -1 step from setting fan speed.
9.1.1.10. Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
     • 
• 
• 
• 
When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. Timer “off” activates.
 d. Quiet button is pressed again.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
C. Control contents
a. Fan Speed manual
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -1 step from setting fan speed.
 3. Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.