ORDER NO. MAC9807010C3
CS-MC90KH
Operation Details
3)  Air Circulation Mode Operation
• When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences
at low airflow volume. It stops when the temperature drops to 2
°
C below the setting temperature.
Air Circulation Mode Operation Time Diagram
ON
Setting
Temp.
OFF
Compressor
Indoor Fan
Outdoor Fan
Operation
Indication LED
2°C
Intake Air Temp.
a                b                 c                d                 e
Lo
Lo
Operation
Stop
Higher
+2
°
C
Standard
±
0
°
C
Lower
–2
°
C
Cooling
27
°
C
25
°
C
23
°
C
Soft Dry
24
°
C
22
°
C
20
°
C
Cooling Mode
Soft Dry Mode
Setting Temperature (Standard)
25
°
C
22
°
C
Cooling Mode
Soft Dry Mode
23
°
C
Intake air
temperature
4) Automatic Mode Operation
Standard for Determining Operation Mode
(a) Indoor fan operates at Lo fan speed for 20 seconds.
(b) After judging indoor air temperature, the operation mode is determined and operation continued at the mode
determined.
(c) After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation
includes Cooling mode operation.
(d) If Automatic Mode operation is started while the air conditioner is operating, operation will continue. If current
operation is in Cooling mode (including the operation which is a part of Soft Dry mode operation), it will be
maintained, for 20 seconds at Lo fan speed. Then, the selected operation mode will continue.
(e) Room temperature adjustment.
The following are added to the setting temperature specified as above.
Untitled-17
6/26/00, 3:38 PM
24
– 25 –
ORDER NO. MAC9807010C3
CS-MC90KH
Operation Details
5) Sleep Mode Auto Operation
Cooling or Soft Dry Operation
6) Auto Restart Control
• If there is a power failure, operation will be automatically restarted when the  power is resumed.
It will start with previous operation mode and airflow direction.
(Time Delay Safety Control is valid)
• Auto Restart Control is not available when Timer or Sleep Mode is set.
• This control can be omitted by cutting the jumper wire J2. (Refer Circuit Diagram)
When you press the SLEEP Mode, the following move-
ment will start to avoid overcooling.
• The fan speed is automatically set to Low.
• The setting temperature will be risen by 0.5
°
C at the
start of operation and by 0.5
°
C one hour later.
• The operation will stop after 8 hours.
7) Indoor Fan Speed Control
• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the
table.
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection
button.
START
STOP
1 HOUR
8 HOURS
0.5°C UP
0.5°C UP
SET
TEMP.
Fan Speed
Hi
t
t
Manual
Automatic
Cooling
Soft Dry
Air Circulation
Me
t
t
Lo
t
t
t
SLo
t
*
 SLo: Indoor Fan rotates at 4-second intervals at Low speed.
Stop
t
t
Untitled-17
6/26/00, 3:38 PM
25
– 26  –
ORDER NO. MAC9807010C3
CS-MC90KH
Operation Details
*
The left and right airflow direction louvers can be
adjusted manually.
Lower limit for
Cooling Mode and
Soft Dry Mode
Lower limit for Air Circulation Mode
When set a Airflow Direction Auto-Control with
remote control, the louver swings up and down as
shown in the diagram.
The louver does not swing when the Indoor Fan
stops during operation.
When stopped with remote control, the discharge
vent is closed with the louver.
8) Airflow Direction Control
34
°
58
°
Horizontal
Airflow Direction Auto-Control
Swing up and down
Upper limit
*
 1 There is no swinging while indoor fan is stopped during Cooling and Soft Dry operation.
*
 2 In Air Circulation operation, when the intake air temperature reaches set temperature, the airflow direction is
changed from upper limit to lower limit. When the intake air temperature falls to 2
°
C lower than set temperature,
the airflow direction is changed from lower limit to upper limit.
When the airflow direction set button is pressed,
the automatic airflow is released and the airflow
direction louver move up and down in the range
shown in the diagram.
The louver can be stopped by releasing the button
at the desired louver position.
When the remote control is used to stop the opera-
tion, the discharge vent is closed with airflow
direction louver.
• When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time,
so that the room will reach nearly to the set temperature by the desired time.
• For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
• For Automatic mode, the indoor fan will operate at SLo speed for 20 seconds 15 minutes before the set time to detect
the intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
9) Delay ON Timer Control
*
The left and right airflow direction louvers can be
adjusted manually.
Lower limit for
Cooling Mode and
Soft Dry Mode
Lower limit for Air Circulation Mode
The louver can be adjusted with in a range
“Airflow Direction Setting Button” is pressed.
34
°
58
°
Horizontal
Airflow Direction Manual Control
Upper limit
Untitled-17
6/26/00, 3:38 PM
26
– 27 –
ORDER NO. MAC9807010C3
CS-MC90KH
Installation Information
Attached accessories
Accessories: Flaring piping kit
CZ-3F5, 7AEN
SELECT THE BEST LOCATION
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Indoor unit of this room air conditioner shall be installed on the wall in a height of at least 2.3 m.
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If piping length is over the rated length, additional refrigerant should be added as shown in the table.
Qty.
1
6
1
2
2
No.
1
2
3
4
5
Accessories part
Installation plate
Installation plate fixing screw
Remote control
Battery
Air purifying filter
MODEL
MC140K
MC180K
3MC200K
Piping size
Gas
3/8"
3/8"
3/8"
Liquid
1/4"
1/4"
1/4"
Rated
Length
10
10
10
Max.
Elevation
(m)
5
5
5
Max.
Piping
Length
(m)
15
15
15
Additional
Refrigerant
(g/m)
15
15
15
INDOOR UNIT
OUTDOOR UNIT
No.
6
7
8
9
!
Qty.
1
3
1
1
2
Accessories part
Clamping cover of piping
Vinyl tape
Vinyl tape
Remote
control
holder
Remote control
holder fixing
screw
Untitled-18
6/26/00, 3:39 PM
27
Page of 83